Gree GMV6 DC Inverter VRF Units Service Manual
190
“
PH
”
Compressor drive DC
bus high voltage protection
Compressor drive
board is abnormal
Yes
Check if power supply voltage
is higher than 430V or 780V
(for 460V- voltage)
No
Replace the compressor
drive board
Yes
Adjust the voltage to 208/230V
or 460V(for 460V-voltage)
2.161 "PL" Under Voltage Protection for DC Bus of Compressor
Drive
Fault display:
main board of outdoor unit displays
Applicable models: GMV6, GMV5, GMV5S series
Fault diagnosis:
When the input power cable of the main board has a voltage below 320 V, the unit triggers protection
against faults.
Possible causes:
■
Power voltage is lower than 200V or 360V(for 460V-voltage);
■
Compressor drive board is abnormal.
Troubleshooting:
“
PL
”
Compressor drive DC
bus low voltage protection
Compressor drive
board is abnormal
Yes
Check if power supply voltage
is lower than 200V or 360V
(for 460V- voltage)
No
Replace the compressor
drive board
Yes
Adjust the voltage to 208/230V
or 460V(for 460V-voltage)
2.162 "PJ" Inverter Compressor Startup Failure
Fault display:
main board of outdoor unit displays
Fault diagnosis:
If the fault code displayed on the 2-digit digital LED of the outdoor unit's main control board is PJ, it
indicates the inverter compressor startup failure.
Possible causes:
■ Poor contact of compressor's UVW cables;
Содержание GMV-1015WM/G-U
Страница 212: ...Gree GMV6 DC Inverter VRF Units Service Manual 210 Models GMV 400WM G U GMV 450WM G U GMV 504WM G U...
Страница 229: ...Gree GMV6 DC Inverter VRF Units Service Manual 227 Models GMV 400WM G U GMV 450WM G U GMV 504WM G U...
Страница 234: ...Gree GMV6 DC Inverter VRF Units Service Manual 232...
Страница 264: ...Gree GMV6 DC Inverter VRF Units Service Manual 262...
Страница 325: ...Gree GMV6 DC Inverter VRF Units Service Manual 323 GMV 400WM G U GMV 450WM G U and GMV 504WM G U...
Страница 331: ...JF00304610...