background image

Critical Power 

 

Modifications reserved 

Page 52/53 

GE_UPS_ISG_TLE_SUL_40K_M15_1US_V010.docx 

Installation Guide 

TLE Scalable Series 40 - 150 UL S1

 

 

“Top Cable Entry/Exit Sidecar” (TCE) and “Top Hat Fascia” (THF) assembling

 

 

Fig. 6.1-3   Top Cable Entry/Exit Sidecar (TCE) and Top Hat Fascia (THF) assembling 

 

 

Remove the roof “

A

” of the UPS cabinet.

 

Remove side panel 

“C”

. This panel is no longer used

Remove, with appropriate tool, the two metallic windows 

D

” 

from the metal screen. 

Fix the structure 

“E”

 with the appropriate screws. 

Fix the roof “

A

” of the UPS cabinet. 

Fix the top plate 

“F”

 with the appropriate screws. 

1247B

Knock out appropriate holes in top plate for “Top Cable Entry/Exit Sidecar”. 

Fix side panel 

“G”

 with the appropriate screws. 

Fix the structure 

“Top Hat Fascia - B”

 with the appropriate screws

.

 

 

A

E

F

G

Torx

M5x12

TLES_UL_040-150_

TCE+FCL_

Assembling_GE_01

Top Hat Fascia

Tensilock

M5x12

Torx M5x12

Torx M5x12

B

Top Cable Entry/Exit Sidecar

Torx

M5x12

Torx

M5x12

C

D

Edge protection over the metal cut is
mandatory to protect from sharp edges 

!

Содержание FGC TLE Series

Страница 1: ...TLE SERIES UPS 40 150 KVA KW 480 VAC Three phase Highly Efficient and Scalable GE Industrial Solutions...

Страница 2: ...onitors the output voltage and frequency and will instantaneously switch to double conversion mode and inverter usage during voltage and or frequency disturbances to insure compliance with the ITI CBE...

Страница 3: ...bolt on battery monitoring systems Optional maintenance bypass capabilities via external wrap around cabinetry Optional 208VAC output via matching stepdown transformer cabinetry Optional output distri...

Страница 4: ...ries UPS is equipped with menu driven touch screen display panel provides easy to read details on UPS status and metering parameter settings UPS configuration This user friendly display panel provides...

Страница 5: ...isfeature reducesthe need ofoversizingthe input power system gensets feedercables and overcurrent devices Generator Compatibility User programmable features such as slew rate phase angle rate of chang...

Страница 6: ...reased load capacity or redundancy Scalable The system can be easily expanded for higher capacity and redundancy without any interruption to the critical load ortransferto bypass Distributed Control L...

Страница 7: ...UPS performance is optimized at 50 75 load operation as this is the most common operating range The optimization of theTLE Series includes selecting all major power chain components based on maximizin...

Страница 8: ...Black Service access Front and top access only External cable connections Bottom at the front of the cabinet or top with lateral sidecar Paralleling RPA version Up to 6 units for redundancy or capaci...

Страница 9: ...49 lbs 385 Kg 992 lbs 450 Kg 1147 lbs 520 Kg Floor loading 152 lbs sq ft 742 Kg m2 178 lbs sq ft 867 Kg m2 205 lbs sq ft 1002 Kg m2 Dimensions WxDxH 23 62 x 34 06 x 64 17 inches 600 x 865 x 1630 mm BY...

Страница 10: ...29 40 1 40 0 40 0 29 5 75 0 3 220 lbs 3 220 lbs 38 40 1 40 0 40 0 29 5 75 0 3 500 lbs 3 500 lbs 54 40 1 40 0 40 0 29 5 75 0 4 620 lbs 4 620 lbs 58 80 2 40 0 40 0 29 5 75 0 2 860 lbs 5 720 lbs 77 80 2...

Страница 11: ...bs 13 860 lbs 150Kva 150Kw 5 40 1 40 0 40 0 29 5 75 0 3 500 lbs 3 500 lbs 9 40 1 40 0 40 0 29 5 75 0 4 620 lbs 4 620 lbs 12 80 2 40 0 80 0 29 5 75 0 2 860 lbs 5 720 lbs 17 80 2 40 0 80 0 29 5 75 0 3 2...

Страница 12: ...data transmission SSL encrypted with unidirectional communication iUPSGuard can communicate through various channels and monitors single UPS or parallel UPS systems through web SNMP card Detailed repo...

Страница 13: ...and startup to availability services to help you proactively reduce downtime and meet your service level commitments From installationto product retirement warranty upgradesto remote monitoring proac...

Страница 14: ...14 LP33 Series II UPS www gecriticalpower com Notes...

Страница 15: ...15 LP33 Series II UPS www gecriticalpower com Notes...

Страница 16: ...of the General Electric Company The GE brand logo and lumination are trademarks of the General Electric Company 2017 General Electric Company Information provided is subject to change without notice...

Страница 17: ...Uninterruptible Power Supply GE Consumer Industrial SA General Electric Company CH 6595 Riazzino Locarno Switzerland T 41 0 91 850 51 51 F 41 0 91 850 52 52 www gecriticalpower com imagination at wor...

Страница 18: ...2 2017 File name GE_UPS_ISG_TLE_SUL_40K_M15_1US_V010 Revision 1 0 Identification No 8600123208P Up dating Revision Concern Date COPYRIGHT 2017 by GE Consumer Industrial SA All rights reserved The info...

Страница 19: ...bout the installation of the UPS Thank you for choosing GE START UP AND COMMISSIONING A GE GLOBAL SERVICES FIELD ENGINEER must perform start up and commissioning of the UPS Please Contact GE GLOBAL SE...

Страница 20: ...ing from the use of the information contained in this document WARNING TLE Scalable Series 40 150 is a product that needs to be installed by a licensed and knowledgeable contractor Installation restri...

Страница 21: ...s 40 150 Power connection with Common Input Utility 31 4 8 2 TLE Scalable Series 40 150 Power connection with Dual Input Utility 33 4 8 3 Battery cabinet connection to TLE Scalable Series 40 150 35 4...

Страница 22: ...y accurately during Commissioning and Maintenance of the UPS for the following Damaged components squeezed wires and cables or not correctly inserted plugs After removing the sidewalls of the UPS make...

Страница 23: ...tool to short between individual or separate battery terminals or to the cabinet or rack Do not lay tools or metal parts on top of the battery and do not lay them where they could fall onto the batte...

Страница 24: ...this manual the following symbols are defined WARNING if instruction is not followed injury or serious equipment damage may occur CAUTION internal parts have dangerous voltage present Risk of electri...

Страница 25: ...2 LAYOUT 2 1 LAYOUT TLE SCALABLE Series 40 150 Fig 2 1 1 TLE Scalable Series 40 150 General view Fig 2 1 2 Control panel Fig 2 1 3 Q1 UPS Output switch Fig 2 1 4 Connectivity Slots TLES_040 120_S1_UPS...

Страница 26: ...nection CI Customer Interface Board see Fig 2 1 4 CR Connectivity Slots J35 P Serial port RS232 for IMV protocol Q1 UPS Output switch RPA RPA board Redundant Parallel Architecture for Parallel System...

Страница 27: ...lorid PACKING MATERIAL RECYCLING GE in compliance with environment protection uses only environmentally friendly material UPS packing materials must be recycled in compliance with all applicable regul...

Страница 28: ...the unpacked UPS Forklift The UPS may be lifted with a forklift in upright position Take note of the center of gravity marked on the package Crane Fig 4 1 2 Position of the carrying belts when moving...

Страница 29: ...ns W x D x H Standard UPS 23 62 x 34 06 x 64 17 inches 600 x 865 x 1630 mm UPS with options TCE THF 27 56 x 34 06 x 75 00 inches 700 x 865 x 1905 mm Weight Standard UPS 992 lbs 450 kg UPS with options...

Страница 30: ...0 inches 757 x 750 x 1905 mm 40 00 x 29 50 x 75 00 inches 1016 x 750 x 1905 mm Lbs kg lbs sq ft kg m2 TLE Scalable Series 150 50 TLE Scalable Series 150 80 TLE Scalable Series 150 100 TLE Scalable Ser...

Страница 31: ...ances and with a temperature range not exceeding 13 F 25 C to 131 F 55 C In case the battery is included please refer to Section 4 3 2 Some important functions of the UPS such as the customized functi...

Страница 32: ...ance free Operation at temperatures higher than 77 F 25 C will reduce battery life The TLE Scalable Series 40 150 UPS can radiate radio frequency energy Although some RFI Radio Frequency Interference...

Страница 33: ...g of the UPS cabinet TLE Scalable Series 40 150 on the floor The UPS cabinet is free standing and normally does not require to be bolted to the floor The UPS cabinet can be fixed however to the floor...

Страница 34: ...nge 4 F 20 C to 104 F 40 C The life of valve regulated batteries will be reduced by 50 for each additional 18 F 10 C that the battery ambient temperature is above 77 F 25 C The Battery System associat...

Страница 35: ...tude for cooling air 77 F 25 C to 86 F 30 C UPS model Losses Cooling air flow VFI SEM Super Eco Mode VFI PF 0 9 PF 1 PF 0 9 PF 1 PF 0 9 PF 1 TLE Scalable Series 150 40 6005 BTU hr 1760 kW 6142 BTU hr...

Страница 36: ...GE Service Center Fig 4 6 1 ShockWatch device Fig 4 6 2 TiltWatch device NOTE Be aware of the heavy weight of the UPS pay attention when moving the UPS cabinet Take care not to damage the UPS when mov...

Страница 37: ...etch foil check the status of the A Humidity indicator 10 to 70 The UPS can be commissioned 80 The UPS shall not be commissioned Please contact your GE Service Center Fig 4 6 4 Location of the Protect...

Страница 38: ...d from a Common Input source or Dual Input sources if desired Common Input Utility Rectifier Bypass Fig 4 7 1 1 Common Input Utility Rectifier Bypass The same power source is to be used for both Bypas...

Страница 39: ...connected and grounded solidly due to the existence of voltage surge protection devices inside the UPS The connection of the Battery to the UPS must be protected with fuses or similar devices accordi...

Страница 40: ...requirement is based on the current data below The maximum available fault current from the battery supply is 20kA The minimum breaker voltage rating is 540V Fig 4 7 3 1 Common Input Rectifier Bypass...

Страница 41: ...120 225 A 200 A 225 A 300 A TLE Scalable Series 150 150 300 A 250 A 300 A 400 A WIRING Wire sizing according to NEC Section 210 20 A Table 310 16 Use 194 F 90 C copper Wiring requirements AC INPUT REC...

Страница 42: ...45 6 55 65 75 40 50 60 4 70 85 95 55 65 75 3 85 100 110 65 75 85 2 95 115 130 75 90 100 1 110 130 150 85 100 115 1 0 125 150 170 100 120 135 2 0 145 175 195 115 135 150 3 0 165 200 225 130 155 175 4...

Страница 43: ...e Series 40 150 Single UPS with Common Input Utility for Rectifier Bypass Single UPS with Common Input Utility for Rectifier Bypass 3 wire distribution 3 phase plus ground Single UPS with Dual Input U...

Страница 44: ...S_ISG_TLE_SUL_40K_M15_1US_V010 docx Installation Guide TLE Scalable Series 40 150 UL S1 UPS Parallel System with Common Input Utility Rectifier Bypass UPS Parallel System with Common Input Utility Rec...

Страница 45: ...TLE Scalable Series 40 150 UL S1 UPS Parallel System with Dual Input Utility for Rectifier Bypass Connect a single input Neutral to Bypass Utility inside the UPS common Neutral for Bypass and Rectifi...

Страница 46: ...to avoid risk of short circuit between different poles The grounding and neutral connection of the electrical system must be in accordance with local regulations In case of additional cabinets contain...

Страница 47: ...C L3 PE Ground Input Utility NOTE The interconnection links BR1 BR2 and BR3 on the input bus bars MUST REMAIN CONNECTED see Fig 4 8 1 1 Output Load L1 Load phase A L1 L2 Load phase B L2 L3 Load phase...

Страница 48: ...ain a Neutral Bus as per the following Figure 4 8 1 2 If no Neutral Connection is available with the Bypass Input 3 wire input ground and the Load does not require a Neutral solidly connect the Output...

Страница 49: ...pass phase C L3 PE Ground Input Utility N Neutral Input Utility NOTE The interconnection links BR1 BR2 and BR3 on the input bus bars MUST BE REMOVED see Fig 4 8 2 3 Output Load L1 Load phase A L1 L2 L...

Страница 50: ...ain a Neutral Bus as per the following Figure 4 8 2 2 If no Neutral Connection is available with the Bypass Input 3 wire input ground and the Load does not require a Neutral solidly connect the Output...

Страница 51: ...4B75 C rating size per NEC Table 310 16 and or all applicable national and local codes see also Section 4 7 4 Battery cabinet can be located on either side of the UPS The connecting cables PE are supp...

Страница 52: ...mperature sensor TLES_UL_040 150_S1_UPS IM0284 J14_01US EPO EPO XA Q1 I ON 0 OFF J35 J36 TP5 TP4 C34 C35 C64 C63 C56 C54 L2 L1 J31 J37 J34 J38 C62 C61 R102 R101 R100 R99 R98 R38 R86 R76 R66 R56 R46 R1...

Страница 53: ...input characteristic As the inverter output filter exhibits a predominantly capacitive characteristic it may provide some degree of reactive power compensation when combined with lagging power factor...

Страница 54: ...ency converter the SEM Operation Mode is automatically disabled Fig 4 8 5 1 Interconnection links BR1 BR2 and BR3 In order to avoid improper operation only the Rectifier input should be powered L1 1 L...

Страница 55: ...the same for all units of the Parallel System no phase shift allowed between units NOTE It is strongly recommended that no transformers automatic circuit breakers or fuses should be inserted between...

Страница 56: ...bles In this way communication is maintained between units in case one of the control cables should fail or be accidentally damaged or disconnected The standard length of the control bus cable between...

Страница 57: ...s of a Parallel System the switches SW1 1 2 3 4 5 6 MUST BE IN POSITION ON see Fig 4 9 2 2 Fig 4 9 2 3 Bus connection on intermediate units Intermediate units of a RPA Parallel System On the two board...

Страница 58: ...onnection The communication bus cable connectors are placed on the two boards P13 P14 IM0022 Bus Interface Board see Fig 4 9 3 1 Fig 4 9 3 2 View electronic module on intermediate unit Control bus cab...

Страница 59: ...ONNECTING THEM from the two boards P13 P14 IM0022 Bus Interface Board For reliability reasons the cables J1A J2A 1 2 3 4 5 and J1B J2B 1 2 3 4 5 connecting the units should be run in separated protect...

Страница 60: ...ic Switch NOTE This procedure could imply a Load shut down Keep SELV cables separated from HIGH VOLTAGE cables Fig 4 10 2 XA EPO Emergency Power Off RPA Parallel System connection schematics In a Para...

Страница 61: ...System max 6 UPS it s possible to install the following connectivity boards max 3 Customer Interface boards for each UPS max 2 3 ph SNMP WEB Plug in Adapter boards for Parallel System ATTENTION The i...

Страница 62: ...tware GE iUPSGuard GE Data Protection or GE Service Software for system protection and management of the UPS systems Fig 5 1 2 Serial port J35 P connection to PC with RS232 1 1 cable DB9m DB9f Connect...

Страница 63: ...s On terminals X1 6 of the following 27 signals can be selected from the display entering with the appropriate password Some UPS functions can be activated with parameters when an external Normally Op...

Страница 64: ...N def Parameter RL 5 X1 12 13 14 NO C NC LOAD ON MAINS def Parameter RL 2 X1 15 16 17 NO C NC GENERAL ALARM def Parameter RL 4 X1 18 19 20 NO C NC BUZZER ACOUSTIC ALARM def Parameter RL 6 In case diff...

Страница 65: ...aux contact from the External Bypass Switch to the programmable input X1 10 21 making the UPS operate as if the internal switch Q2 has closed This function can be activated by changing a dedicated pa...

Страница 66: ...provides UPS information via the standard SNMP Protocol UPS MIB RFC 1628 GE Single MIB GE Parallel MIB The UPS can therefore be monitored by a Network Management System NMS or by our applications for...

Страница 67: ...on of input and output cables from the top of the UPS The Top Cable Entry Exit Sidecar can be located on either side of the UPS cabinet The Top Cable Entry Exit Sidecar is accessibly from right side s...

Страница 68: ...etallic windows D from the metal screen Fix the structure E with the appropriate screws Fix the roof A of the UPS cabinet Fix the top plate F with the appropriate screws 1247BKnock out appropriate hol...

Страница 69: ...ocx Installation Guide TLE Scalable Series 40 150 UL S1 7 NOTES 7 1 NOTES FORM It is recommended to note in this section Notes with date and short description all the operations performed on the UPS a...

Страница 70: ...t Uninterruptible Power Supply GE Consumer Industrial SA General Electric Company CH 6595 Riazzino Locarno Switzerland T 41 0 91 850 51 51 F 41 0 91 850 52 52 www gecriticalpower com imagination at wo...

Страница 71: ...sue 10 27 2017 File name GE_UPS_TDS_TLE_SUL_40K_M15_1US_V010 Revision 1 0 Identification No Up dating Revision Concern Date COPYRIGHT 2017 by GE Consumer Industrial SA All rights reserved The informat...

Страница 72: ...e Internal protection All internal live parts shrouded Transport On pallet Cabinet suitable for handling by forklift Color RAL 9005 black Installation Minimum distance from the wall 2 5 cm and floor f...

Страница 73: ...HD for 100 non linear load EN 62040 5 Output voltage tolerance at 100 unbalanced load Ph N 3 Output frequency 60 Hz Output frequency tolerance free running 0 1 with mains synchronization adjustable to...

Страница 74: ...and Dutch Graphic diagram indicating UPS status Command keys and parameters setting UPS status control LED OPTIONS COMMUNICATION OPTIONS 1 Additional Customer Interface Card 2 iUPS Guard 3 GE Data Pr...

Страница 75: ...ranch Circuit Over Current Protection All Models CAUTION To reduce the risk of fire only connect UPS to a circuit provided with see below maximum amperes branch circuit over current protection in acco...

Страница 76: ...lbs 2096 kg 31 80 2 2860 lbs 1297 kg 5720 lbs 2594 kg 41 3220 lbs 1461 kg 6440 lbs 2922 kg 50 3500 lbs 1588 kg 7000 lbs 3176 kg 73 4620 lbs 2096 kg 9240 lbs 4192 kg 100 6 40 1 2860 lbs 1297 kg 2860 l...

Страница 77: ...nterruptible Power Supply GE Consumer Industrial SA General Electric Company CH 6595 Riazzino Locarno Switzerland T 41 0 91 850 51 51 F 41 0 91 850 52 52 www gecriticalpower com imagination at work TL...

Страница 78: ...017 File name GE_UPS_USM_TLE_SUL_40K_M15_1US_V010 Revision 1 0 Identification No 8600123209P Up dating Revision Concern Date COPYRIGHT 2017 by GE Consumer Industrial SA All rights reserved The informa...

Страница 79: ...ut the use of the UPS Thank you for choosing GE START UP AND COMMISSIONING A GE GLOBAL SERVICES FIELD ENGINEER must perform start up and commissioning of the UPS Please Contact GE GLOBAL SERVICES at l...

Страница 80: ...rom the use of the information contained in this document WARNING TLE Scalable Series 40 150 is a product that needs to be installed by a licensed and knowledgeable contractor Installation restriction...

Страница 81: ...rt up of the TLE Scalable Series 40 150 55 7 1 2 Complete UPS shut down 59 7 1 3 Restore to normal operation after System shutdown with Load not supplied 60 7 1 4 Restore to normal operation after EPO...

Страница 82: ...curately during Commissioning and Maintenance of the UPS for the following Damaged components squeezed wires and cables or not correctly inserted plugs After removing the sidewalls of the UPS make sur...

Страница 83: ...ol to short between individual or separate battery terminals or to the cabinet or rack Do not lay tools or metal parts on top of the battery and do not lay them where they could fall onto the battery...

Страница 84: ...is manual the following symbols are defined WARNING if instruction is not followed injury or serious equipment damage may occur CAUTION internal parts have dangerous voltage present Risk of electric s...

Страница 85: ...l view with open door Fig 2 1 6 TLE Scalable Series 80 100 General view with open door Fig 2 1 7 TLE Scalable Series 120 150 General view with open door TLES_040 120_S1_UPS_GE_02 TLES_UL_040 150_S1_Sw...

Страница 86: ...other UPS available allowing you to support a greater number of today s enterprise computing Power Factor Corrected PFC equipment High Efficiency Thanks to type Advanced Neutral Point Clamped three le...

Страница 87: ...s eliminating all single points of failure The decentralized bypass offers great exibility to up or down grade the system in case future needs might change TLE Scalable Series 40 150 BEST IN CLASS EFF...

Страница 88: ...s to modulation strategy applied to IGBT Bridge the rectifier provides clean input power in terms of low THDi and unity power factor Inverter The Inverter converts the DC voltage into a three phase AC...

Страница 89: ...r is available the Load is normally powered through the Automatic Bypass When the Utility Voltage is detected out of the prescribed tolerances the Load is automatically transferred to the Inverter Whe...

Страница 90: ...hen a Battery low warning occurs on a unit not necessary to support the present Load this unit will shut down after a timeout period selectable The Load is shared between the other units As the warnin...

Страница 91: ...dition is corrected the Load will be automatically transferred back to the Inverter Fig 4 2 5 1 Block diagram Automatic Bypass If the UPS is unable to return to normal mode following an automatic tran...

Страница 92: ...control circuitry see Fig 4 3 1 1 Parallel units for power capacity Several units can be paralleled in order to achieve output power greater than the maximum power of a single unit The maximum total...

Страница 93: ...nicates with all other modules in order to act or react if necessary adapting to the new conditions 4 3 4 Synchronization All units are identical but one unit is arbitrarily selected as the reference...

Страница 94: ...required to maintain a reliable supply to the critical load Then an efficiency optimization algorithm determines the best UPS configuration in order to maintain the running UPS in their highest effic...

Страница 95: ...pared in advance before the installation The installation must be performed only with the UPS system completely shut down The AC Rectifiers input power 4 must be the same with clockwise phase rotation...

Страница 96: ...fication label 4 6 WARRANTY GE operating through its authorized agents warrants that the standard products will be free of defects in materials and workmanship for a period as per contract specificati...

Страница 97: ...RIAL RECYCLING GE in compliance with environment protection uses only environmentally friendly material UPS packing materials must be recycled in compliance with all applicable regulations RECYCLING A...

Страница 98: ...l Panel positioned on the UPS front door acts as the UPS user interface Main features LCD Touch screen color graphic display See Chapter 6 Multilanguage communication interface English German Italian...

Страница 99: ...e programmed to meet customer needs by changing parameters Operation commands of the UPS 6 1 HOME SCREEN Fig 6 1 1 LCD screen The LCD screen after 5 minutes of inactivity shuts down the backlight To r...

Страница 100: ...6 2 EVENTS Shows in chronological order all the events occurred alarms messages commands handling etc See Section 6 3 SETUP Allows the user to customize some UPS functions to specific requirements and...

Страница 101: ...ervice Key yellow color Key for disabling the Service Key procedure Used only by the Service Center LEDS UPS STATUS LED LOAD PROTECTED green color When lit indicates that the UPS is functioning correc...

Страница 102: ...en LED STOP OPERATION red color It warns about the imminent Inverter stop default parameter 3 min and the consequent Load shut down as result of The battery is fully discharged and the Load cannot be...

Страница 103: ...ptic Diagram LED 1 Rectifier LED 2 Inverter LED 3 Booster Battery charger LED 4 Automatic Bypass LED 5 LOAD Examples of typical scenarios in the Synoptic Diagram Load supplied by Inverter Load supplie...

Страница 104: ...rs like AC DC and various statistics In this mode the keys perform the following functions Return to HOME screen Shows the main screen EVENTS See Section 6 3 Shows the main screen SETUP See Section 6...

Страница 105: ...t shows the true battery autonomy Charge level The battery charge level On battery time Total operating time of the UPS on battery in hours BATTERY DISCHARGE COUNTER Residual Charge Level The number o...

Страница 106: ...tolerance faults Number of fast transients The number of fast transients occurred on the bypass utility on the last seven days Bypass quality index The statistic evaluation in 100 good 0 bad of the B...

Страница 107: ...ent power Total apparent Load power kVA UPS operation time Total operating time for the UPS in hours Active Power Total effective Load power kW SEM operation time Total operating time for the UPS in S...

Страница 108: ...keys perform the following functions Shows the main screen MEASURES See Section 6 2 Return to HOME screen Shows the main screen SETUP See Section 6 4 Shows the main screen COMMANDS See Section 6 5 Sho...

Страница 109: ...n event Nr 511 is the more recent Nr 1 is the first Data MM DD YYYY Exact hour of the moment when the event occurred HH MM SS thousandth Number of standard GE code of the event Explicit text describin...

Страница 110: ...FAILURE The parallel communication bus system is subject to high errors rate on channel JA 4007 BUS JB CRC FAILURE The parallel communication bus system is subject to high errors rate on channel JB 4...

Страница 111: ...E Dangerous high DC Voltage caused Inverter shut down Inverter restarts automatically after Battery returns to floating voltage 4117 BATTERY EARTH FAULT A leakage current to earth has been detected on...

Страница 112: ...FORMER OVERTEMPERATURE The temperature sensor of the Inverter Transformer indicates overtemperature Elapsed stop operation time Inverter shut down With Utility OK Load is transferred on Utility 4308 D...

Страница 113: ...d remains supplied by Utility until the alarm stays ON 4522 FAN FAILURE The Fan Control Board indicates a malfunction of one or more ventilators 4530 LOAD LOCKED ON UTILITY Load is locked on Utility b...

Страница 114: ...ard in particular from the DC supply Can be enabled or disabled with respective parameter 4702 LOSS OF REDUNDANCY A time of lost redundancy superior than specified in respective parameter was detected...

Страница 115: ...settings 4124 MANUAL AUTOMATIC BOOST CHARGE STOP The automatic boost charge has finished The battery s voltage will return to the maintenance value A manually activated boost charge will finish if it...

Страница 116: ...561 LOAD OFF Push button Load Off on the UPS Control Panel has been pressed with the output circuit switch Q1 closed 4562 DETOUR ON The auxiliary contact indicates that Q2 Manual Bypass was closed 456...

Страница 117: ...de will be temporarily inhibited 4609 SEM INHIBITED LOW LOAD SEM Operation Mode inhibited due to minimal load not reached 4699 BATTERY TEST IMPOSSIBLE Automatic Battery Test is not possible due to No...

Страница 118: ...without password protection In this mode the keys perform the following functions Shows the main screen MEASURES See Section 6 2 Shows the main screen EVENTS See Section 6 3 Return to HOME screen Sho...

Страница 119: ...s are XON standing for the XON XOFF protocol or None standing for any protocol PRINTER COMMANDS By using the keys MEASURES ALARMS PARAMETERS ALL it is possible to print selected data NOTE Please confi...

Страница 120: ...ing in VFI double conversion mode at all times When the UPS is in SEM Operating Mode the SEM LED is ON green light NOTE The configuration of the activation schedule can only be updated when SEM Operat...

Страница 121: ...value NOTE To avoid undesired SEM Operation Mode verify Date and Time SEM screen how many hours of SEM Operation Mode have been selected for each day of the week NOTE The SEM Operation Mode will beco...

