Gree GMV6 DC Inverter VRF Units Service Manual
86
Yes
No
No
"b8" Outdoor Humidity
Sensor Fault
Whether the interface
terminal between the main board and
temperature sensor gets loose or
contains foreign matters?
Remove the foreign
matters and plug it tightly
Whether the temperature
sensor is abnormal?
Yes
Replace the temperature
sensor
The detection circuit may
operate improperly
Yes
Replace the main control
board
2.25 "b9" Heat Exchanger's Gas Outlet Temperature Sensor Fault
Fault display:
main board of outdoor unit, wired controller of indoor unit and receiver of indoor unit
display
Fault diagnosis:
The temperature sensor detection circuit samples the AD value of temperature sensor and
determines the range of AD value. When the sampled AD value exceeds the limits for 30 consecutive
seconds, the fault is generated.
Possible causes:
■ Poor contact between the temperature sensor and the main
board interface;
■ Abnormal temperature sensor;
■ Abnormal detection circuit.
Troubleshooting:
Содержание GMV-1015WM/G-U
Страница 212: ...Gree GMV6 DC Inverter VRF Units Service Manual 210 Models GMV 400WM G U GMV 450WM G U GMV 504WM G U...
Страница 229: ...Gree GMV6 DC Inverter VRF Units Service Manual 227 Models GMV 400WM G U GMV 450WM G U GMV 504WM G U...
Страница 234: ...Gree GMV6 DC Inverter VRF Units Service Manual 232...
Страница 264: ...Gree GMV6 DC Inverter VRF Units Service Manual 262...
Страница 325: ...Gree GMV6 DC Inverter VRF Units Service Manual 323 GMV 400WM G U GMV 450WM G U and GMV 504WM G U...
Страница 331: ...JF00304610...