Gree GMV6 DC Inverter VRF Units Service Manual
149
“
HH
”
fan drive DC bus high
voltage protection
Fan drive board is
abnormal
Yes
Check if power supply voltage
is higher than 430V or 780V
(for 460V- voltage)
No
Replace the fan drive
board
Yes
Adjust the voltage to 208/230V
or 460V(for 460V-voltage)
2.106 "HL" Under Voltage Protection for DC Bus of Fan Drive
Fault display:
main board of outdoor unit displays
Fault diagnosis:
If the fault code displayed on the 2-digit digital LED of the outdoor unit's main control board is HL, it
indicates the under voltage protection for the DC bus of fan drive.
Possible causes:
■
Power voltage is lower than 200V or 360V(for 460V-voltage);;
■
Fan drive board is abnormal.
Troubleshooting:
“
HH
”
fan drive DC bus low
voltage protection
Fan drive board is
abnormal
Yes
Check if power supply voltage
is lower than 200V or 360V
(for 460V- voltage)
No
Replace the fan drive
board
Yes
Adjust the voltage to 208/230V
or 460V(for 460V-voltage)