Страница 122: ...f all Inverters in the system at least 1 minute of normal operation must be programmed during the week the Yes No parameter is automatically disabled if this condition is not satisfied In case this mi...

Страница 123: ...many hours of IEMi Operation Mode have been selected for each day of the week NOTE For IEMi Operation Mode to become active a manual Inverter start is required at start up and after a Load Off reset T...

Страница 124: ...e user to execute UPS operation commands In this mode the keys perform the following functions Shows the main screen MEASURES See Section 6 2 Shows the main screen EVENTS See Section 6 3 Shows the mai...

Страница 125: ...ching ON command NOTE When SEM Operation Mode or IEMi Operation Mode is enabled control of Inverter status and selection of the feed path is done autonomously by the UPS control logic Therefore Invert...

Страница 126: ...Shows the Module shutdown status ACTIVE NOT ACTIVE System shutdown System shutdown Load Off command for an RPA Parallel System NOTE This command will immediately disconnect the Load System shutdown c...

Страница 127: ...EST Acoustical alarm test acoustical alarm should be always activated Module shutdown procedure Guides throught the procedures to shutdown a single UPS or a RPA Parallel System unit Attention For a si...

Страница 128: ...nformation on the RPA Parallel System In this mode the keys perform the following functions Shows the main screen MEASURES See Section 6 2 NOTE During IEMi Operation Mode the Percent Load information...

Страница 129: ...the RPA System Parallel Input Utility status for RECT Rectifier and BYP Bypass Battery status for CHRG Battery Charger green color On grey color Off Q1 Load output switch Q2 Manual Bypass switch only...

Страница 130: ...structions given below However we recommend that at least the initial procedure should be performed by an instructed person Check after every step for correct reaction of the UPS LEDs on the panel and...

Страница 131: ...ty screens are fixed in their position The switches Q1 is open Pos O and the Battery Cabinet Breaker must be open Pos O LEDs on Synoptic Diagram Q1 UPS Output switch LED 1 Rectifier LED 2 Inverter LED...

Страница 132: ...and reliability of the UPS UPS Language This parameter allows the choice of language used to display the information Date dd mm yyyy You can adjust the date of the real time clock existing in the UPS...

Страница 133: ...1 41Vdc for cell 284 309 cells x 1 41Vdc 401 436Vdc NiCd Battery with boost charge 1 41 1 55 boost charge Vdc for cell 281 cells x 1 41Vdc 397 436 Vdc Flooded Lead Acid Battery without boost charge 2...

Страница 134: ...ker Pos I NOTE Before performing the next procedure 4 make sure that the LED 3 Booster Battery charger is lit 4 Insert the Inverter performing the command Inverter ON Perform the Inverter ON command f...

Страница 135: ...ected from UPS Rectifier and Inverter are shut down and all contactors are opened LED 1 Rectifier and LED 2 Inverter are OFF LED ALARM is lit 2 Open Q1 UPS Output switch Pos O 3 Disconnect the battery...

Страница 136: ...tput switch MUST BE CLOSED Pos I Battery Cabinet Breaker MUST BE OPEN Pos O Make sure that SEM Operation Mode is disabled before starting this procedure View of the Synoptic Diagram after performed th...

Страница 137: ...NOTE Before performing the next procedure 3 make sure that the LED 3 Booster Battery charger is lit 3 Insert the Inverter performing the command Inverter ON Perform the Inverter ON command from the s...

Страница 138: ...binet Breaker MUST BE OPEN Pos O Make sure that SEM Operation Mode is disabled before starting this procedure View of the Synoptic Diagram after performed the command EPO Emergency Power Off with LOAD...

Страница 139: ...NOTE Before performing the next procedure 4 make sure that the LED 3 Booster Battery charger is lit 4 Insert the Inverter performing the command Inverter ON Perform the Inverter ON command from the s...

Страница 140: ...pen Open the front door and make sure that All the connections to the input output terminals or bus bars of the UPS have been made correctly The safety screens are fixed in their position The switches...

Страница 141: ...and reliability of the UPS UPS Language This parameter allows the choice of language used to display the information Date dd mm yyyy You can adjust the date of the real time clock existing in the UPS...

Страница 142: ...1 41Vdc for cell 284 309 cells x 1 41Vdc 401 436Vdc NiCd Battery with boost charge 1 41 1 55 boost charge Vdc for cell 281 cells x 1 41Vdc 397 436 Vdc Flooded Lead Acid Battery without boost charge 2...

Страница 143: ...polarities on both side of the switch fuse holder 3 Connect the battery to the UPS by closing the Battery Cabinet Breaker Pos I 4 Insert the Inverter performing the command Inverter ON Before performi...

Страница 144: ...PS Rectifier and Inverter are shut down and all contactors are opened LED 1 Rectifier and LED 2 Inverter are OFF LED ALARM is lit 2 Open Q1 UPS Output switch Pos O 3 Disconnect the battery from the UP...

Страница 145: ...Q1 UPS Output switch MUST BE CLOSED Pos I Battery Cabinet Breaker MUST BE OPEN Pos O View of the Synoptic Diagram after performed the command System shutdown with LOAD NOT SUPPLIED 1 Restore the comma...

Страница 146: ...command Inverter ON Perform the Inverter ON command from the screen Commands 1 Inverter ON Soft start of Inverter indicated with blinking LED 2 Inverter At the end of Soft start the LED 2 Inverter re...

Страница 147: ...make sure that the UPS is in the following status Q1 UPS Output switch MUST BE CLOSED Pos I Battery Cabinet Breaker MUST BE OPEN Pos O View of the Synoptic Diagram after performed the command EPO Eme...

Страница 148: ...ng the Battery Cabinet Breaker Pos I NOTE Before performing the next procedure 4 make sure that the LED 3 Booster Battery charger is lit 4 Insert the Inverter performing the command Inverter ON Perfor...

Страница 149: ...ixed in their position The switches Q1 is open Pos O and the Battery Cabinet Breaker must be open Pos O LEDs on Synoptic Diagram Q1 UPS Output switch LED 1 Rectifier LED 2 Inverter LED 3 Booster Batte...

Страница 150: ...and reliability of the UPS UPS Language This parameter allows the choice of language used to display the information Date dd mm yyyy You can adjust the date of the real time clock existing in the UPS...

Страница 151: ...1 41Vdc for cell 284 309 cells x 1 41Vdc 401 436Vdc NiCd Battery with boost charge 1 41 1 55 boost charge Vdc for cell 281 cells x 1 41Vdc 397 436 Vdc Flooded Lead Acid Battery without boost charge 2...

Страница 152: ...indicates that the DC link 1 and DC link 2 has reached 400Vdc see screen MEASURES Rectifier Attention check the right DC polarities on both side of the switch fuse holder 3 Connect the Battery on all...

Страница 153: ...sfer to Inverter LED ALARM turns Off and the LED LOAD PROTECTED must be lit The Synoptic Diagram on all UPS units must display the status LOAD SUPPLIED BY INVERTER Synoptic Diagram of first unit Synop...

Страница 154: ...m all Inverters of the Redundant Parallel System 1 Disconnect the Inverter performing the Inverter OFF command on the Unit to separate 1 Perform the Inverter OFF command from the screen Commands 1 Inv...

Страница 155: ...Pos O Press MUTE key to reset Acoustical Alarm LED ALARM remains lit Synoptic diagram of the unit to separate Synoptic diagram of other units NOTE Before performing the next procedure 5 wait 5 minute...

Страница 156: ...procedure Open the front door of the Unit to reconnect and make sure that All the connections to the input output terminals or bus bars of the UPS have been made correctly The protection panels are fa...

Страница 157: ...nect by closing the Battery Cabinet Breaker Pos I Synoptic diagram of the unit to reconnect Synoptic diagram of other units 4 Insert the Inverter performing the command Inverter ON on the Unit to reco...

Страница 158: ...m shutdown Shutdown Load is disconnected from UPS Parallel System Rectifiers and Inverters are shut down and all Contactors are opened LED ALARM is lit Synoptic diagram of first unit Synoptic diagram...

Страница 159: ...rting this procedure If IEMi option is available make sure that IEMi Operation Mode is disabled before starting this procedure View of the Synoptic Diagram on all UPS units after performed the command...

Страница 160: ...emains lit In case of sufficient output power the output will transfer to Inverter LED ALARM turns Off and the LED LOAD PROTECTED must be lit Synoptic diagram of first unit Synoptic diagram of other u...

Страница 161: ...cedure If IEMi option is available make sure that IEMi Operation Mode is disabled before starting this procedure View of the Synoptic Diagram on all UPS units after performed the command EPO Emergency...

Страница 162: ...emains lit In case of sufficient output power the output will transfer to Inverter LED ALARM turns Off and the LED LOAD PROTECTED must be lit Synoptic diagram of first unit Synoptic diagram of other u...

Страница 163: ...o receive status information and measurement values of the UPS In case of a critical condition time on battery remaining battery autonomy time or low battery for the Load the software starts a control...

Страница 164: ...nents of the UPS which need periodic maintenance if not replaced could cause a reliability reduction of the supply system We highly recommend that you contact your GE Service Center for preventive mai...

Страница 165: ...ry Test to verify the full runtime of the Battery the charger needs at least 8 hours to recharge the Battery up to 90 of its capacity Long shut down periods of the UPS system To guarantee that the Bat...

Страница 166: ...ser Manual TLE Scalable Series 40 150 UL S1 10 NOTES 10 1 NOTES FORM It is recommended to note in this section Notes with date and short description all the operations performed on the UPS as maintena...

Страница 167: ...t Uninterruptible Power Supply GE Consumer Industrial SA General Electric Company CH 6595 Riazzino Locarno Switzerland T 41 0 91 850 51 51 F 41 0 91 850 52 52 www gecriticalpower com imagination at wo...

Страница 168: ...sue 10 27 2017 File name GE_UPS_TDS_TLE_SUL_40K_M15_1US_V010 Revision 1 0 Identification No Up dating Revision Concern Date COPYRIGHT 2017 by GE Consumer Industrial SA All rights reserved The informat...

Страница 169: ...e Internal protection All internal live parts shrouded Transport On pallet Cabinet suitable for handling by forklift Color RAL 9005 black Installation Minimum distance from the wall 2 5 cm and floor f...

Страница 170: ...HD for 100 non linear load EN 62040 5 Output voltage tolerance at 100 unbalanced load Ph N 3 Output frequency 60 Hz Output frequency tolerance free running 0 1 with mains synchronization adjustable to...

Страница 171: ...and Dutch Graphic diagram indicating UPS status Command keys and parameters setting UPS status control LED OPTIONS COMMUNICATION OPTIONS 1 Additional Customer Interface Card 2 iUPS Guard 3 GE Data Pr...

Страница 172: ...ranch Circuit Over Current Protection All Models CAUTION To reduce the risk of fire only connect UPS to a circuit provided with see below maximum amperes branch circuit over current protection in acco...

Страница 173: ...lbs 2096 kg 31 80 2 2860 lbs 1297 kg 5720 lbs 2594 kg 41 3220 lbs 1461 kg 6440 lbs 2922 kg 50 3500 lbs 1588 kg 7000 lbs 3176 kg 73 4620 lbs 2096 kg 9240 lbs 4192 kg 100 6 40 1 2860 lbs 1297 kg 2860 l...

Страница 174: ...d cost of ownership and improved power usage effectiveness PUE compared to conventional UPS Features and Benefits Technology at Its Best Highly reliable and efficient tri level conversion Automatic or...

Страница 175: ...25kW BTU hr kW 8593 2 5 13113 3 8 20023 5 9 27184 8 0 250kW BTU hr kW 9026 2 6 14118 4 1 22120 6 5 30461 8 9 Heat rejection in eBoost operating mode 1 PF load nominal voltage frequency energy storage...

Страница 176: ...in an electrical system up to 65kA RECTIFIER Configuration Three phases rectifier bridge with three level IGBT technology Input Voltage 480VAC 3 phase 4 wire ground OR 3 wire ground 15 without batter...

Страница 177: ...technology IGBT Output waveform True sine wave Output voltage tolerance Static 1 Load step 0 100 0 3 recovering to within 1 in 1 cycle Load step 0 50 0 2 recovering to within 1 in 1 cycle 100 unbalanc...

Страница 178: ...ical Transfer limits Steady state RMS tolerance 20 Vrms adjustable Instantaneous voltage distortion with respective to Normal Sine wave Magnitude 75Vp Duration 500 s adjustable Steady state frequency...

Страница 179: ...e Page of LCD Load level in Battery run time in min Multilanguage Graphic LCD Display of UPS metering functions event history configuration of parameters and helps perform critical UPS Operations Supp...

Страница 180: ...FB CB3 Battery Fuses or Circuit Breaker F1 F2 F3 AC Input Fuses or Circuit Breaker TLE Series UPS 160 200 225 250 Technical Datasheet With separate Bypass Utility connect a single input Neutral to By...

Страница 181: ...e right to make changes to specifications of products described at any time without notice and without obligation to notify any person of such changes 601 Shiloh Road Plano TX 75074 1 877 546 3243 tol...

Страница 182: ...ply GE Consumer Industrial SA General Electric Company CH 6595 Riazzino Locarno Switzerland T 41 0 91 850 51 51 F 41 0 91 850 52 52 www gecriticalpower com imagination at work TLES_UL_160 500_S2b_UPS_...

Страница 183: ...p dating Revision Concern Date COPYRIGHT 2018 by GE Consumer Industrial SA All rights reserved The information contained in this publication is intended solely for the purposes indicated The present p...

Страница 184: ...e installation of the UPS Thank you for choosing GE START UP AND COMMISSIONING A GE GLOBAL SERVICES FIELD ENGINEER must perform start up and commissioning of the UPS Please Contact GE GLOBAL SERVICES...

