Gree GMV6 DC Inverter VRF Units Service Manual
57
follows:
LED1
LED2
LED3
Function code
Display status
Current process
Display status
Current status
Display status
C9
On
00
Blinks
OC
Blinks
Press the SW1 up button and the SW2 down button to select the corresponding compressor
emergency operation status.
LED1
LED2
LED3
Description
Function
code
Display
status
Current
process
Display
status
Current
status
Display
status
C9
On
00
Blinks
OC
Blinks
Fans 1 and 2 run normally.
C9
On
01
Blinks
OC
Blinks
The operation of fan 1 is
shielded.
C9
On
02
Blinks
OC
Blinks
The operation of fan 2 is
shielded.
After selecting the corresponding value, press the SW3 confirm button. All modules display as follows:
LED1
LED2
LED3
Function code
Display status
Mode
Display status
Current status
Display status
C9
On
00
On
OC
On
C9
On
01
On
OC
On
C9
On
02
On
OC
On
The basic module memorizes this setting and does not clear it even upon power failure and power-
on again. The default value is 00.
Then, press the SW4 back button to return to the previous process. (During setting, press SW4 to
return to the previous process. If the setting is completed, press SW4 to resume the unit to the current
normal working status.)
If you do not press any button in 5 minutes, the system will automatically exit the current screen and
the unit will resume displaying the current status.
If a basic module sets compressor failure emergency operation, the status indicators and LEDs on
the module indicate the corresponding status.
LED1
LED2
LED3
Description
Module address
Module
failure/indoor unit
failure
Module status
ADD
C9
ON
System running-fan emergency operation
status
ADD
C9
OF
System standby-fan emergency operation
status
①
This function is applicable only to dual-fan models;
②
A module can set only one fan to emergency mode;
③
The default status is 00.
④
The system cannot run continuously for more than 120 hours in fan emergency operation
status. If it exceeds 120 hours, the entire system is stopped, and the indoor unit displays the
"Ad" limit operation code.
Содержание GMV-1015WM/G-U
Страница 212: ...Gree GMV6 DC Inverter VRF Units Service Manual 210 Models GMV 400WM G U GMV 450WM G U GMV 504WM G U...
Страница 229: ...Gree GMV6 DC Inverter VRF Units Service Manual 227 Models GMV 400WM G U GMV 450WM G U GMV 504WM G U...
Страница 234: ...Gree GMV6 DC Inverter VRF Units Service Manual 232...
Страница 264: ...Gree GMV6 DC Inverter VRF Units Service Manual 262...
Страница 325: ...Gree GMV6 DC Inverter VRF Units Service Manual 323 GMV 400WM G U GMV 450WM G U and GMV 504WM G U...
Страница 331: ...JF00304610...