T
ECHNICAL
D
ESCRIPTION
OI 250 (EN)
REV7
/REV1
A5.2
Technical Data: Spring Operating Mechanism
Type
FK 3-1
Motor for charging the closing spring
Rated voltage (preferred values)
- Direct voltage
V
60/110/125/220/250 *)
- Alternating voltage
V
120/230 *)
Allowable rated voltage deviation
85 to 110 % Vn
Power consumption
W
750
Closing spring charging time
s
< 15
Shunt releases, closing and opening:
Rated supply voltage
(preferred values only with direct voltage)
V
60/110/125/220/250 *)
Allowable rated supply voltage deviation
- Shunt closing release
85 to 110 % Vn
- Shunt opening release
70 to 110 % Vn
Power consumption of releases
- Shunt closing release
W
340
- Shunt opening release
W
340
Minimum pulse duration
ms
10
Auxiliary circuits:
Rated continuous load current
A
10
Auxiliary contact tripping capability
- At 230 V alternating voltage
A
10
- At 220 V direct voltage in an inductive circuit with a
time constant of L/R = 20 ms
A
2
Anti-condensation heating unit:
Rated voltage (preferred values)
V
120 or 230 *)
Power consumption
W
80
*) Specify when ordering.
Содержание GL 311 F3/4031 P/VE
Страница 2: ......
Страница 10: ...INTRODUCTION 10 146 OI 250 EN REV7 REV6...
Страница 12: ...SAFETY 12 146 OI 250 EN REV7 REV3...
Страница 48: ...INSTALLATION 48 146 OI 250 EN REV7 REV7...
Страница 80: ...INSPECTION AND MAINTENANCE 80 146 OI 250 EN REV7 REV3...
Страница 102: ...RECONDITIONING 102 146 OI 250 EN REV7 REV7...
Страница 104: ...END OF LIFE MANAGEMENT 104 146 OI 250 EN REV7 REV2a...
Страница 114: ...SPECIAL EQUIPMENT OPTIONAL 114 146 OI 250 EN REV7 REV0...
Страница 128: ...REPLACEMENT PARTS AND ACCESSORIES 128 146 OI 250 EN REV7 REV6...
Страница 130: ...HANDLING USED SULFUR HEXAFLUORIDE 130 146 OI 250 EN REV7 REV2...