Modifications reserved
Page 78/90
GE_UPS_USM_TLE_SUL_40K_M15_1US_V010.docx
User Manual
TLE Scalable Series 40 - 150 UL S1
7.3.2
Separate a UPS unit from the Redundant Parallel System
NOTE !
Make sure that
SEM Operation Mode
is disabled before starting this procedure.
If
IEMi
option is available, make sure that
IEMi Operation Mode
is disabled before
starting this procedure.
NOTE !
The
Load
is powered by the
UPS Redundant Parallel System
.
One UPS unit of the
Parallel System
has to be turned Off, while the
Load
is shared
between the other units supplying the parallel bus.
WARNING !
The control bus cable connecting
J1A - J2A
and
J1B - J2B
cannot be connected or
disconnected after the system has been powered on.
Initial status
:
Load supplied from all Inverters of the
Redundant Parallel System
.
1. Disconnect the Inverter performing the “Inverter OFF” command
on the Unit to separate
.
1 - Perform the
“Inverter OFF”
command from the screen:
Commands 1 / Inverter /
OFF
.
2 - Repeat the
“Inverter OFF”
command from the screen:
Commands 1 / Inverter /
OFF
.
With
Redundant System
, performing the
“Inverter OFF”
command the
Inverter
shuts down and it will stay OFF.
Performing the
“Inverter OFF”
command the
Load
is transferred to the
Utility
and the
Inverter
remains
operating, it means the system is not redundant.
In this case is not possible to switch-OFF one unit without transferring the
Load
on
Utility
.
•
Load
supplied from
Inverter(s)
of the other Unit(s) of the
Parallel System.
Synoptic diagram of the unit to separate
Synoptic diagram of other units
2. Open “Q1 - UPS Output switch” (Pos. O) on the Unit to separate.
•
LED ALARM
is lit.
Synoptic diagram of the unit to separate
Synoptic diagram of other units
Continue
→
Содержание FGC TLE Series
Страница 1: ...TLE SERIES UPS 40 150 KVA KW 480 VAC Three phase Highly Efficient and Scalable GE Industrial Solutions...
Страница 14: ...14 LP33 Series II UPS www gecriticalpower com Notes...
Страница 15: ...15 LP33 Series II UPS www gecriticalpower com Notes...
Страница 333: ...TLE Series UPS 225 1500 kW for best in class multi mode operating efficiency...