8.2.2
Replacing the Closing and Opening Coil
• Disconnect the wire connections from the coil (3).
• Push aside the leaf spring (1) with your finger in the direction of
the arrow.
• Lift out the yoke (2) and place it on a clean surface.
• Replace the yoke (2) and mount the leaf spring (1).
• Check the fit of the leaf spring (1): it must snap into place.
• Connect the coil (3).
1
Leaf spring
-
2
Yoke
-
3
Coil
-
4
Side plate
-
1 2
3
4
1
2
3
4
Remove the coil being replaced and insert a new coil over the
side plates (4).
The wrong coil type can cause the mechanism to malfunction.
Make sure you have the correct coil type. Compare the part
number on the coils.
CAUTION