Page 83/90
GE_UPS_USM_TLE_SUL_40K_M15_1US_V010.docx
User Manual
TLE Scalable Series 40 - 150 UL S1
7.3.5
Restore to normal operation after “System shutdown” with Load not supplied
WARNING !
Please check and ensure the conditions of the connected load are safe before
proceeding, as this procedure will result in the connection of power to the load
circuit(s).
NOTE !
Before performing this operation, make sure that all units of the
Parallel System
are
in the following status:
“Q1 - UPS Output switch”
MUST BE CLOSED (Pos. I).
“Battery Cabinet Breaker”
MUST BE OPEN (Pos. O).
Make sure that
SEM Operation Mode
is disabled before starting this procedure.
If
IEMi
option is available, make sure that
IEMi Operation Mode
is disabled before
starting this procedure.
View of the
Synoptic Diagram
, on all UPS
units, after performed the command “
System
shutdown”,
with LOAD NOT SUPPLIED.
1. Restore the command “System shutdown” of
the Parallel System
.
Restore the command
“System shutdown”
, on
anyone of the Parallel Units, through
the screen:
Commands 1 / System shutdown /
Reset
.
•
The
Load
is supplied by the
Utility
through the
Automatic Bypass
of all
Units
.
•
Rectifiers
start automatically, blinking
LED 1 (Rectifier)
indicates Soft-start.
•
At the end of
Rectifier
Soft-start, the
LED 1 (Rectifier)
remains lit.
LED ALARM
are lit.
The
Synoptic Diagram
, on all UPS units, must display the status
“
LOAD SUPPLIED BY AUTOMATIC BYPASS
”
.
Synoptic diagram of first unit
Synoptic diagram of other units
Continue
→
Содержание FGC TLE Series
Страница 1: ...TLE SERIES UPS 40 150 KVA KW 480 VAC Three phase Highly Efficient and Scalable GE Industrial Solutions...
Страница 14: ...14 LP33 Series II UPS www gecriticalpower com Notes...
Страница 15: ...15 LP33 Series II UPS www gecriticalpower com Notes...
Страница 333: ...TLE Series UPS 225 1500 kW for best in class multi mode operating efficiency...