Страница 185: ...ontained in this document WARNING TLE Series 160 500 is a Category C3 UPS Product according to IEC 62040 2 This is a product for commercial and industrial application in the second environment install...

Страница 186: ...225 250 Power connection with Common Input Utility 35 4 8 2 TLE Series 160 200 225 250 Power connection with Dual Input Utility 37 4 8 3 TLE Series 300 400 500 Power connection with Common Input Utili...

Страница 187: ...rately during Commissioning and Maintenance of the UPS for the following Damaged components squeezed wires and cables or not correctly inserted plugs After removing the sidewalls of the UPS make sure...

Страница 188: ...ol to short between individual or separate battery terminals or to the cabinet or rack Do not lay tools or metal parts on top of the battery and do not lay them where they could fall onto the battery...

Страница 189: ...is manual the following symbols are defined WARNING if instruction is not followed injury or serious equipment damage may occur CAUTION internal parts have dangerous voltage present Risk of electric s...

Страница 190: ...eries 160 200 225 250 General view Fig 2 1 3 Control Panel Fig 2 1 4 Connectivity Rack Fig 2 1 2 TLE Series 160 200 225 250 General view with open doors Fig 2 1 5 Q1 UPS Output switch TLES_UL_225 250_...

Страница 191: ...l Battery connection CI Customer Interface Board see Fig 2 1 4 CR Connectivity Rack J35 P Serial port RS232 for IMV protocol Q1 UPS Output switch RPA RPA board Redundant Parallel Architecture for Para...

Страница 192: ...ies 300 400 500 General view Fig 2 2 3 Control panel Fig 2 2 4 Connectivity Rack Fig 2 2 2 TLE Series 300 400 500 General view with open doors Fig 2 2 5 Q1 UPS Output switch TLES_UL_400 500_S1_UPS_GE_...

Страница 193: ...Battery connection CI Customer Interface Board see Fig 2 2 4 CR Connectivity Rack J35 P Serial port RS232 for IMV protocol Q1 UPS Output switch RPA RPA board Redundant Parallel Architecture for Parall...

Страница 194: ...d PACKING MATERIAL RECYCLING GE in compliance with environment protection uses only environmentally friendly material UPS packing materials must be recycled in compliance with all applicable regulatio...

Страница 195: ...unpacked UPS Forklift The UPS may be lifted with a forklift in upright position Take note of the center of gravity marked on the package Crane Fig 4 1 2 Position of the carrying belts when moving the...

Страница 196: ...1120 x 865 x 1905 mm Weight 1345 lbs 610 kg Floor loading 129 lbs sq ft 630 kg m2 Dimensions and weights TLE Series 300 400 500 Dimensions W x D x H 63 78 x 34 06 x 75 00 inches 1620 x 865 x 1905 mm W...

Страница 197: ...and with a temperature range not exceeding 13 F 25 C to 131 F 55 C In case the battery is included please refer to Section 4 3 2 Some important functions of the UPS such as the customized functions ar...

Страница 198: ...xplained in Section 9 1 4 of the User Manual read and understand them The TLE Series 160 500 UPS can radiate radio frequency energy Although some RFI Radio Frequency Interference filtering is inherent...

Страница 199: ...d the bottom of the UPS for the connection of input and output cables Pay attention to the position of these openings when choosing the placement of the UPS These openings are covered with a protectiv...

Страница 200: ...the floor Fig 4 4 1 6 Fixing of the UPS cabinet on the floor Fig 4 4 1 7 TLE Series 160 220 225 250 UPS cabinet floor fixing points Fig 4 4 1 8 TLE Series 300 400 500 UPS cabinet floor fixing points T...

Страница 201: ...nge 4 F 20 C to 104 F 40 C The life of valve regulated batteries will be reduced by 50 for each additional 18 F 10 C that the battery ambient temperature is above 77 F 25 C The Battery System associat...

Страница 202: ...w rate requirement of the UPS system Contact your GE Service Center for appropriate solutions The below table indicates the heat dissipation at full Load at PF 1 and charged Battery up to 3280 ft 1000...

Страница 203: ...GE Service Center Fig 4 6 1 ShockWatch device Fig 4 6 2 TiltWatch device NOTE Be aware of the heavy weight of the UPS pay attention when moving the UPS cabinet Take care not to damage the UPS when mo...

Страница 204: ...enter Fig 4 6 4 TLE Series 300 400 500 Location of the Anti Humidity Corrosion devices TLE Series 300 400 500 a Humidity indicator b Desiccant bag 8 pcs c VCI foil base d PE stretch foil PROTECTIVE FO...

Страница 205: ...Common Input source or Dual Input sources if desired Common Input Utility Rectifier Bypass Fig 4 7 1 1 Common Input Utility Rectifier Bypass The same power source is to be used for both Bypass Supply...

Страница 206: ...nected and grounded solidly due to the existence of voltage surge protection devices inside the UPS The connection of the Battery to the UPS must be protected with fuses or similar devices according t...

Страница 207: ...chart below Minimum battery cable requirement is based on the current data below The maximum available fault current from the battery supply is 20kA The minimum breaker voltage rating is 540V The AC v...

Страница 208: ...Series 400 700 A 600 A 600 A 500 A 700 A 600 A 1000 A 1000 A TLE Series 500 900 A 700 A 800 A 700 A 900 A 700 A 1200 A 1200 A WIRING Wire sizing according to NEC Section 210 20 A Table 310 16 Use 167...

Страница 209: ...6 55 65 75 40 50 60 4 70 85 95 55 65 75 3 85 100 110 65 75 85 2 95 115 130 75 90 100 1 110 130 150 85 100 115 1 0 125 150 170 100 120 135 2 0 145 175 195 115 135 150 3 0 165 200 225 130 155 175 4 0 19...

Страница 210: ...160 500 Single UPS with Common Input Utility for Rectifier Bypass Single UPS with Common Input Utility for Rectifier Bypass 3 wire distribution 3 phase plus ground Single UPS with Dual Input Utility...

Страница 211: ...E_UPS_ISG_TLE_SUL_M16_M50_2bU_V010 docx Installation Guide TLE Series 160 500 UL S2B UPS Parallel System with Common Input Utility Rectifier Bypass UPS Parallel System with Common Input Utility Rectif...

Страница 212: ...uide TLE Series 160 500 UL S2B UPS Parallel System with Dual Input Utility for Rectifier Bypass Connect a single input Neutral to Bypass Utility inside the UPS common Neutral for Bypass and Rectifier...

Страница 213: ...k of short circuit between different poles The grounding and neutral connection of the electrical system must be in accordance with local regulations In case of additional cabinets containing batterie...

Страница 214: ...plate C NOTE For UPS correct operation the input utility phase rotation must be clock wise CAUTION Panel A B and C should never be removed or replaced with power applied to the UPS These panels are i...

Страница 215: ...US a Utility mains Battery Output load Position of the cover protection for cables input from the bottom of the UPS PE L3 1 L2 1 L1 1 N Utility Neutral Load Neutral Load 1 Rectifier Bypass Utility BR2...

Страница 216: ...The interconnection links BR1 BR2 and BR3 on the input bus bars MUST REMAIN CONNECTED Output Load L1 Load phase A L1 L2 Load phase B L2 L3 Load phase L3 N Neutral Ground External Battery connection Po...

Страница 217: ...et must contain a Neutral Bus as per the following Figure 4 8 1 2 If no Neutral Connection is available with the Bypass Input 3 wire input ground and the Load does not require a Neutral solidly connec...

Страница 218: ...L3 L3 2 Bypass phase C L3 PE Ground N Neutral NOTE The interconnection links BR1 BR2 and BR3 on the input bus bars MUST BE REMOVED see Fig 4 8 2 3 Output Load L1 Load phase A L1 L2 Load phase B L2 L3...

Страница 219: ...et must contain a Neutral Bus as per the following Figure 4 8 2 2 If no Neutral Connection is available with the Bypass Input 3 wire input ground and the Load does not require a Neutral solidly connec...

Страница 220: ...lity Fig 4 8 2 3 TLE Series 300 400 500 Interconnection links BR1 BR2 and BR3 NOTE For separate Bypass and Rectifier input configuration the interconnection links BR1 BR2 and BR3 MUST BE REMOVED see F...

Страница 221: ...phase L3 N Neutral Ground External Battery connection Positive pole of the battery Before closing the External Battery Fuses verify for correct polarity of the battery connection Negative pole of the...

Страница 222: ...et must contain a Neutral Bus as per the following Figure 4 8 3 2 If no Neutral Connection is available with the Bypass Input 3 wire input ground and the Load does not require a Neutral solidly connec...

Страница 223: ...g 4 8 4 3 Output Load L1 Load phase A L1 L2 Load phase B L2 L3 Load phase L3 N Neutral Ground External Battery connection Positive pole of the battery Before closing the External Battery Fuses verify...

Страница 224: ...et must contain a Neutral Bus as per the following Figure 4 8 4 2 If no Neutral Connection is available with the Bypass Input 3 wire input ground and the Load does not require a Neutral solidly connec...

Страница 225: ...ks BR1 BR2 and BR3 NOTE For separate Bypass and Rectifier input configuration the interconnection links BR1 BR2 and BR3 MUST BE REMOVED see Fig 4 8 4 3 PE L3 1 L1 2 L2 2 with bottom cable entry PE N U...

Страница 226: ...tic As the inverter output filter exhibits a predominantly capacitive characteristic it may provide some degree of reactive power compensation when combined with lagging power factor loads Conversely...

Страница 227: ...8 6 2 TLE Series 300 400 500 Interconnection links BR1 BR2 and BR3 In order to avoid improper operation only the Rectifier input should be powered L1 1 L2 1 and L3 1 Fig 4 8 2 1 4 8 4 1 therefore the...

Страница 228: ...the same for all units of the Parallel System no phase shift allowed between units NOTE It is strongly recommended that no transformers automatic circuit breakers or fuses should be inserted between t...

Страница 229: ...s In this way communication is maintained between units in case one of the control cables should fail or be accidentally damaged or disconnected The standard length of the control bus cable between tw...

Страница 230: ...a Parallel System the switches SW1 1 2 3 4 5 6 MUST BE IN POSITION ON see Fig 4 9 2 2 Fig 4 9 2 3 Bus connection on intermediate units Intermediate units of a RPA Parallel System On the two boards P1...

Страница 231: ...t Access to the control bus connection The communication bus cable connectors are placed on the two boards P13 P14 IM0022 Bus Interface Board see Fig 4 9 3 1 and 4 9 3 2 Fig 4 9 3 3 View electronic mo...

Страница 232: ...3 P14 IM0022 Bus Interface Board For reliability reasons the cables J1A J2A 1 2 3 4 5 and J1B J2B 1 2 3 4 5 connecting the units should be run in separated protected conduits as indicated in Fig 4 9 3...

Страница 233: ...nal block for EPO Emergency Power Off command connection When opened this contact causes the immediate opening of the Contactors K6 and K7 as well as the shut down of Rectifier Inverter and Static Swi...

Страница 234: ...n the EPO Emergency Power Off has been activated the system must be restored as follows Realize the push button EPO Emergency Power Off contact on XA EPO 1 EPO 2 is closed again Perform the Inverter O...

Страница 235: ...Customer Interface boards for each UPS max 2 3 ph SNMP WEB Plug in Adapter boards for Parallel System ATTENTION The installation of any option board must be performed by a GE Service Technician Prior...

Страница 236: ...select printing of measurements alarms and parameters see User Manual to Section 6 4 SETUP PRINTER Fig 5 1 2 Serial port J35 P connection to PC with RS232 1 1 cable DB9m DB9f The serial port J35 P RS2...

Страница 237: ...mally Open C Common NC Normally Closed Output signals on voltage free contacts Programmable functions on input contacts On terminals X1 6 of the following 27 signals can be selected from the display e...

Страница 238: ...ult is the following X1 1 2 3 NO C NC UTILITY FAILURE def Parameter RL 1 X1 4 5 6 NO C NC LOAD ON INVERTER def Parameter RL 3 X1 7 8 9 NO C NC STOP OPERATION def Parameter RL 5 X1 12 13 14 NO C NC LOA...

Страница 239: ...iderably unstable in frequency it should be suitable to install the signal GENERATOR ON on X1 11 22 See Fig 5 2 1 X1 Since the Parameter for of the reading of the Generator function is password protec...

Страница 240: ...connected to a separate AUX contact of the External Maintenance Bypass Switch 5 2 7 X1 terminal block eBoost IEMi control signal The UPS operation in either eBoost or IEMi operating modes can be contr...

Страница 241: ...10 docx Installation Guide TLE Series 160 500 UL S2B 6 NOTES 6 1 NOTES FORM It is recommended to note in this section Notes with date and short description all the operations performed on the UPS as m...

Страница 242: ...GE Consumer Industrial SA General Electric Company CH 6595 Riazzino Locarno Switzerland T 41 0 91 850 51 51 F 41 0 91 850 52 52 www gecriticalpower com imagination at work TLES_UL_160 500_S2b_UPS_GE_0...

Страница 243: ...ting Revision Concern Date COPYRIGHT 2018 by GE Consumer Industrial SA All rights reserved The information contained in this publication is intended solely for the purposes indicated The present publi...

Страница 244: ...use of the UPS Thank you for choosing GE START UP AND COMMISSIONING A GE GLOBAL SERVICES FIELD ENGINEER must perform start up and commissioning of the UPS Please Contact GE GLOBAL SERVICES at least tw...

Страница 245: ...ed in this document WARNING TLE Series 160 500 is a Category C3 UPS Product according to IEC 62040 2 This is a product for commercial and industrial application in the second environment installation...

Страница 246: ...FOR SINGLE TLE SERIES 160 500 56 7 1 1 Initial start up of the TLE Series 160 500 56 7 1 2 Complete UPS shut down 60 7 1 3 Restore to normal operation after System shutdown with Load not supplied 61...

