Gree GMV6 DC Inverter VRF Units Service Manual
52
current screen and the unit will resume displaying the current status. (During setting, press SW4 to return
to the previous process. If the setting is completed, press SW4 to resume the unit to the current normal
working status.)
4.2.3.6 n3 Forced Defrosting
Introduction:
This function is used when forced defrosting is required during unit maintenance. After entering
forced defrosting, the system automatically exits according to the exit conditions, and then automatically
runs according to the system conditions.
Setting steps:
Step 1:
Enter n3 forced defrosting, and ensure that the master unit displays as follows:
LED1
LED2
LED3
Function code
Display status
Current
process/mode
Display status
Current status
Display status
n3
On
00
Blinks
00
Blinks
Step 2:
Press the SW3 confirm button. The master module displays as follows:
LED1
LED2
LED3
Function code
Display status
Current
process/mode
Display status
Current status
Display status
n3
On
00
On
00
On
If the defrosting condition is not met, the module displays the set mode. If the setting is completed,
press SW4 to resume the unit to the current normal working status.
When the defrosting exit condition is met, the system automatically exits and resumes normal running
control.
4.2.3.7 n4 Forced Energy Saving Mode
Introduction:
The maximum output capability limit is used in scenarios where the user needs to forcibly limit the
system power consumption. Available functions are as follows:
Code
Maximum Output Capability
10
100% (default setting)
09
90%
08
80%
After the capability limit is set, the cooling or heating effect is correspondingly reduced.
Setting steps:
Step 1:
Enter n4 maximum output capability limit setting, and ensure that the master unit displays
as follows:
LED1
LED2
LED3
Function code
Display status
Current
process/mode
Display status
Current status
Display status
n4
On
10
Blinks
OC
Blinks
Step 2:
Press the SW1 up button and the SW2 down button to select the corresponding value.
Содержание GMV-1015WM/G-U
Страница 212: ...Gree GMV6 DC Inverter VRF Units Service Manual 210 Models GMV 400WM G U GMV 450WM G U GMV 504WM G U...
Страница 229: ...Gree GMV6 DC Inverter VRF Units Service Manual 227 Models GMV 400WM G U GMV 450WM G U GMV 504WM G U...
Страница 234: ...Gree GMV6 DC Inverter VRF Units Service Manual 232...
Страница 264: ...Gree GMV6 DC Inverter VRF Units Service Manual 262...
Страница 325: ...Gree GMV6 DC Inverter VRF Units Service Manual 323 GMV 400WM G U GMV 450WM G U and GMV 504WM G U...
Страница 331: ...JF00304610...