Critical Power
Modifications reserved
Page 42/69
GE_UPS_ISG_TLE_SUL_M62_1M0_2US_V010.docx
Installation Guide
TLE Series 625 - 750 - 1000 UL S2
TLE Series 625 - 750 - 1000
Power connection bus bars configuration for the top cable entry or bottom cable entry
The configuration of the
TLE Series 625 - 750 - 1000
is with top cable entry as standard (see
Fig. 4.9-3)
.
It is possible to configure the bus bars with bottom cable entry (see
Fig. 4.9-4)
.
Fig. 4.9-3 TLE Series 625 - 750 - 1000 – Power connection configuration bus bars with top cable entry (standard)
Power connection cables are connected to bus bars using
M12 bolts
.
The bolts of the connection cables must be tightened with a torque wrench at
530 Lb-in / 60 Nm
.
Fig. 4.9-4 TLE Series 625 - 750 - 1000 - Power connection configuration bus bars with bottom cable entry
Position of the bus bars for
cables input from the top of the UPS
Q1
Top entry cables
Utility input & Load output
Load
L3
Load
L2
Load
L1
BR3
BR2
BR1
L3-1
L2-1
L1-1
L3-2
L2-2
L1-2
N
N
Q1
Top entry cables
Utility input & Load output
TLE Series 1000
TLE Series 625 & 750
Position of the bus bars for
cables input from the bottom of the UPS
Q1
Load
L3
Load
L2
Load
L1
BR3
BR2
L3-1
L2-1
L3-2
L2-2
N
Bottom entry cables
Utility input & Load output
BR1
L1-1
L1-2
N
Q1
TLE Series 1000
TLE Series 625 & 750
Bottom entry cables
Utility input & Load output
Содержание FGC TLE Series
Страница 1: ...TLE SERIES UPS 40 150 KVA KW 480 VAC Three phase Highly Efficient and Scalable GE Industrial Solutions...
Страница 14: ...14 LP33 Series II UPS www gecriticalpower com Notes...
Страница 15: ...15 LP33 Series II UPS www gecriticalpower com Notes...
Страница 333: ...TLE Series UPS 225 1500 kW for best in class multi mode operating efficiency...