Страница 247: ...ly during Commissioning and Maintenance of the UPS for the following Damaged components squeezed wires and cables or not correctly inserted plugs After removing the sidewalls of the UPS make sure that...

Страница 248: ...o short between individual or separate battery terminals or to the cabinet or rack Do not lay tools or metal parts on top of the battery and do not lay them where they could fall onto the battery or i...

Страница 249: ...anual the following symbols are defined WARNING if instruction is not followed injury or serious equipment damage may occur CAUTION internal parts have dangerous voltage present Risk of electric shock...

Страница 250: ...1 LAYOUT TLE Series 160 220 225 250 Fig 2 1 1 TLE Series 160 200 225 250 General view Fig 2 1 3 Control Panel Fig 2 1 4 Q1 UPS Output switch Fig 2 1 2 TLE Series 160 200 225 250 General view with ope...

Страница 251: ...2 2 LAYOUT TLE Series 300 400 500 Fig 2 2 1 TLE Series 300 400 500 General view Fig 2 2 3 Control Panel Fig 2 2 4 Q1 UPS Output switch Fig 2 2 2 TLE Series 300 400 500 General view with open doors TLE...

Страница 252: ...otal Load than any other UPS available allowing you to support a greater number of today s enterprise computing Power Factor Corrected PFC equipment High Efficiency Thanks to type Advanced Neutral Poi...

Страница 253: ...eliminating all single points of failure The decentralized bypass offers great exibility to up or down grade the system in case future needs might change TLE Series 160 500 BEST IN CLASS EFFICIENCY H...

Страница 254: ...modulation strategy applied to IGBT Bridge the rectifier provides clean input power in terms of low THDi and unity power factor Inverter The Inverter converts the DC voltage into a three phase AC vol...

Страница 255: ...e the Load is normally powered through the Automatic Bypass When the Utility Voltage is detected out of the prescribed tolerances the Load is automatically transferred to the Inverter When the Utility...

Страница 256: ...3 When a Battery low warning occurs on a unit not necessary to support the present Load this unit will shut down after a timeout period selectable The Load is shared between the other units As the wa...

Страница 257: ...condition is corrected the Load will be automatically transferred back to the Inverter Fig 4 2 5 1 Block diagram Automatic Bypass If the UPS is unable to return to normal mode following an automatic...

Страница 258: ...mmon control circuitry see Fig 4 3 1 1 Parallel units for power capacity Several units can be paralleled in order to achieve output power greater than the maximum power of a single unit The maximum to...

Страница 259: ...nicates with all other modules in order to act or react if necessary adapting to the new conditions 4 3 4 Synchronization All units are identical but one unit is arbitrarily selected as the reference...

Страница 260: ...UPSs required to maintain a reliable supply to the critical load Then an efficiency optimization algorithm determines the best UPS configuration in order to maintain the running UPS in their highest...

Страница 261: ...prepared in advance before the installation The installation must be performed only with the UPS system completely shut down The AC Rectifiers input power 4 must be the same with clockwise phase rota...

Страница 262: ...entification label 4 6 WARRANTY GE operating through its authorized agents warrants that the standard products will be free of defects in materials and workmanship for a period as per contract specifi...

Страница 263: ...MATERIAL RECYCLING GE in compliance with environment protection uses only environmentally friendly material UPS packing materials must be recycled in compliance with all applicable regulations RECYCLI...

Страница 264: ...ntrol Panel positioned on the UPS front door acts as the UPS user interface Main features LCD Touch screen color graphic display See Chapter 6 Multilanguage communication interface English German Ital...

Страница 265: ...an be programmed to meet customer needs by changing parameters Operation commands of the UPS 6 1 HOME SCREEN Fig 6 1 1 LCD screen The LCD screen after 5 minutes of inactivity shuts down the backlight...

Страница 266: ...ion 6 2 EVENTS Shows in chronological order all the events occurred alarms messages commands handling etc See Section 6 3 SETUP Allows the user to customize some UPS functions to specific requirements...

Страница 267: ...Key yellow color Key for disabling the Service Key procedure Used only by the GE Service Center LEDS UPS STATUS LED LOAD PROTECTED green color When lit indicates that the UPS is functioning correctly...

Страница 268: ...s open LED STOP OPERATION red color It warns about the imminent Inverter stop default parameter 3 min and the consequent Load shut down as result of The battery is fully discharged and the Load cannot...

Страница 269: ...noptic Diagram LED 1 Rectifier LED 2 Inverter LED 3 Booster Battery charger LED 4 Automatic Bypass LED 5 LOAD Examples of typical scenarios in the Synoptic Diagram Load supplied by Inverter Load suppl...

Страница 270: ...meters like AC DC and various statistics In this mode the keys perform the following functions Return to HOME screen Shows the main screen EVENTS See Section 6 3 Shows the main screen SETUP See Sectio...

Страница 271: ...ttery autonomy Charge level The battery charge level On battery time Total operating time of the UPS on battery in hours BATTERY DISCHARGE COUNTER Residual Charge Level The number of discharges combin...

Страница 272: ...of fast transients The number of fast transients occurred on the bypass utility on the last seven days Bypass quality index The statistic evaluation in 100 good 0 bad of the Bypass utility Status Bypa...

Страница 273: ...ime Total operating time for the UPS in hours Active Power Total effective Load power kW eBoost operation time Total operating time for the UPS in eBoost Operation Mode in hours This counter is displa...

Страница 274: ...he keys perform the following functions Shows the main screen MEASURES See Section 6 2 Return to HOME screen Shows the main screen SETUP See Section 6 4 Shows the main screen COMMANDS See Section 6 5...

Страница 275: ...to an event Nr 511 is the more recent Nr 1 is the first Data MM DD YYYY Exact hour of the moment when the event occurred HH MM SS thousandth Number of standard GE code of the event Explicit text descr...

Страница 276: ...JA CRC FAILURE The parallel communication bus system is subject to high errors rate on channel JA 4007 BUS JB CRC FAILURE The parallel communication bus system is subject to high errors rate on chann...

Страница 277: ...LTAGE Dangerous high DC Voltage caused Inverter shut down Inverter restarts automatically after Battery returns to floating voltage 4117 BATTERY EARTH FAULT A leakage current to earth has been detecte...

Страница 278: ...RANSFORMER OVERTEMPERATURE The temperature sensor of the Inverter Transformer indicates overtemperature Elapsed stop operation time Inverter shut down With Utility OK Load is transferred on Utility 43...

Страница 279: ...Load remains supplied by Utility until the alarm stays ON 4522 FAN FAILURE The Fan Control Board indicates a malfunction of one or more ventilators 4530 LOAD LOCKED ON UTILITY Load is locked on Utilit...

Страница 280: ...ly Board in particular from the DC supply Can be enabled or disabled with respective parameter 4702 LOSS OF REDUNDANCY A time of lost redundancy superior than specified in respective parameter was det...

Страница 281: ...ined settings 4124 MANUAL AUTOMATIC BOOST CHARGE STOP The automatic boost charge has finished The battery s voltage will return to the maintenance value A manually activated boost charge will finish i...

Страница 282: ...61 LOAD OFF Push button Load Off on the UPS Control Panel has been pressed with the output circuit switch Q1 closed 4562 DETOUR ON The auxiliary contact indicates that Q2 Manual Bypass was closed 4564...

Страница 283: ...ation Mode will be temporarily inhibited 4609 eBoost INHIBITED LOW LOAD eBoost Operation Mode inhibited due to minimal load not reached 4699 BATTERY TEST IMPOSSIBLE Automatic Battery Test is not possi...

Страница 284: ...e without password protection In this mode the keys perform the following functions Shows the main screen MEASURES See Section 6 2 Shows the main screen EVENTS See Section 6 3 Return to HOME screen Sh...

Страница 285: ...alues are XON standing for the XON XOFF protocol or None standing for any protocol PRINTER COMMANDS By using the keys MEASURES ALARMS PARAMETERS ALL it is possible to print selected data NOTE Please c...

Страница 286: ...e value is No the UPS is normally operating in VFI double conversion mode at all times When the UPS is in eBoost Operating Mode the eBoost LED is ON green light NOTE The configuration of the activatio...

Страница 287: ...alue NOTE To avoid undesired eBoost Operation Mode verify Date and Time eBoost screen how many hours of eBoost Operation Mode have been selected for each day of the week NOTE The eBoost Operation Mode...

Страница 288: ...st of all Inverters in the system at least 1 minute of normal operation must be programmed during the week the Yes No parameter is automatically disabled if this condition is not satisfied In case thi...

Страница 289: ...how many hours of IEMi Operation Mode have been selected for each day of the week NOTE For IEMi Operation Mode to become active a manual Inverter start is required at start up and after a Load Off res...

Страница 290: ...s the user to execute UPS operation commands In this mode the keys perform the following functions Shows the main screen MEASURES See Section 6 2 Shows the main screen EVENTS See Section 6 3 Shows the...

Страница 291: ...tching ON command NOTE When eBoost Operation Mode or IEMi Operation Mode is enabled control of Inverter status and selection of the feed path is done autonomously by the UPS control logic Therefore In...

Страница 292: ...us Shows the Module shutdown status ACTIVE NOT ACTIVE System shutdown System shutdown Load Off command for an RPA Parallel System NOTE This command will immediately disconnect the Load System shutdown...

Страница 293: ...er TEST Acoustical alarm test acoustical alarm should be always activated Module shutdown procedure Guides throught the procedures to shutdown a single UPS or a RPA Parallel System unit Attention For...

Страница 294: ...me information on the RPA Parallel System In this mode the keys perform the following functions Shows the main screen MEASURES See Section 6 2 NOTE During IEMi Operation Mode the Percent Load informat...

Страница 295: ...of the RPA System Parallel Input Utility status for RECT Rectifier and BYP Bypass Battery status for CHRG Battery Charger green color On grey color Off Q1 Load output switch Q2 Manual Bypass switch on...

Страница 296: ...step instructions given below However we recommend that at least the initial procedure should be performed by an instructed person Check after every step for correct reaction of the UPS LEDs on the p...

Страница 297: ...ttery Protections must be open Pos O TLE Series 160 200 225 250 TLE Series 300 400 500 LEDs on Synoptic Diagram Q1 UPS Output switch CB3 External Battery switch option LED 1 Rectifier LED 2 Inverter L...

Страница 298: ...reliability of the UPS UPS Language This parameter allows the choice of language used to display the information Date dd mm yyyy You can adjust the date of the real time clock existing in the UPS by...

Страница 299: ...arge 1 41Vdc for cell 284 309 cells x 1 41Vdc 401 436Vdc NiCd Battery with boost charge 1 41 1 55 boost charge Vdc for cell 281 cells x 1 41Vdc 397 436 Vdc Flooded Lead Acid Battery without boost char...

Страница 300: ...CB3 External Battery switch option NOTE Before performing the next procedure 4 make sure that the LED 3 Booster Battery charger is lit 4 Insert the Inverter performing the command Inverter ON Perform...

Страница 301: ...m UPS Rectifier and Inverter are shut down and all contactors are opened LED 1 Rectifier and LED 2 Inverter are OFF LED ALARM is lit 2 Open Q1 UPS Output switch Pos O 3 Disconnect the Battery from the...

Страница 302: ...ry Protections MUST BE DISCONNECTED and the CB3 External Battery switch option MUST BE OPEN If eBoost option is available make sure that eBoost Operation Mode is disabled before starting this procedur...

Страница 303: ...CB3 External Battery switch option NOTE Before performing the next procedure 3 make sure that the LED 3 Booster Battery charger is lit 3 Insert the Inverter performing the command Inverter ON Perform...

Страница 304: ...CB3 External Battery switch option MUST BE OPEN If eBoost option is available make sure that eBoost Operation Mode is disabled before starting this procedure View of the Synoptic Diagram after perfor...

Страница 305: ...CB3 External Battery switch option NOTE Before performing the next procedure 4 make sure that the LED 3 Booster Battery charger is lit 4 Insert the Inverter performing the command Inverter ON Perform...

Страница 306: ...the UPS have been made correctly The safety screens are fixed in their position The switches Q1 and CB3 option are open Pos O and the External Battery Protections must be open Pos O TLE Series 160 200...

Страница 307: ...reliability of the UPS UPS Language This parameter allows the choice of language used to display the information Date dd mm yyyy You can adjust the date of the real time clock existing in the UPS by...

Страница 308: ...arge 1 41Vdc for cell 284 309 cells x 1 41Vdc 401 436Vdc NiCd Battery with boost charge 1 41 1 55 boost charge Vdc for cell 281 cells x 1 41Vdc 397 436 Vdc Flooded Lead Acid Battery without boost char...

Страница 309: ...the switch fuse holder 3 Connect the Battery to the UPS by closing the External Battery Protections and close if present the CB3 External Battery switch option 4 Insert the Inverter performing the co...

Страница 310: ...shut down and all contactors are opened LED 1 Rectifier and LED 2 Inverter are OFF LED ALARM is lit 2 Open Q1 UPS Output switch Pos O 3 Disconnect the Battery from the UPS by opening if present the C...

Страница 311: ...rotections MUST BE DISCONNECTED and the CB3 External Battery switch option MUST BE OPEN View of the Synoptic Diagram after performed the command System shutdown with LOAD NOT SUPPLIED 1 Restore the co...

Страница 312: ...the command Inverter ON Perform the Inverter ON command from the screen Commands 1 Inverter ON Soft start of Inverter indicated with blinking LED 2 Inverter At the end of Soft start the LED 2 Inverte...

Страница 313: ...is in the following status Q1 UPS Output switch MUST BE CLOSED External Battery Protections MUST BE DISCONNECTED and the CB3 External Battery switch option MUST BE OPEN View of the Synoptic Diagram af...

