Page 81/92
GE_UPS_USM_TLE_SUL_M62_1M0_2US_V010.docx
User Manual
TLE Series 625 - 750 - 1000 UL S2
3. Perform the command “Module shutdown” on the
Unit to separate only when the symbol Q1 in the
Synoptic Diagram is shown open.
Perform the command
“Module shutdown
” through
the
screen:
Commands 1 / Module shutdown /
Shutdown
.
Synoptic diagram of the unit to separate
Synoptic diagram of other units
4. Disconnect the Battery on the Unit to separate by opening the “External Battery Protections”.
Press
“MUTE”
key to reset
Acoustical Alarm
.
LED ALARM
remains lit.
Synoptic diagram of the unit to separate
Synoptic diagram of other units
NOTE !
Before performing the next procedure (5) wait 5 minutes for
DC-Link Capacitors
discharge.
Use the
MEASURES/Rectifier
screen to ensure that the
DC-link1 and DC-link 2
voltage
has reached 10Vdc.
5. Disconnect the Utility supply on the Unit to separate
.
LCD display is Off
Synoptic diagram of the unit to separate
Synoptic diagram of other units
END OF PROCEDURE
DANGER !
It will take 5 minutes for the DC capacitors to discharge.
Open only the front door, do not open any other part of the UPS.
NOTE !
For any further intervention contact nearest
Service Center
.
Содержание FGC TLE Series
Страница 1: ...TLE SERIES UPS 40 150 KVA KW 480 VAC Three phase Highly Efficient and Scalable GE Industrial Solutions...
Страница 14: ...14 LP33 Series II UPS www gecriticalpower com Notes...
Страница 15: ...15 LP33 Series II UPS www gecriticalpower com Notes...
Страница 333: ...TLE Series UPS 225 1500 kW for best in class multi mode operating efficiency...