Possible causes:
■ If two or more master units' DIP switches (SA2) are detected to be master unit's DIP switches,
keep only one master unit's DIP switch (SA2) to be "00000" and other master units' DIP switches (SA2)
to be different;
■ Abnormal DIP switch or main board.
Troubleshooting:
Yes
"CJ" System Address Code
Conflict
Keep the SA2 DIP switch to be
"00000" for only one master unit, and
set that for other master units to be
different. After redialing, power on the
redialed units again
The detection circuit may
operate improperly
Yes
Replace the main control
board
No
Whether two or more master units'
DIP switches (SA2) are set to the master
unit's DIP switches?