GE_UPS_ISG_TLE_SUL_M16_M50_2bU_V010.docx
Installation Guide
TLE Series 160 - 500 UL S2B
Fig. 4.4.1-9 TLE Series 160 - 220 - 225 - 250
RPA Parallel System disposition
Fig. 4.4.1-10 TLE Series 300 - 400 - 500
RPA Parallel System disposition
In case of
Parallel System
, try to place the UPS modules in sequence of their numbers
(marked on the packing).
If the units are positioned “
side by side
”, the side panels must be mounted on all
units.
4.4.2
Battery location
Batteries require a well-ventilated room with controlled temperature to obtain reliable operation.
The
Battery
can be installed immediately adjacent to the UPS (left or right side) or remotely from the
UPS.
If the
Battery
is installed remotely from the UPS, a wall mounted DC disconnect device must be installed
within line-of-site to both the UPS and the
Battery
.
The optimal room temperature for
Battery
storage is
68°F
(20°C)
to
77°F
(25°C) and shall never exceed
the range
-4°F
(-20°C) to
104°F
(40°C).
The life of valve-regulated batteries will be reduced by 50% for each additional
18°F
(10°C) that the
battery ambient temperature is above
77°F
(25°C).
The
Battery System
associated with larger UPS is usually either rack mounted or installed in multiple
Battery Cabinets
.
Installation and assembly must be made according to the local standards and
Battery System
manufacturer‘s recommendations.
The
Battery Circuit Breaker
or
Battery Fuse Box
must be mounted as near as possible to the
Battery
.
WARNING !
Battery
installation and connection must be performed by qualified personnel
only.
Read all safety instructions before proceeding with the installation (see
Section 1)
.
Battery discharging and/or charging activities may cause the emission of
hydrogen gas; therefore, the room requires proper ventilation and fresh air.
Comply with the UL1778-CSAC22.2no170.3 UPS safety standard, ANSI/IEEE P1184
Guide for Batteries for Uninterruptible Power Supply Systems and applicable codes
and governmental regulations.
TLES_UL_2
25-250_S1_
RPA dispos
ition_GE_01U
S
UPS
3 - 4 - 5 - 6
UPS 2
UPS 1
TLES_UL_4
00-500_S1_
RPA dispos
ition_GE_0
1US
UPS
3 - 4 - 5 - 6
UPS 1
UPS 2
Содержание FGC TLE Series
Страница 1: ...TLE SERIES UPS 40 150 KVA KW 480 VAC Three phase Highly Efficient and Scalable GE Industrial Solutions...
Страница 14: ...14 LP33 Series II UPS www gecriticalpower com Notes...
Страница 15: ...15 LP33 Series II UPS www gecriticalpower com Notes...
Страница 333: ...TLE Series UPS 225 1500 kW for best in class multi mode operating efficiency...