Modifications reserved
Page 50/90
GE_UPS_USM_TLE_SUL_40K_M15_1US_V010.docx
User Manual
TLE Scalable Series 40 - 150 UL S1
Module shutdown
Module shutdown
Load Off command for a single UPS.
NOTE !
This command will immediately disconnect the
Load
.
“Module shutdown”
cannot disconnect the UPS from the
Load
with
“Q2 -
Manual Bypass switch”
(only if provided by customer) closed.
For the RPA Parallel System
In an RPA Parallel System, the “Module shutdown” command disconnects the
Load to the selected unit only (“Q1 – UPS Output switch” closed).
Module shutdown RESET
“Module shutdown”
restore command for an individual UPS.
Led Module shutdown status
Shows the
“Module shutdown”
status: ACTIVE / NOT ACTIVE
System shutdown
System shutdown
Load Off command for an
RPA Parallel System
.
NOTE !
This command will immediately disconnect the
Load
.
“System shutdown”
cannot disconnect the
RPA Parallel System
from the
Load
with
“Q2 - Manual Bypass switch”
(only if provided by customer) closed.
For the RPA Parallel System
If “System shutdown”
is pressed on one unit connected to the Parallel Bus (“Q1 –
UPS Output switch” closed), all the units are separated from the Load.
System shutdown RESET
“System shutdown”
restore command for a
RPA Parallel System
.
For the RPA Parallel System
The “System shutdown reset” must be done only on one unit connected to the
Parallel Bus (“Q1 – UPS Output switch” closed).
Led System shutdown status
Shows the
“System shutdown”
status: ACTIVE / NOT ACTIVE
Booster
Only for
Service Center
.
Содержание FGC TLE Series
Страница 1: ...TLE SERIES UPS 40 150 KVA KW 480 VAC Three phase Highly Efficient and Scalable GE Industrial Solutions...
Страница 14: ...14 LP33 Series II UPS www gecriticalpower com Notes...
Страница 15: ...15 LP33 Series II UPS www gecriticalpower com Notes...
Страница 333: ...TLE Series UPS 225 1500 kW for best in class multi mode operating efficiency...