Страница 314: ...rotections and close if present the CB3 External Battery switch option NOTE Before performing the next procedure 4 make sure that the LED 3 Booster Battery charger is lit 4 Insert the Inverter perform...

Страница 315: ...s must be open Pos O TLE Series 160 200 225 250 TLE Series 300 400 500 LEDs on Synoptic Diagram Q1 UPS Output switch CB3 External Battery switch option LED 1 Rectifier LED 2 Inverter LED 3 Booster Bat...

Страница 316: ...reliability of the UPS UPS Language This parameter allows the choice of language used to display the information Date dd mm yyyy You can adjust the date of the real time clock existing in the UPS by...

Страница 317: ...arge 1 41Vdc for cell 284 309 cells x 1 41Vdc 401 436Vdc NiCd Battery with boost charge 1 41 1 55 boost charge Vdc for cell 281 cells x 1 41Vdc 397 436 Vdc Flooded Lead Acid Battery without boost char...

Страница 318: ...k 1 and DC link 2 has reached 400Vdc see screen MEASURES Rectifier Attention check the right DC polarities on both side of the switch fuse holder 3 Connect the Battery on all Units by closing the Exte...

Страница 319: ...to Inverter LED ALARM turns Off and the LED LOAD PROTECTED must be lit The Synoptic Diagram on all UPS units must display the status LOAD SUPPLIED BY INVERTER Synoptic Diagram of first unit Synoptic...

Страница 320: ...tus Load supplied from all Inverters of the Redundant Parallel System 1 Disconnect the Inverter performing the Inverter OFF command on the Unit to separate 1 Perform the Inverter OFF command from the...

Страница 321: ...then the External Battery Protections Press MUTE key to reset Acoustical Alarm LED ALARM remains lit Synoptic diagram of the unit to separate Synoptic diagram of other units NOTE Before performing th...

Страница 322: ...ting this procedure Open the front door of the Unit to reconnect and make sure that All the connections to the input output terminals or bus bars of the UPS have been made correctly The protection pan...

Страница 323: ...nal Battery Protections and close if present the CB3 External Battery switch option Synoptic diagram of the unit to reconnect Synoptic diagram of other units 4 Insert the Inverter performing the comma...

Страница 324: ...wn Shutdown Load is disconnected from UPS Parallel System Rectifiers and Inverters are shut down and all Contactors are opened LED ALARM is lit Synoptic diagram of first unit Synoptic diagram of other...

Страница 325: ...that eBoost Operation Mode is disabled before starting this procedure If IEMi option is available make sure that IEMi Operation Mode is disabled before starting this procedure View of the Synoptic Dia...

Страница 326: ...of Soft start the LED 2 Inverter remains lit In case of sufficient output power the output will transfer to Inverter LED ALARM turns Off and the LED LOAD PROTECTED must be lit Synoptic diagram of firs...

Страница 327: ...eration Mode is disabled before starting this procedure If IEMi option is available make sure that IEMi Operation Mode is disabled before starting this procedure View of the Synoptic Diagram on all UP...

Страница 328: ...of Soft start the LED 2 Inverter remains lit In case of sufficient output power the output will transfer to Inverter LED ALARM turns Off and the LED LOAD PROTECTED must be lit Synoptic diagram of firs...

Страница 329: ...critical conditions In addition comprehensive data collection and analysis improves diagnostics capability and enhances response time Continuous monitoring and ongoing maintenance help ensure maximum...

Страница 330: ...ponents of the UPS which need periodic maintenance if not replaced could cause a reliability reduction of the supply system We highly recommend that you contact your GE Service Center for preventive m...

Страница 331: ...ttery Test to verify the full runtime of the Battery the charger needs at least 8 hours to recharge the Battery up to 90 of its capacity Long shut down periods of the UPS system To guarantee that the...

Страница 332: ...V010 docx User Manual TLE Series 160 500 UL S2B 10 NOTES 10 1 NOTES FORM It is recommended to note in this section Notes with date and short description all the operations performed on the UPS as main...

Страница 333: ...TLE Series UPS 225 1500 kW for best in class multi mode operating efficiency...

Страница 334: ...omation and power delivery technologies to enable cleaner smarter and more efficient power for electrical infrastructures and consumers around the world Ensuring Uptime for Critical Processes 2 Missio...

Страница 335: ...ment Optimization TLE Series UPS 225 to 1500 kW Up to 97 Efficient in Premium Protection Mode double conversion Up to 99 Efficient in Premium Energy Save Mode eBoost Unity 1 0 Output Power Factor High...

Страница 336: ...GE s TLE Series UPS is one of the most energy efficient multi mode UPS in the industry and provides world class energy efficiency across the operating load range The TLE Series delivers efficiency up...

Страница 337: ...Life Cycle Cost Savings data center life cycle cost 10 years The TLE Series with 97 efficiency in double conversion mode and 99 efficiency in eBoost operating mode provides considerable life cycle co...

Страница 338: ...analysis The TLE Series is also equipped with special hardware and monitoring capability for limited life components like fans and capacitors Waveform capturing capability Fan failure detection Compon...

Страница 339: ...le rate of change and voltage rate of change allow the UPS to quickly sync to a genset during emergency back up Total Harmonic Distortion THD A distorted output voltage waveform affects the proper fun...

Страница 340: ...Scalable and Modular The system can be easily expanded for higher capacity and redundancy without any interruption to the critical load or transfer to bypass Redundant Communication Redundant high sp...

Страница 341: ...GE provides integrated cabinets to include 3CB maintenance bypass capability at 480V with downstream stepdown transformer to 208 120V Feature options include SKRU kirk key interlocks and 208V output...

Страница 342: ...he possibility to start applications and send messages and e mails for every upcoming or disappearing alarm Remote Monitoring and Diagnostic Solution iUPSGuard GE remote monitoring solution is an anyt...

Страница 343: ...0 utility failure with waveform capture Factory Testing Customer Witness Testing 0 100 step loads with waveform capture 0 100 bypass transfers with waveform captures Output short circuit with waveform...

Страница 344: ...12 Name of Document www gecriticalpower com TLE Series UPS 480 277 VAC Configurations 225 kW 250 kW 400 kW 500 kW 44 1 W 63 8 W 118 W 143 5 W 200 W 200 W 750 kW 1000 kW 1250 kW 1500 kW 12...

Страница 345: ...st Factor 3 1 Static Voltage Regulation 1 100 Step Load Voltage Regulation 3 100 Linear Load Voltage Distortion 3 0 THD maximum 100 Non Linear Load Voltage Distortion 5 0 THD maximum eBoost Transfer T...

Страница 346: ...14 Name of Document www gecriticalpower com TLE Series UPS 400 230 VAC Configurations 400 kW 600 kW 800 kW 1000 kW 1200 kW 200 kW 44 1 W 63 8 W 118 W 143 5 W 200 W 200 W 14...

Страница 347: ...d Voltage Regulation 3 100 Linear Load Voltage Distortion 1 5 THD maximum 100 Non Linear Load Voltage Distortion 5 0 THD maximum eBoost Transfer Time 2msec from Bypass to Inverter within ITI CBEMA vol...

Страница 348: ...als Battery Capacitor Replacements Contractual Services Maintenance Service Contracts Remote Monitoring Diagnostics Technical Services Training Training for Operators Training for Maintenance Staff Pr...

Страница 349: ...wer Supply GE Consumer Industrial SA General Electric Company CH 6595 Riazzino Locarno Switzerland T 41 0 91 850 51 51 F 41 0 91 850 52 52 www gecriticalpower com imagination at work TLES_UL_625 750 1...

Страница 350: ...ng Revision Concern Date COPYRIGHT 2018 by GE Consumer Industrial SA All rights reserved The information contained in this publication is intended solely for the purposes indicated The present publica...

Страница 351: ...t the installation of the UPS Thank you for choosing GE START UP AND COMMISSIONING A GE GLOBAL SERVICES FIELD ENGINEER must perform start up and commissioning of the UPS Please Contact GE GLOBAL SERVI...

Страница 352: ...contained in this document WARNING TLE Series 625 750 1000 is a Category C3 UPS Product according to IEC 62040 2 This is a product for commercial and industrial application in the second environment i...

Страница 353: ...8 4 Installation requirements 37 4 9 WIRING CONNECTION 40 4 9 1 TLE Series 625 750 Power connection with Common Input Utility 44 4 9 2 TLE Series 625 750 Power connection with Dual Input Utility 46 4...

Страница 354: ...ccurately during Commissioning and Maintenance of the UPS for the following Damaged components squeezed wires and cables or not correctly inserted plugs After removing the sidewalls of the UPS make su...

Страница 355: ...tool to short between individual or separate battery terminals or to the cabinet or rack Do not lay tools or metal parts on top of the battery and do not lay them where they could fall onto the batter...

Страница 356: ...this manual the following symbols are defined WARNING if instruction is not followed injury or serious equipment damage may occur CAUTION internal parts have dangerous voltage present Risk of electric...

Страница 357: ...2 1 1 TLE Series 625 750 General view Fig 2 1 4 Connectivity Rack Fig 2 1 3 Control Panel Fig 2 1 5 Manual switches Q1 Fig 2 1 2 TLE Series 625 750 General view with open doors TLES_UL_7500_S1_UPS_GE...

Страница 358: ...m cable entry for External Battery connection 3 Bus bars for Utility input and Load output 4 Bus bars for External Battery connection CI Customer Interface Board see Fig 2 1 4 CR Connectivity Rack J35...

Страница 359: ...2 1 TLE Series 1000 General view Fig 2 2 4 Connectivity Rack Fig 2 2 3 Control Panel Fig 2 2 5 Manual switches Q1 Fig 2 2 2 TLE Series 1000 General view with open doors TLES_UL_1000_S1_UPS_GE_02 TLES_...

Страница 360: ...able entry for External Battery connection 3 Bus bars for Utility input and Load output 4 Bus bars for External Battery connection CI Customer Interface Board see Fig 2 2 4 CR Connectivity Rack J35 P...

Страница 361: ...rid PACKING MATERIAL RECYCLING GE in compliance with environment protection uses only environmentally friendly material UPS packing materials must be recycled in compliance with all applicable regulat...

Страница 362: ...he unpacked UPS Forklift The UPS may be lifted with a forklift in upright position Take note of the center of gravity marked on the package Crane Fig 4 1 2 Position of the carrying belts when moving t...

Страница 363: ...q ft 848 kg m2 Dimensions and weights TLE Series 1000 Dimensions W x D x H 143 50 x 34 06 x 75 00 inches 3645 x 865 x 1905 mm Weight UPS complete 5732 lbs 2600 kg Power Section cabinet 3638 lbs 1650 k...

Страница 364: ...nces and with a temperature range not exceeding 13 F 25 C to 131 F 55 C In case the battery is included please refer to Section 4 3 2 Some important functions of the UPS such as the customized functio...

Страница 365: ...ined in Section 9 1 4 of the User Manual read and understand them The TLE Series 625 750 1000 UPS can radiate radio frequency energy Although some RFI Radio Frequency Interference filtering is inheren...

Страница 366: ...g the placement of the UPS These openings are covered with a protective plate Please remove the plates before drilling any holes TLES_UL_750_S1_UPS view top_01US FRONTAL SIDE 64 57 1640mm 118 12 3000...

Страница 367: ...does not require to be bolted to the floor The UPS cabinet can be fixed however to the floor by bolting it with the supporting blocks to the floor Fig 4 4 1 7 TLE Series 625 750 UPS cabinet floor fixi...

Страница 368: ...ase of Parallel System try to place the UPS modules in sequence of their numbers marked on the packing If the units are positioned side by side the side panels must be mounted on all units 0 53 13 5mm...

Страница 369: ...dditional 18 F 10 C that the battery ambient temperature is above 77 F 25 C The Battery System associated with larger UPS is usually either rack mounted or installed in multiple Battery Cabinets Insta...

Страница 370: ...n a dirty environment In order to prevent overheating of the UPS the available air intake flow rate must exceed the total air exhaust flow rate requirement of the UPS system Contact your Dealer or the...

Страница 371: ...TiltWatch device NOTE Take care not to damage the UPS when moving by forklift A damaged UPS must never be installed or connected to Utility or Battery In case of any damage sustained during the trans...

Страница 372: ...the Anti Humidity Corrosion devices TLE Series 1000 a Humidity indicator b Desiccant bag 17 pcs c VCI foil base d PE stretch foil PROTECTIVE FOIL Fig 4 6 5 Location of the Protective foil TLE Series...

Страница 373: ...delivered split into two cabinets Power Section cabinet and In Out Section cabinet Align them together with the Power Section cabinet on the left side cabinet with Control Panel Pay attention that no...

Страница 374: ...em together with the Power Section cabinet on the left side cabinet with Control Panel Pay attention that no loose cables are trapped when pushing the cabinets together Once finally positioned the two...

Страница 375: ...f size 60 10 x 270mm L2 Rectifier Interconnection L1 Rectifier 1 Bus bar of size 60 10 x 270mm L3 Rectifier Interconnection L1 Rectifier 1 Bus bar of size 60 10 x 270mm N Neutral Interconnection N Neu...

Страница 376: ...s bar of size 60 10 x 270mm L3 Rectifier Interconnection L1 Rectifier 1 Bus bar of size 60 10 x 270mm N Neutral Interconnection N Neutral 1 Bus bar of size 100 10 x 270mm In Out Section cabinet Bus ba...

Страница 377: ...male 32 poles Power Section cabinet In Out Section cabinet 3 XTR2A Connector Power Section cabinet In Out Section cabinet XTR2 Connector Fig 4 7 3 2 Connection of hearting connectors HAN connectors N...

Страница 378: ...n cabinet In Out Section cabinet H9 LEM H10 Power Section cabinet In Out Section cabinet H10 LEM H11 Power Section cabinet In Out Section cabinet H11 LEM H13 Power Section cabinet In Out Section cabin...

