T
ROUBLESHOOTING
OI 250 (EN)
REV7
/REV2
8.2
Mechanism Reconditioning Procedures
8.2.1
Replacing the Charging Motor
• Disconnect both wires from the motor limit switch.
• Unscrew the M6 mounting screws and remove the motor.
• Install the new motor and tighten the mounting screws to a torque
of 7Nm.
• Reconnect the wires to the motor limit switch.
M6
MO
T
O
R
Lubrication of the motor pinion may cause the operating
mechanism to malfunction.
Do not grease or lubricate the motor pinion.
CAUTION
If the wiring is incorrect, the motor will stall and may become
damaged.
Turn on the power to the motor briefly and check to see whether
the motor drives the gear unit.
If this is not the case:
- Turn off the power to the motor immediately.
- Check the connections and correct if necessary.
CAUTION