Gree GMV6 DC Inverter VRF Units Service Manual
16
Checklist Before GMV6 Commissioning
Category
No.
Item
Reference Value
Qualified
Inspector
Refrigerating
system
17
Is the stop valve of each module
open to the maximum opening?
—
18
Is the refrigerant pressure normal?
Connect the high pressure gauge
of the pressure gauge to the liquid
pipe valve of the outdoor unit,
connect the low pressure gauge to
the gas pipe valve, and read the
value.
At this time, the high and
low pressures of the system
are in balance, and the
difference between the
saturation temperature
corresponding to the
balanced pressure value
and the ambient
temperature (higher one of
the indoor and outdoor
temperatures) does not
exceed 5°C. If it exceeds
5°C, check for the outdoor
unit leakage.
19
Is there any leakage of chiller oil at
the valve?
If so, immediately check for valve
leakage with soap bubbles or a
leak detector. If leakage is
confirmed, stop subsequent
commissioning at once, and
continue the work only after the
problem is solved.
—
20
Is the outdoor unit being warmed
up for more than 2 hours before
commissioning?
—
Electrical
system
21
Is the power cable connected
correctly? Is the terminal block
secure?
—
22
Is the power cable appearance in
good condition and not exposed?
The appearance is in good
condition and not exposed.
23
Is the power capacity less than the
maximum power of the unit?
The power capacity is not
less than the maximum
power of the unit.
24
Is there any poorly connected
electrical component detected
when the power is off?
All components are reliably
connected.
25
Do the cable diameters of the
indoor and outdoor units meet the
unit design requirements?
Refer to electrical
installation.
26
Do the circuit breaker and leakage
switch meet the unit design
requirements?
Refer to electrical
installation.
27
Do the power voltage, phase
sequence, and frequency meet the
unit requirements?
The power voltage, phase
sequence, and frequency
are consistent with those on
the unit nameplate, and the
voltage fluctuates within
±10%.
28
Is the power cable more than 1 m
away from a TV?
—
29
Is there any strong electromagnetic
interference, dust, acid and alkaline
gas in the environment where the
unit is located?
—
Содержание GMV-1015WM/G-U
Страница 212: ...Gree GMV6 DC Inverter VRF Units Service Manual 210 Models GMV 400WM G U GMV 450WM G U GMV 504WM G U...
Страница 229: ...Gree GMV6 DC Inverter VRF Units Service Manual 227 Models GMV 400WM G U GMV 450WM G U GMV 504WM G U...
Страница 234: ...Gree GMV6 DC Inverter VRF Units Service Manual 232...
Страница 264: ...Gree GMV6 DC Inverter VRF Units Service Manual 262...
Страница 325: ...Gree GMV6 DC Inverter VRF Units Service Manual 323 GMV 400WM G U GMV 450WM G U and GMV 504WM G U...
Страница 331: ...JF00304610...