Critical Power
Modifications reserved
Page 16/60
GE_UPS_ISG_TLE_SUL_M16_M50_2bU_V010.docx
Installation Guide
TLE Series 160 - 500 UL S2B
4.2
DELIVERY
When delivered, inspect the
package integrity
and
the physical condition of the cabinets
carefully.
In case of any damage sustained during transport, immediately inform the carrier and contact your
GE
Service Center
.
A
detailed report
of the damage is necessary for any insurance claim.
NOTE !
A damaged UPS must never be installed or connected to
Utility
or
Battery
!
4.3
STORAGE
4.3.1
Storage of the UPS
The equipment is carefully packed for transport and
storage so that it is in a perfect condition when eventually
installed.
Never leave an UPS outside the building and do not store
the UPS one on top of the other.
We recommend to store the UPS in its original package in
a
dry, dust-free room, away from chemical substances,
and with a temperature range not exceeding -
13°F
(-25°C)
to
131°F
(55°C).
In case the battery is included please refer to
Section 4.3.2
.
Some important functions of the UPS, such as the customized functions, are defined by parameters
stored in a
RAM memory
.
A small backup
Battery
located on the Control Unit board supplies the RAM.
If the storage time of the UPS exceeds
1 year
, these functions
should be verified
by an authorized
GE
Service Center
before putting the UPS into operation.
4.3.2
Storage of Battery
When the delivery includes a maintenance free
Battery
, keep in mind that they are subject to self-
discharge and therefore you must recharge the
Battery
.
The storage time without
Battery
recharge depends on the temperature of the storage site.
The optimal temperature for
Battery
storage is
68°F
(20°C)
to
77°F
(25°C) and shall never exceed the
range
-4°F
(-20°C) to
104°F
(40°C).
Recharge stored maintenance free
Battery
every:
6 months when the storage temperature is 68°F (20°C)
3 months when the storage temperature is 86°F (30°C)
2 months when the storage temperature is 95°F (35°C)
Содержание FGC TLE Series
Страница 1: ...TLE SERIES UPS 40 150 KVA KW 480 VAC Three phase Highly Efficient and Scalable GE Industrial Solutions...
Страница 14: ...14 LP33 Series II UPS www gecriticalpower com Notes...
Страница 15: ...15 LP33 Series II UPS www gecriticalpower com Notes...
Страница 333: ...TLE Series UPS 225 1500 kW for best in class multi mode operating efficiency...