TLE Series 625 - 750 - 1000 UL S2
7.3.6
Restore to normal operation after “EPO - Emergency Power Off” with Load not
supplied
WARNING !
Please check and ensure the conditions of the connected load are safe before
proceeding, as this procedure will result in the connection of power to the load
circuit(s).
NOTE !
Before performing this operation, make sure that all units of the
Parallel System
are
in the following status:
“Q1 - UPS Output switch”
MUST BE CLOSED.
“External Battery Protections”
MUST BE DISCONNECTED.
If
eBoost™
option is available, make sure that
eBoost™ Operation Mode
is disabled
before starting this procedure.
If
IEMi
option is available, make sure that
IEMi Operation Mode
is disabled before
starting this procedure.
View of the
Synoptic Diagram
, on all UPS
units, after performed the command “
EPO -
Emergency Power Off”,
with LOAD NOT
SUPPLIED.
1. Restore the “EPO -Emergency Power Off” button.
•
Press
“MUTE”
key to reset
Alarm
and
Acoustical Alarm
.
•
LED ALARM
remains lit.
2. Perform the “Inverter OFF” command on all Units.
Perform the
“Inverter OFF”
command from the screen:
Commands 1 / Inverter /
OFF
.
•
Rectifiers
start automatically.
LEDs 1 (Rectifier)
blinking, indicates
Soft-start
.
•
After performed the
“Inverter OFF”
command on the last unit of the
Parallel System
, the output of all
Units
connect to
Automatic Bypass
.
The
Synoptic Diagram
, on all UPS units, must display the status
“
LOAD SUPPLIED BY AUTOMATIC BYPASS
”
.
Synoptic diagram of first unit
Synoptic diagram of other units
Continue
→
Содержание FGC TLE Series
Страница 1: ...TLE SERIES UPS 40 150 KVA KW 480 VAC Three phase Highly Efficient and Scalable GE Industrial Solutions...
Страница 14: ...14 LP33 Series II UPS www gecriticalpower com Notes...
Страница 15: ...15 LP33 Series II UPS www gecriticalpower com Notes...
Страница 333: ...TLE Series UPS 225 1500 kW for best in class multi mode operating efficiency...