Gree GMV6 DC Inverter VRF Units Service Manual
88
Yes
No
No
"bA" Oil Return
Temperature Sensor Fault
Whether the interface
terminal between the main board and
temperature sensor gets loose or
contains foreign matters?
Remove the foreign
matters and plug it tightly
Whether the temperature
sensor is abnormal?
Yes
Replace the temperature
sensor
The detection circuit may
operate improperly
Yes
Replace the main control
board
2.27
"
bd
"
Subcooler air inlet temperature sensor error
Error display:
ODU main board, IDU wired controller, IDU receive light board will display
Applicable model:
all ODUs
Error judgment condition and method:
Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge
the range of AD value. If the sampling AD value exceeds upper limit and lower limit in 30 seconds
continuously, report the error
Possible reasons:
■Poor contact between
temperature sensor and terminal in main board interface
■Temperature sensor is abnormal
■Detecting circuit is abnormal
Troubleshooting: