Gree GMV6 DC Inverter VRF Units Service Manual
29
LED1
LED2
LED3
Function code
Display status
Current process
Display status
Current status
Display status
1G
On
01
Blinks
OC
Blinks
Press the SW1 up button and the SW2 down button to select the corresponding basic module: 00
means all modules, 01~04 means module 1 to module 4.
LED1
LED2
LED3
Function code
Display status
Current process
Display status
Current status
Display status
1G
On
00
Blinks
OC
Blinks
1G
On
01
Blinks
OC
Blinks
1G
On
02
Blinks
OC
Blinks
1G
On
03
Blinks
OC
Blinks
1G
On
04
Blinks
OC
Blinks
After selecting the corresponding basic module, press the SW3 confirm button. The module displays
as follows. The current factory default status is 00. Value 00 represents 0 Pa outdoor static pressure, 01
represents 30 Pa, 02 represents 50 Pa, 03 represents 80 Pa, and 04 represents 110 Pa.
LED1
LED2
LED3
Function code
Display status
Mode
Display status
Current status
Display status
1G
On
ADD
On
00
Blinks
Press the SW1 up button and the SW2 down button to select the corresponding static pressure mode
for the outdoor unit.
LED1
LED2
LED3
Function code
Display status
Mode
Display status
Current status
Display status
1G
On
ADD
On
00
Blinks
1G
On
ADD
On
01
Blinks
1G
On
ADD
On
02
Blinks
1G
On
ADD
On
03
Blinks
1G
On
ADD
On
04
Blinks
After selecting the corresponding static pressure mode for the outdoor unit, press the SW3 confirm
button. The master module displays as follows:
LED1
LED2
LED3
Function code
Display status
Mode
Display status
Current status
Display status
1G
On
ADD
On
00
On
1G
On
ADD
On
01
On
1G
On
ADD
On
02
On
1G
On
ADD
On
03
On
1G
On
ADD
On
04
On
Each basic module memorizes this setting and does not clear it even upon power failure and power-
on again. The default value is 00.
Step 6:
Switch the commissioning software to the commissioning control interface.
Click "Debug" to switch to the engineering commissioning interface. The unit will automatically
operate the commissioning modules listed in this interface from top to bottom and from left to right. Note:
The commissioning function only applies to the single-system network.
Содержание GMV-1015WM/G-U
Страница 212: ...Gree GMV6 DC Inverter VRF Units Service Manual 210 Models GMV 400WM G U GMV 450WM G U GMV 504WM G U...
Страница 229: ...Gree GMV6 DC Inverter VRF Units Service Manual 227 Models GMV 400WM G U GMV 450WM G U GMV 504WM G U...
Страница 234: ...Gree GMV6 DC Inverter VRF Units Service Manual 232...
Страница 264: ...Gree GMV6 DC Inverter VRF Units Service Manual 262...
Страница 325: ...Gree GMV6 DC Inverter VRF Units Service Manual 323 GMV 400WM G U GMV 450WM G U and GMV 504WM G U...
Страница 331: ...JF00304610...