Gree GMV6 DC Inverter VRF Units Service Manual
321
Outdoor units Combination
Power
Fuse Capacity Minimum Circuit
Ampacity
Maximum
Overcurrent
Protection
Cross-sectional
Area of Power
Cable Conductor
V/Ph/Hz
A
A
A
mm²
GMV-
1230WM/G-U 615+615
440~460V
3~ 60Hz
40+40
38.0+38.0
40+40
4*6.0+4*6.0
GMV-
1295WM/G-U 615+680
440~460V
3~ 60Hz
40+45
38.0+40.9
40+45
4*6.0+4*10.0
GMV-
1360WM/G-U 680+680
440~460V
3~ 60Hz
45+45
40.9+40.9
45+45
4*10.0+4*10.0
GMV-
1399WM/G-U
335+504+56
0
440~460V
3~ 60Hz
20+30+40
21.0+25.0+36.2
20+30+40
4*4.0+4*4.0+4*6.0
GMV-
1455WM/G-U
280+560+61
5
440~460V
3~ 60Hz
20+40+40
20.0+36.2+38.0
20+40+40
4*4.0+4*6.0+4*6.0
GMV-
1510WM/G-U
280+615+61
5
440~460V
3~ 60Hz
20+40+40
20.0+38.0+38.0
20+40+40
4*4.0+4*6.0+4*6.0
GMV-
1565WM/G-U
335+615+61
5
440~460V
3~ 60Hz
20+40+40
21.0+38.0+38.0
20+40+40
4*4.0+4*6.0+4*6.0
GMV-
1623WM/G-U
504+504+61
5
440~460V
3~ 60Hz
30+30+40
25.0+25.0+38.0
30+30+40
4*4.0+4*4.0+4*6.0
GMV-
1679WM/G-U
504+560+61
5
440~460V
3~ 60Hz
30+40+40
25.0+36.2+38.0
30+40+40
4*4.0+4*6.0+4*6.0
GMV-
1734WM/G-U
504+615+61
5
440~460V
3~ 60Hz
30+40+40
25.0+38.0+38.0
30+40+40
4*4.0+4*6.0+4*6.0
GMV-
1790WM/G-U
560+615+61
5
440~460V
3~ 60Hz
40+40+40
36.2+38.0+38.0
40+40+40
4*6.0+4*6.0+4*6.0
GMV-
1845WM/G-U
615+615+61
5
440~460V
3~ 60Hz
40+40+40
38.0+38.0+38.0
40+40+40
4*6.0+4*6.0+4*6.0
GMV-
1910WM/G-U
615+615+68
0
440~460V
3~ 60Hz
40+40+45
38.0+38.0+40.9
40+40+45
4*6.0+4*6.0+4*10.0
GMV-
1975WM/G-U
615+680+68
0
440~460V
3~ 60Hz
40+45+45
38.0+40.9+40.9
40+45+45
4*6.0+4*10.0+4*10.
0
GMV-
2040WM/G-U
680+680+68
0
440~460V
3~ 60Hz
45+45+45
40.9+40.9+40.9
45+45+45
4*10.0+4*10.0+4*1
0.0
GMV-
2069WM/G-U
335+504+61
5+615
440~460V
3~ 60Hz 20+30+40+40
21.0+25.0+38.0+
38.0
20+30+40+40 4*4.0+4*4.0+4*6.0+
4*6.0
GMV-
2129WM/G-U
450+504+56
0+615
440~460V
3~ 60Hz 30+30+40+40
24.2+25.0+36.2+
38.0
30+30+40+40 4*4.0+4*4.0+4*6.0+
4*6.0
GMV-
2190WM/G-U
400+560+61
5+615
440~460V
3~ 60Hz 30+40+40+40
23.9+36.2+38.0+
38.0
30+40+40+40 4*4.0+4*6.0+4*6.0+
4*6.0
GMV-
2245WM/G-U
450+615+61
5+615
440~460V
3~ 60Hz 30+40+40+40
23.9+38.0+38.0+
38.0
30+40+40+40 4*4.0+4*6.0+4*6.0+
4*6.0
GMV-
2295WM/G-U
560+560+56
0+615
440~460V
3~ 60Hz 40+40+40+40
36.2+36.2+36.2+
38.0
40+40+40+40 4*6.0+4*6.0+4*6.0+
4*6.0
GMV-
2350WM/G-U
560+560+61
5+615
440~460V
3~ 60Hz 40+40+40+40
36.2+36.2+38.0+
38.0
40+40+40+40 4*6.0+4*6.0+4*6.0+
4*6.0
GMV-
2414WM/G-U
504+615+61
5+680
440~460V
3~ 60Hz 30+40+40+45
25.0+38.0+38.0+
40.9
30+40+40+45 4*4.0+4*6.0+4*6.0+
4*10.0
GMV-
2470WM/G-U
560+615+61
5+680
440~460V
3~ 60Hz 40+40+40+45
36.2+38.0+38.0+
40.9
40+40+40+45 4*6.0+4*6.0+4*6.0+
4*10.0
GMV-
2525WM/G-U
615+615+61
5+680
440~460V
3~ 60Hz 40+40+40+45
38.0+38.0+38.0+
40.9
40+40+40+45 4*6.0+4*6.0+4*6.0+
4*10.0
GMV-
2590WM/G-U
615+615+68
0+680
440~460V
3~ 60Hz 40+40+45+45
38.0+38.0+40.9+
40.9
40+40+45+45 4*6.0+4*6.0+4*10.0
+4*10.0
GMV-
2655WM/G-U
615+680+68
0+680
440~460V
3~ 60Hz 40+45+45+45
38.0+40.9+40.9+
40.9
40+45+45+45 4*6.0+4*10.0+4*10.
0+4*10.0
GMV-
2720WM/G-U
680+680+68
0+680
440~460V
3~ 60Hz 45+45+45+45
40.9+40.9+40.9+
40.9
45+45+45+45 4*10.0+4*10.0+4*1
0.0+4*10.0
NOTICE!
1. Copper-core cable which complies with local regulations must be applied.
2. According to on-site installation conditions, local regulations must be met.
Содержание GMV-1015WM/G-U
Страница 212: ...Gree GMV6 DC Inverter VRF Units Service Manual 210 Models GMV 400WM G U GMV 450WM G U GMV 504WM G U...
Страница 229: ...Gree GMV6 DC Inverter VRF Units Service Manual 227 Models GMV 400WM G U GMV 450WM G U GMV 504WM G U...
Страница 234: ...Gree GMV6 DC Inverter VRF Units Service Manual 232...
Страница 264: ...Gree GMV6 DC Inverter VRF Units Service Manual 262...
Страница 325: ...Gree GMV6 DC Inverter VRF Units Service Manual 323 GMV 400WM G U GMV 450WM G U and GMV 504WM G U...
Страница 331: ...JF00304610...