Gree GMV6 DC Inverter VRF Units Service Manual
69
↓
LED1
LED2
LED3
Parameter code
Display status
Parameter code
Display status
Parameter code
Display status
nb
On
Pc
Blinks
-n
Blinks
↓
LED1
LED2
LED3
Parameter code
Display status
Parameter code
Display status
Parameter code
Display status
N1
On
M0
On
12
On
↓
LED1
LED2
LED3
Parameter code
Display status
Parameter code
Display status
Parameter code
Display status
81
On
50
On
06
On
↓
LED1
LED2
LED3
Parameter code
Display status
Parameter code
Display status
Parameter code
Display status
7X
On/Off
XX
Off
XX
Off
If a parameter is invalid on the unit, value "00" is displayed.
If there are two levels of menus on the master unit, you can press the SW4 back button to return to
the previous level. Press the SW4 query button again to exit query status.
If you do not press any button on the master unit in 5 minutes, the system will automatically exit the
current screen and the unit will resume displaying the current status.
4.3 Restoration to Default Settings
Restoration to default settings 1 (clearing all settings)
On the main board of the master unit, press and hold the SW1 up button and SW4 back button for
over 10 seconds to restore the system default settings. All modules display as follows:
LED1
LED2
LED3
Meaning
Address
code
Display
status
Function
code
Display
status
Status code
Display
status
Restoration to default
settings 1
ADD
On
01
On
0C
Blinks for 3
seconds
At this time, the system clears all settings, including engineering numbers of the indoor and outdoor
units, quantities of the indoor and outdoor units, and commissioning completion status.
Restoration to default settings 2 (clearing all settings except the commissioning status)
On the main board of the master unit, press and hold the SW2 down button and SW4 back button
for over 10 seconds to clear all the system settings. All modules display as follows:
LED1
LED2
LED3
Meaning
Address
code
Display
status
Function
code
Display
status
Status code
Display
status
Restoration to default
settings 2
ADD
On
02
On
0C
Blinks for 3
seconds
At this time, the system clears all settings, including engineering numbers of the indoor and outdoor
units, but stores quantities of the indoor and outdoor units, and commissioning completion status.
Restoration to default settings 3 (clearing only function settings of the outdoor unit)
On the main board of the master unit, press and hold the SW3 back button and SW4 back button for
over 10 seconds to clear all the system settings. All modules display as follows:
Содержание GMV-1015WM/G-U
Страница 212: ...Gree GMV6 DC Inverter VRF Units Service Manual 210 Models GMV 400WM G U GMV 450WM G U GMV 504WM G U...
Страница 229: ...Gree GMV6 DC Inverter VRF Units Service Manual 227 Models GMV 400WM G U GMV 450WM G U GMV 504WM G U...
Страница 234: ...Gree GMV6 DC Inverter VRF Units Service Manual 232...
Страница 264: ...Gree GMV6 DC Inverter VRF Units Service Manual 262...
Страница 325: ...Gree GMV6 DC Inverter VRF Units Service Manual 323 GMV 400WM G U GMV 450WM G U and GMV 504WM G U...
Страница 331: ...JF00304610...