Modifications reserved
Page 41/90
GE_UPS_USM_TLE_SUL_40K_M15_1US_V010.docx
User Manual
TLE Scalable Series 40 - 150 UL S1
Code
Message
Description
4604
COMMAND IEMi ON
The IEMi Operation Mode function is enabled, and
according to the time program the UPS system will
run in IEMi Operation Mode.
4605
COMMAND IEMi OFF
The IEMi Operation Mode has been disabled or the
programmed time is expired.
4606
SEM/IEMi ACTIVATION ALLOWED
SEM/IEMi control signal has been cleared on the
Customer Interface Board (X1 - 11, 22).
Operating mode depends on scheduled activation
of the functions.
4607
SEM/IEMi ACTIVATION INHIBITED
Customer Interface Board (X1 - 11, 22) received an
SEM/IEMi control signal.
SEM™ Operation Mode and IEMi Operation Mode
will be temporarily inhibited.
4609
SEM INHIBITED - LOW LOAD
SEM™ Operation Mode inhibited due to minimal
load not reached.
4699
BATTERY TEST IMPOSSIBLE
Automatic Battery Test is not possible due to:
-
No Utility Rectifier or Bypass.
-
Battery not fully charged.
-
Load is below 10% or above 80%.
Test is postponed for 1 week.
4763
REMOTE CONTROL ON
Inverter can be started or shut-down by remote
control.
Commands source can be chosen depending on
the value of parameter (Service only):
0 = Only local panel
1 = Only Remote Control
2 = Both
4764
REMOTE CONTROL OFF
Inverter cannot be started or shut-down by remote
control.
Commands source can be chosen depending on
the value of parameter (Service only):
0 = Only local panel
1 = Only Remote Control
2 = Both
4798
SERVICE KEY ACTIVATED
A valid Service Key has been entered.
It will no longer be requested in the next 6 hours.
4799
SERVICE KEY DEACTIVATED
The Service Key validity period has expired.
Содержание FGC TLE Series
Страница 1: ...TLE SERIES UPS 40 150 KVA KW 480 VAC Three phase Highly Efficient and Scalable GE Industrial Solutions...
Страница 14: ...14 LP33 Series II UPS www gecriticalpower com Notes...
Страница 15: ...15 LP33 Series II UPS www gecriticalpower com Notes...
Страница 333: ...TLE Series UPS 225 1500 kW for best in class multi mode operating efficiency...