241
When the compressor frequency is 120 Hz, the current curve corresponding to the evaporation
temperature and condensation temperature is shown as follows:
When the compressor is working at another frequency, the current curve can be obtained through
interpolation calculation of the above frequency.
(2) Inverter compressor DA80PHDG-A1Y2:
When the compressor frequency is 30 Hz, the current curve corresponding to the evaporation
temperature and condensation temperature is shown as follows:
When the compressor frequency is 60 Hz, the current curve corresponding to the evaporation
temperature and condensation temperature is shown as follows: