Critical Power
Modifications reserved
Page 21/60
GE_UPS_ISG_TLE_SUL_M16_M50_2bU_V010.docx
Installation Guide
TLE Series 160 - 500 UL S2B
4.5
VENTILATION AND COOLING
Fig. 4.5-1 Installation on plain floor
Fig. 4.5-2 Installation on raised floor
The heat produced by the UPS is transferred to the environment by its ventilation.
Air inlets for UPS ventilation are located on the front of the UPS, while air outlets are on top of the
cabinet.
A suitable ventilation or cooling system must be installed to extract the heat from the UPS room.
NOTE !
Do not put anything on the top of the cabinet.
19.7” (500mm) of air clearance MUST BE LEFT from the top of the UPS for a sufficient
exhausted air exchange, proper cooling, service access and safety.
Air filtering systems could be required when the UPS operates in a dirty environment.
In order to prevent overheating of the UPS, the available air intake flow rate must exceed the total air
exhaust flow rate requirement of the UPS system.
Contact your
GE Service Center
for appropriate solutions.
The below table indicates the heat dissipation at full
Load
at
PF = 1
and charged
Battery
, up to
3280 ft
(1000 m) altitude, for cooling air
77°F
(25°C) to
86°F
(30°C).
UPS model
Losses
Cooling air flow
VFI
eBoost™ (option)
VFI
PF = 1
PF = 1
PF = 1
TLE Series 160
20137 BTU/hr
5.9 kW
6826 BTU/hr
2.0 kW
1013 CFM
1721 m
3
/h
TLE Series 200
25256 BTU/hr
7.4 kW
8532 BTU/hr
2.5 kW
1270 CFM
2158 m
3
/h
TLE Series 225
27986 BTU/hr
8.2 kW
10922 BTU/hr
3.2 kW
1408 CFM
2392 m
3
/h
TLE Series 250
31741 BTU/hr
9.3 kW
10239 BTU/hr
3.0 kW
1597 CFM
2713 m
3
/h
TLE Series 300
32765 BTU/hr
9.6 kW
12799 BTU/hr
3.8 kW
1648 CFM
2800 m
3
/h
TLE Series 400
48123 BTU/hr
14.1 kW 18089 BTU/hr
5.3 kW
2421 CFM
4113 m
3
/h
TLE Series 500
63823 BTU/hr
18.7 kW 20819 BTU/hr
6.1 kW
3210 CFM
5454 m
3
/h
NOTE !
Even when
eBoost™ Operating Mode
option is available, the ventilation and cooling
system shall be rated as for operation in
VFI mode
.
Air E
xtrac
tion
Air
Int
ake
TLES_
600-8
00_S1
_UPS v
entila
tion_R
aised
floor_0
1GB
Air In
take
TLES
_600-
800_
S1_
UPS v
entilat
ion_Ra
ised f
loor_
01G
B
Air Ex
trac
tion
Содержание FGC TLE Series
Страница 1: ...TLE SERIES UPS 40 150 KVA KW 480 VAC Three phase Highly Efficient and Scalable GE Industrial Solutions...
Страница 14: ...14 LP33 Series II UPS www gecriticalpower com Notes...
Страница 15: ...15 LP33 Series II UPS www gecriticalpower com Notes...
Страница 333: ...TLE Series UPS 225 1500 kW for best in class multi mode operating efficiency...