Страница 379: ...Connector Power Section cabinet In Out Section cabinet XTR2 Connector Fig 4 7 3 5 Connection of hearting connectors HAN connectors NOTE All these connections must be performed by QUALIFIED SERVICE PER...

Страница 380: ...cabinet In Out Section cabinet H9 LEM H10 Power Section cabinet In Out Section cabinet H10 LEM H11 Power Section cabinet In Out Section cabinet H11 LEM H13 Power Section cabinet In Out Section cabinet...

Страница 381: ...ut source or Dual Input sources if desired Common Input Utility Rectifier Bypass Fig 4 7 1 1 Common Input Utility Rectifier Bypass The same power source is to be used for both Bypass Supply and Rectif...

Страница 382: ...connected and grounded solidly due to the existence of voltage surge protection devices inside the UPS The connection of the Battery to the UPS must be protected with fuses or similar devices accordin...

Страница 383: ...UPS rating AC Input Rectifier AC Input Bypass AC Input DC Input F1 F2 F3 F4 Nom Max Nom Max TLE Series 625 782 880 752 782 880 1500 TLE Series 750 945 1025 902 945 1025 1810 TLE Series 1000 1260 1367...

Страница 384: ...5 6 55 65 75 40 50 60 4 70 85 95 55 65 75 3 85 100 110 65 75 85 2 95 115 130 75 90 100 1 110 130 150 85 100 115 1 0 125 150 170 100 120 135 2 0 145 175 195 115 135 150 3 0 165 200 225 130 155 175 4 0...

Страница 385: ...25 750 1000 Single UPS with Common Input Utility for Rectifier Bypass Single UPS with Common Input Utility for Rectifier Bypass 3 wires distribution 3 phase plus ground Single UPS with Dual Input Util...

Страница 386: ...PS_ISG_TLE_SUL_M62_1M0_2US_V010 docx Installation Guide TLE Series 625 750 1000 UL S2 UPS Parallel System with Common Input Utility Rectifier Bypass UPS Parallel System with Common Input Utility Recti...

Страница 387: ...e TLE Series 625 750 1000 UL S2 UPS Parallel System with Dual Input Utility for Rectifier Bypass Connect a single input Neutral to Bypass Utility inside the UPS common Neutral for Bypass and Rectifier...

Страница 388: ...rcuit between different poles The grounding and neutral connection of the electrical system must be in accordance with local regulations In case of additional cabinets containing batteries input outpu...

Страница 389: ...For UPS correct operation the input utility phase rotation must be clock wise CAUTION Panel A B C D E F and G should never be removed or replaced with power applied to the UPS These panels are in clos...

Страница 390: ...nnected to bus bars using M12 bolts The bolts of the connection cables must be tightened with a torque wrench at 530 Lb in 60 Nm Fig 4 9 4 TLE Series 625 750 1000 Power connection configuration bus ba...

Страница 391: ...onfiguration of the TLE Series 625 750 1000 is with top cable entry as standard It is possible to configure the bus bars with bottom cable entry see Fig 4 9 6 Battery connection cables are connected t...

Страница 392: ...L3 Load phase L3 N Neutral PE Ground External Battery connection Positive pole of the battery Negative pole of the battery PE Battery cabinet ground Bolt Size Torque M10 355 Lb in 40 Nm Before closing...

Страница 393: ...net must contain a Neutral Bus as per the following Figure 4 9 1 2 If no Neutral Connection is available with the Bypass Input 3 wires input ground and the Load does not require a Neutral solidly conn...

Страница 394: ...g 4 9 2 3 Output Load L1 Load phase A L1 L2 Load phase B L2 L3 Load phase L3 N Neutral PE Ground External Battery connection Positive pole of the battery Negative pole of the battery PE Battery cabine...

Страница 395: ...net must contain a Neutral Bus as per the following Figure 4 9 2 2 If no Neutral Connection is available with the Bypass Input 3 wires input ground and the Load does not require a Neutral solidly conn...

Страница 396: ...TLE Series 625 750 Interconnection links BR1 BR2 and BR3 NOTE For separate Bypass and Rectifier input configuration the interconnection links BR1 BR2 and BR3 MUST BE REMOVED see Fig 4 9 2 3 INTERCONNE...

Страница 397: ...oad phase L3 N Neutral PE Ground External Battery connection Positive pole of the battery Negative pole of the battery PE Battery cabinet ground Bolt Size Torque M10 355 Lb in 40 Nm Before closing the...

Страница 398: ...t must contain a Neutral Bus as per the following Figure 4 9 3 2 If no Neutral Connection is available with the Bypass Input 3 wires input ground and the Load does not require a Neutral solidly connec...

Страница 399: ...9 4 3 Output Load L1 Load phase A L1 L2 Load phase B L2 L3 Load phase L3 N Neutral PE Ground External Battery connection Positive pole of the battery Negative pole of the battery PE Battery cabinet gr...

Страница 400: ...net must contain a Neutral Bus as per the following Figure 4 9 4 2 If no Neutral Connection is available with the Bypass Input 3 wires input ground and the Load does not require a Neutral solidly conn...

Страница 401: ...TLE Series 1000 Interconnection links BR1 BR2 and BR3 NOTE For separate Bypass and Rectifier input configuration the interconnection links BR1 BR2 and BR3 MUST BE REMOVED see Fig 4 9 4 3 INTERCONNECT...

Страница 402: ...cteristic As the inverter output filter exhibits a predominantly capacitive characteristic it may provide some degree of reactive power compensation when combined with lagging power factor loads Conve...

Страница 403: ...of the UPS are set for frequency converter the eBoost Operation Mode is automatically disabled Fig 4 9 6 1 TLE Series 625 750 1000 Interconnection links BR1 BR2 and BR3 In order to avoid improper ope...

Страница 404: ...be the same for all units of the Parallel System no phase shift allowed between units NOTE It is strongly recommended that no transformers automatic circuit breakers or fuses should be inserted betwee...

Страница 405: ...les In this way communication is maintained between units in case one of the control cables should fail or be accidentally damaged or disconnected The standard length of the control bus cable between...

Страница 406: ...f a Parallel System the switches SW1 1 2 3 4 5 6 MUST BE IN POSITION ON see Fig 4 10 2 2 Fig 4 10 2 3 Bus connection on intermediate units Intermediate units of a RPA Parallel System On the two boards...

Страница 407: ...Access to the control bus connection The communication bus cable connectors are placed on the two boards P13 P14 IM0022 Bus Interface Board see Fig 4 10 3 1 and 4 10 3 2 Fig 4 10 3 3 View electronic...

Страница 408: ...NG THEM from the two boards P13 P14 IM0022 Bus Interface Board For reliability reasons the cables J1A J2A 1 2 3 4 5 and J1B J2B 1 2 3 4 5 connecting the units should be run in separated protected cond...

Страница 409: ...terminal block for EPO Emergency Power Off command connection When opened this contact causes the immediate opening of the Contactors K6 and K7 as well as the shut down of Rectifier Inverter and Stat...

Страница 410: ...hen the EPO Emergency Power Off has been activated the system must be restored as follows Realize the push button EPO Emergency Power Off contact on XA EPO 1 EPO 2 is closed again Perform the Inverter...

Страница 411: ...ds max 3 Customer Interface boards for each UPS max 2 3 ph SNMP WEB Plug in Adapter boards for Parallel System ATTENTION The installation of any option board must be performed by GE SERVICE TECHNICIAN...

Страница 412: ...o select printing of measurements alarms and parameters see User Manual to Section 6 4 SETUP PRINTER Fig 5 1 2 Serial port J35 P connection to PC with RS232 1 1 cable DB9m DB9f The serial port J35 P R...

Страница 413: ...ormally Open C Common NC Normally Closed Output signals on voltage free contacts Programmable functions on input contacts On terminals X1 6 of the following 27 signals can be selected from the display...

Страница 414: ...default is the following X1 1 2 3 NO C NC UTILITY FAILURE def Parameter RL 1 X1 4 5 6 NO C NC LOAD ON INVERTER def Parameter RL 3 X1 7 8 9 NO C NC STOP OPERATION def Parameter RL 5 X1 12 13 14 NO C N...

Страница 415: ...onsiderably unstable in frequency it should be suitable to install the signal GENERATOR ON on X1 11 22 See Fig 5 2 1 X1 Since the Parameter for of the reading of the Generator function is password pro...

Страница 416: ...connected to a separate AUX contact of the External Maintenance Bypass Switch 5 2 7 X1 terminal block eBoost IEMi control signal The UPS operation in either eBoost or IEMi operating modes can be cont...

Страница 417: ...docx Installation Guide TLE Series 625 750 1000 UL S2 6 NOTES 6 1 NOTES FORM It is recommended to note in this section Notes with date and short description all the operations performed on the UPS as...

Страница 418: ...Supply GE Consumer Industrial SA General Electric Company CH 6595 Riazzino Locarno Switzerland T 41 0 91 850 51 51 F 41 0 91 850 52 52 www gecriticalpower com imagination at work TLES_UL_625 750 1000...

Страница 419: ...evision Concern Date COPYRIGHT 2018 by GE Consumer Industrial SA All rights reserved The information contained in this publication is intended solely for the purposes indicated The present publication...

Страница 420: ...the use of the UPS Thank you for choosing GE START UP AND COMMISSIONING A GE GLOBAL SERVICES FIELD ENGINEER must perform start up and commissioning of the UPS Please Contact GE GLOBAL SERVICES at leas...

Страница 421: ...ned in this document WARNING TLE Series 625 750 1000 is a Category C3 UPS Product according to IEC 62040 2 This is a product for commercial and industrial application in the second environment install...

Страница 422: ...FOR SINGLE TLE SERIES 625 750 1000 57 7 1 1 Initial start up of the TLE Series 625 750 1000 57 7 1 2 Complete UPS shut down 61 7 1 3 Restore to normal operation after System shutdown with Load not sup...

Страница 423: ...ately during Commissioning and Maintenance of the UPS for the following Damaged components squeezed wires and cables or not correctly inserted plugs After removing the sidewalls of the UPS make sure t...

Страница 424: ...to short between individual or separate battery terminals or to the cabinet or rack Do not lay tools or metal parts on top of the battery and do not lay them where they could fall onto the battery or...

Страница 425: ...manual the following symbols are defined WARNING if instruction is not followed injury or serious equipment damage may occur CAUTION internal parts have dangerous voltage present Risk of electric sho...

Страница 426: ...1 TLE Series 625 750 General view Fig 2 1 4 Connectivity Rack Fig 2 1 3 Control Panel Fig 2 1 5 Q1 UPS Output switch Fig 2 1 2 TLE Series 625 750 General view with open doors TLES_UL_7500_S1_UPS_GE_02...

Страница 427: ...LE Series 1000 General view Fig 2 2 4 Connectivity Rack Fig 2 2 3 Control Panel Fig 2 2 5 Q1 UPS Output switch Fig 2 2 2 TLE Series 1000 General view with open doors TLES_UL_1000_S1_UPS_GE_02 TLES_160...

Страница 428: ...rt more total Load than any other UPS available allowing you to support a greater number of today s enterprise computing Power Factor Corrected PFC equipment High Efficiency Thanks to type Advanced Ne...

Страница 429: ...iminating all single points of failure The decentralized bypass offers great exibility to up or down grade the system in case future needs might change TLE Series 625 750 1000 BEST IN CLASS EFFICIENCY...

Страница 430: ...anks to modulation strategy applied to IGBT Bridge the rectifier provides clean input power in terms of low THDi and unity power factor Inverter The Inverter converts the DC voltage into a three phase...

Страница 431: ...ble the Load is normally powered through the Automatic Bypass When the Utility Voltage is detected out of the prescribed tolerances the Load is automatically transferred to the Inverter When the Utili...

Страница 432: ...4 3 When a Battery low warning occurs on a unit not necessary to support the present Load this unit will shut down after a timeout period selectable The Load is shared between the other units As the...

Страница 433: ...it condition is corrected the Load will be automatically transferred back to the Inverter Fig 4 2 5 1 Block diagram Automatic Bypass If the UPS is unable to return to normal mode following an automati...

Страница 434: ...common control circuitry see Fig 4 3 1 1 Parallel units for power capacity Several units can be paralleled in order to achieve output power greater than the maximum power of a single unit The maximum...

Страница 435: ...ommunicates with all other modules in order to act or react if necessary adapting to the new conditions 4 3 4 Synchronization All units are identical but one unit is arbitrarily selected as the refere...

Страница 436: ...of UPSs required to maintain a reliable supply to the critical load Then an efficiency optimization algorithm determines the best UPS configuration in order to maintain the running UPS in their highes...

Страница 437: ...hut down To remove the hazardous voltages it is necessary to manually open the IP cabinet fuses FU1 FU2 FU3 Fig 4 3 7 2 checking the presence of any voltage before working on the UPS Read carefully th...

Страница 438: ...be prepared in advance before the installation The installation must be performed only with the UPS system completely shut down The AC Rectifiers input power 4 must be the same with clockwise phase ro...

Страница 439: ...e identification label 4 6 WARRANTY GE operating through its authorized agents warrants that the standard products will be free of defects in materials and workmanship for a period as per contract spe...

Страница 440: ...G MATERIAL RECYCLING GE in compliance with environment protection uses only environmentally friendly material UPS packing materials must be recycled in compliance with all applicable regulations RECYC...

Страница 441: ...Control Panel positioned on the UPS front door acts as the UPS user interface Main features LCD Touch screen color graphic display See Chapter 6 Multilanguage communication interface English German It...

Страница 442: ...can be programmed to meet customer needs by changing parameters Operation commands of the UPS 6 1 HOME SCREEN Fig 6 1 1 LCD screen The LCD screen after 5 minutes of inactivity shuts down the backligh...

