R
ECONDITIONING
REV7
/REV7
OI 250 (EN)
10.1.6
Reconditioning the Fixed Contact
• Replace the guide strip (12). The guide strip is located in a
dovetail groove. It is therefore necessary to overcome
mechanical resistance when replacing it.
10.1.7
Lubricating the Interrupter Unit
• Unpack and grease a new interrupter unit (5).
- Lubricate the outer diameter of the interrupter unit in the area of
the electrical sliding contact surface per lubrication specification
L6.
- Grease the entire length of the interrupter tube in the interrupter
unit per lubrication specification L7.
12
Guide strip, 3x5x380 (GK)
1x
12
BA
-P
-PS
-6
5
Interrupter unit
1x
L7