Gree GMV6 DC Inverter VRF Units Service Manual
147
2.103 "H9" Loss of Synchronization Protection for Inverter Fan
Fault display:
main board of outdoor unit displays
Fault diagnosis:
If the fault code displayed on the 2-digit digital LED of the outdoor unit's main control board is H9, it
indicates the loss of synchronization protection for the inverter fan.
Possible causes:
■ Poor contact of fan's UVW cables;
■ The fan is damaged;
■ The blades are stuck (the blades are blocked or the motor shaft
gets rusty);
■ The fan drive board operates improperly.
Troubleshooting:
"H9" Loss of
Synchronization Protection
for the Inverter Fan
The fan drive board is
abnormal
Yes
Replace the fan drive board
No
Whether the U, V and W phases
of fan wires are connected properly?
Yes
No
Replace the fan
Whether the resistance between
the windings of each phase for the fan is normal
(generally less than 10 ohms)? Whether the resistance values are
equal to each other? Is grounding insulation of the phase
windings of the fan normal (generally greater
than 2 megohms)?
Ye
s
Yes
Remove foreign matters
Whether blades are stuck due to foreign
matters or rusting of motor shaft?
Yes
Yes
Replace the faulty fan
Have other faults occurred
at the same time (for example, over-current
protection (H5), IPM module protection (H6),
start failure (HJ))?
Содержание GMV-1015WM/G-U
Страница 212: ...Gree GMV6 DC Inverter VRF Units Service Manual 210 Models GMV 400WM G U GMV 450WM G U GMV 504WM G U...
Страница 229: ...Gree GMV6 DC Inverter VRF Units Service Manual 227 Models GMV 400WM G U GMV 450WM G U GMV 504WM G U...
Страница 234: ...Gree GMV6 DC Inverter VRF Units Service Manual 232...
Страница 264: ...Gree GMV6 DC Inverter VRF Units Service Manual 262...
Страница 325: ...Gree GMV6 DC Inverter VRF Units Service Manual 323 GMV 400WM G U GMV 450WM G U and GMV 504WM G U...
Страница 331: ...JF00304610...