Страница 443: ...ction 6 2 EVENTS Shows in chronological order all the events occurred alarms messages commands handling etc See Section 6 3 SETUP Allows the user to customize some UPS functions to specific requiremen...

Страница 444: ...ervice Key yellow color Key for disabling the Service Key procedure Used only by the Service Center LEDS UPS STATUS LED LOAD PROTECTED green color When lit indicates that the UPS is functioning correc...

Страница 445: ...is open LED STOP OPERATION red color It warns about the imminent Inverter stop default parameter 3 min and the consequent Load shut down as result of The battery is fully discharged and the Load cann...

Страница 446: ...Synoptic Diagram LED 1 Rectifier LED 2 Inverter LED 3 Booster Battery charger LED 4 Automatic Bypass LED 5 LOAD Examples of typical scenarios in the Synoptic Diagram Load supplied by Inverter Load sup...

Страница 447: ...rameters like AC DC and various statistics In this mode the keys perform the following functions Return to HOME screen Shows the main screen EVENTS See Section 6 3 Shows the main screen SETUP See Sect...

Страница 448: ...ttery time Total operating time of the UPS on battery in hours BATTERY DISCHARGE COUNTER Residual Charge Level The number of discharges combined with the percentage of the available residual battery c...

Страница 449: ...lity on the last seven days Bypass quality index The statistic evaluation in 100 good 0 bad of the Bypass utility Status Bypass status free blocked INVERTER SCREEN Frequency The output frequency of th...

Страница 450: ...g time for the UPS in hours Active Power Total effective Load power kW eBoost operation time Total operating time for the UPS in eBoost Operation Mode in hours This counter is displayed only when eBoo...

Страница 451: ...e the keys perform the following functions Shows the main screen MEASURES See Section 6 2 Return to HOME screen Shows the main screen SETUP See Section 6 4 Shows the main screen COMMANDS See Section 6...

Страница 452: ...d to an event Nr 511 is the more recent Nr 1 is the first Data MM DD YYYY Exact hour of the moment when the event occurred HH MM SS thousandth Number of standard GE code of the event Explicit text des...

Страница 453: ...JA CRC FAILURE The parallel communication bus system is subject to high errors rate on channel JA 4007 BUS JB CRC FAILURE The parallel communication bus system is subject to high errors rate on channe...

Страница 454: ...VOLTAGE Dangerous high DC Voltage caused Inverter shut down Inverter restarts automatically after Battery returns to floating voltage 4117 BATTERY EARTH FAULT A leakage current to earth has been detec...

Страница 455: ...TRANSFORMER OVERTEMPERATURE The temperature sensor of the Inverter Transformer indicates overtemperature Elapsed stop operation time Inverter shut down With Utility OK Load is transferred on Utility...

Страница 456: ...Load remains supplied by Utility until the alarm stays ON 4522 FAN FAILURE The Fan Control Board indicates a malfunction of one or more ventilators 4530 LOAD LOCKED ON UTILITY Load is locked on Utili...

Страница 457: ...ply Board in particular from the DC supply Can be enabled or disabled with respective parameter 4702 LOSS OF REDUNDANCY A time of lost redundancy superior than specified in respective parameter was de...

Страница 458: ...efined settings 4124 MANUAL AUTOMATIC BOOST CHARGE STOP The automatic boost charge has finished The battery s voltage will return to the maintenance value A manually activated boost charge will finish...

Страница 459: ...d Off on the UPS Control Panel has been pressed with the output circuit switch Q1 closed 4562 DETOUR ON The auxiliary contact indicates that Manual Bypass Q2 only if provided by customer was closed 45...

Страница 460: ...eration Mode will be temporarily inhibited 4609 eBoost INHIBITED LOW LOAD eBoost Operation Mode inhibited due to minimal load not reached 4699 BATTERY TEST IMPOSSIBLE Automatic Battery Test is not pos...

Страница 461: ...ssible without password protection In this mode the keys perform the following functions Shows the main screen MEASURES See Section 6 2 Shows the main screen EVENTS See Section 6 3 Return to HOME scre...

Страница 462: ...d values are XON standing for the XON XOFF protocol or None standing for any protocol PRINTER COMMANDS By using the keys MEASURES ALARMS PARAMETERS ALL it is possible to print selected data NOTE Pleas...

Страница 463: ...the value is No the UPS is normally operating in VFI double conversion mode at all times When the UPS is in eBoost Operating Mode the eBoost LED is ON green light NOTE The configuration of the activat...

Страница 464: ...value NOTE To avoid undesired eBoost Operation Mode verify Date and Time eBoost screen how many hours of eBoost Operation Mode have been selected for each day of the week NOTE The eBoost Operation Mo...

Страница 465: ...test of all Inverters in the system at least 1 minute of normal operation must be programmed during the week the Yes No parameter is automatically disabled if this condition is not satisfied In case t...

Страница 466: ...n how many hours of IEMi Operation Mode have been selected for each day of the week NOTE For IEMi Operation Mode to become active a manual Inverter start is required at start up and after a Load Off r...

Страница 467: ...ows the user to execute UPS operation commands In this mode the keys perform the following functions Shows the main screen MEASURES See Section 6 2 Shows the main screen EVENTS See Section 6 3 Shows t...

Страница 468: ...tching ON command NOTE When eBoost Operation Mode or IEMi Operation Mode is enabled control of Inverter status and selection of the feed path is done autonomously by the UPS control logic Therefore In...

Страница 469: ...status Shows the Module shutdown status ACTIVE NOT ACTIVE System shutdown System shutdown Load Off command for an RPA Parallel System NOTE This command will immediately disconnect the Load System shut...

Страница 470: ...zzer TEST Acoustical alarm test acoustical alarm should be always activated Module shutdown procedure Guides throught the procedures to shutdown a single UPS or a RPA Parallel System unit Attention Fo...

Страница 471: ...some information on the RPA Parallel System In this mode the keys perform the following functions Shows the main screen MEASURES See Section 6 2 NOTE During IEMi Operation Mode the Percent Load inform...

Страница 472: ...t of the RPA System Parallel Input Utility status for RECT Rectifier and BYP Bypass Battery status for CHRG Battery Charger green color On grey color Off Q1 Load output switch Q2 Manual Bypass switch...

Страница 473: ...step instructions given below However we recommend that at least the initial procedure should be performed by an instructed person Check after every step for correct reaction of the UPS LEDs on the pa...

Страница 474: ...afety screens are fixed in their position The switch Q1 is open Pos O and the External Battery Protections must be open Pos O Q1 UPS Output switch LEDs on Synoptic Diagram LED 1 Rectifier LED 2 Invert...

Страница 475: ...grity and reliability of the UPS UPS Language This parameter allows the choice of language used to display the information Date dd mm yyyy You can adjust the date of the real time clock existing in th...

Страница 476: ...harge 1 41Vdc for cell 284 309 cells x 1 41Vdc 401 436Vdc NiCd Battery with boost charge 1 41 1 55 boost charge Vdc for cell 281 cells x 1 41Vdc 397 436 Vdc Flooded Lead Acid Battery without boost cha...

Страница 477: ...ions NOTE Before performing the next procedure 4 make sure that the LED 3 Booster Battery charger is lit 4 Insert the Inverter performing the command Inverter ON Perform the Inverter ON command from t...

Страница 478: ...hutdown Load is disconnected from UPS Rectifier and Inverter are shut down and all contactors are opened LED 1 Rectifier and LED 2 Inverter are OFF LED ALARM is lit 2 Open Q1 UPS Output switch Pos O 3...

Страница 479: ...MUST BE CLOSED External Battery Protections MUST BE DISCONNECTED If eBoost option is available make sure that eBoost Operation Mode is disabled before starting this procedure View of the Synoptic Dia...

Страница 480: ...ctions NOTE Before performing the next procedure 3 make sure that the LED 3 Booster Battery charger is lit 3 Insert the Inverter performing the command Inverter ON Perform the Inverter ON command from...

Страница 481: ...s MUST BE DISCONNECTED If eBoost option is available make sure that eBoost Operation Mode is disabled before starting this procedure View of the Synoptic Diagram after performed the command EPO Emerge...

Страница 482: ...ctions NOTE Before performing the next procedure 4 make sure that the LED 3 Booster Battery charger is lit 4 Insert the Inverter performing the command Inverter ON Perform the Inverter ON command from...

Страница 483: ...open Open the front door and make sure that All the connections to the input output terminals or bus bars of the UPS have been made correctly The safety screens are fixed in their position The switch...

Страница 484: ...grity and reliability of the UPS UPS Language This parameter allows the choice of language used to display the information Date dd mm yyyy You can adjust the date of the real time clock existing in th...

Страница 485: ...harge 1 41Vdc for cell 284 309 cells x 1 41Vdc 401 436Vdc NiCd Battery with boost charge 1 41 1 55 boost charge Vdc for cell 281 cells x 1 41Vdc 397 436 Vdc Flooded Lead Acid Battery without boost cha...

Страница 486: ...ht DC polarities on both side of the switch fuse holder 3 Connect the Battery to the UPS by closing the External Battery Protections 4 Insert the Inverter performing the command Inverter ON Before per...

Страница 487: ...rom UPS Rectifier and Inverter are shut down and all contactors are opened LED 1 Rectifier and LED 2 Inverter are OFF LED ALARM is lit 2 Open Q1 UPS Output switch Pos O 3 Disconnect the Battery from t...

Страница 488: ...tatus Q1 UPS Output switch MUST BE CLOSED External Battery Protections MUST BE DISCONNECTED View of the Synoptic Diagram after performed the command System shutdown with LOAD NOT SUPPLIED 1 Restore th...

Страница 489: ...ng the command Inverter ON Perform the Inverter ON command from the screen Commands 1 Inverter ON Soft start of Inverter indicated with blinking LED 2 Inverter At the end of Soft start the LED 2 Inver...

Страница 490: ...ration make sure that the UPS is in the following status Q1 UPS Output switch MUST BE CLOSED External Battery Protections MUST BE DISCONNECTED View of the Synoptic Diagram after performed the command...

Страница 491: ...y closing the External Battery Protections NOTE Before performing the next procedure 4 make sure that the LED 3 Booster Battery charger is lit 4 Insert the Inverter performing the command Inverter ON...

Страница 492: ...e fixed in their position The switch Q1 is open Pos O and the External Battery Protections must be open Pos O Q1 UPS Output switch LEDs on Synoptic Diagram LED 1 Rectifier LED 2 Inverter LED 3 Booster...

Страница 493: ...grity and reliability of the UPS UPS Language This parameter allows the choice of language used to display the information Date dd mm yyyy You can adjust the date of the real time clock existing in th...

Страница 494: ...harge 1 41Vdc for cell 284 309 cells x 1 41Vdc 401 436Vdc NiCd Battery with boost charge 1 41 1 55 boost charge Vdc for cell 281 cells x 1 41Vdc 397 436 Vdc Flooded Lead Acid Battery without boost cha...

Страница 495: ...ure It indicates that the DC link 1 and DC link 2 has reached 400Vdc see screen MEASURES Rectifier Attention check the right DC polarities on both side of the switch fuse holder 3 Connect the Battery...

Страница 496: ...to Inverter LED ALARM turns Off and the LED LOAD PROTECTED must be lit The Synoptic Diagram on all UPS units must display the status LOAD SUPPLIED BY INVERTER Synoptic Diagram of first unit Synoptic D...

Страница 497: ...tatus Load supplied from all Inverters of the Redundant Parallel System 1 Disconnect the Inverter performing the Inverter OFF command on the Unit to separate 1 Perform the Inverter OFF command from th...

Страница 498: ...Protections Press MUTE key to reset Acoustical Alarm LED ALARM remains lit Synoptic diagram of the unit to separate Synoptic diagram of other units NOTE Before performing the next procedure 5 wait 5...

Страница 499: ...before starting this procedure Open the front door of the Unit to reconnect and make sure that All the connections to the input output terminals or bus bars of the UPS have been made correctly The pro...

Страница 500: ...o reconnect by closing the External Battery Protections Synoptic diagram of the unit to reconnect Synoptic diagram of other units 4 Insert the Inverter performing the command Inverter ON on the Unit t...

Страница 501: ...screen Commands 1 System shutdown Shutdown Load is disconnected from UPS Parallel System Rectifiers and Inverters are shut down and all Contactors are opened LED ALARM is lit Synoptic diagram of first...

Страница 502: ...is disabled before starting this procedure If IEMi option is available make sure that IEMi Operation Mode is disabled before starting this procedure View of the Synoptic Diagram on all UPS units afte...

Страница 503: ...rter remains lit In case of sufficient output power the output will transfer to Inverter LED ALARM turns Off and the LED LOAD PROTECTED must be lit Synoptic diagram of first unit Synoptic diagram of o...

Страница 504: ...efore starting this procedure If IEMi option is available make sure that IEMi Operation Mode is disabled before starting this procedure View of the Synoptic Diagram on all UPS units after performed th...

Страница 505: ...rter remains lit In case of sufficient output power the output will transfer to Inverter LED ALARM turns Off and the LED LOAD PROTECTED must be lit Synoptic diagram of first unit Synoptic diagram of o...

Страница 506: ...itical conditions In addition comprehensive data collection and analysis improves diagnostics capability and enhances response time Continuous monitoring and ongoing maintenance help ensure maximum pe...

Страница 507: ...tion the unit has not been serviced for the last 20 000 hours by a GE TRAINED TECHNICIAN Some components of the UPS which need periodic maintenance if not replaced could cause a reliability reduction...

Страница 508: ...Battery Test to verify the full runtime of the Battery the charger needs at least 8 hours to recharge the Battery up to 90 of its capacity Long shut down periods of the UPS system To guarantee that t...

Страница 509: ...10 docx User Manual TLE Series 625 750 1000 UL S2 10 NOTES 10 1 NOTES FORM It is recommended to note in this section Notes with date and short description all the operations performed on the UPS as ma...

Отзывы: