background image

NS Series 

Uninterruptible Power Supply 

User Manual 

NS1500/2200/3000-1T 

SAVE THIS MANUAL 

This manual contains important instructions that should be followed during 

installation, operation, and storage of this UPS.  Please read these 

instructions carefully before installation and start-up of the UPS. 

Содержание NS Series

Страница 1: ...nual NS1500 2200 3000 1T SAVE THIS MANUAL This manual contains important instructions that should be followed during installation operation and storage of this UPS Please read these instructions carefully before installation and start up of the UPS ...

Страница 2: ..._________16 6 1 General Problems _______________________________________________16 7 Specifications______________________________________________________18 FCC Part 15 NOTICE Pursuant to section 15 of the FCC rules this product has been tested and thereby complies with the conditions of a Class B digital device which have been established for offering sufficient protection against dangerous interf...

Страница 3: ...cally under normal power conditions During a power failure it can provide immediate back up power from the batteries without any interruption When an overload or UPS malfunction occurs the system will automatically transfer to bypass mode and continue supplying output equipment with utility power When the overload is removed the UPS will automatically transfer back to inverter mode Malfunctions ma...

Страница 4: ...User Manual NS1500 2200 3000 1T Front Rear Panel of NS1500 Rear Panel of NS1500 2 Rev 11 2005 Control Panel ...

Страница 5: ...User Manual NS1500 2200 3000 1T 3 Rev 11 2005 Standard Outlets of NS1500 Standard Outlets of NS2200 NS3000 ...

Страница 6: ...ing any repairs Apart from battery replacement all maintenance and service work should be performed by qualified service personnel Turn off the UPS and unplug it from the AC power source before battery replacement Do not connect your UPS to an outlet that is not properly grounded Do not remove the ground connection from the UPS power plug UPS LOCATION PLACEMENT AND CONNECTION Install the UPS in a ...

Страница 7: ...S BATTERY WARNING This UPS contains a sealed lead acid battery DO NOT open the battery DO NOT short or bridge the battery terminals with any object Once the battery has reached the end of its life ensure that they are properly disposed REFER TO YOUR LOCAL LAWS AND REGULATIONS FOR BATTERY DISPOSAL REQUIREMENTS ...

Страница 8: ...tput power of the UPS as indicated on the UPS rear panel and specifications shown in Section 7 2 Connect the power cord of the UPS to a working grounded AC wall socket 3 Charge the batteries for 8 hours before use When the power cord is plugged into the wall outlet and AC power is available the UPS will automatically recharge its batteries You may use the UPS immediately without recharging but the...

Страница 9: ...e input switch from the rear panel 3 The UPS begins its auto start sequence This takes about ten seconds 4 When the LINE and INVERTER LEDs are lit the UPS will be ready for use 4 3 Turn Off the UPS 1 Press ON OFF button The INVERTER LED will turn off and the BYPASS LED turns on 2 Turn off the input switch from the rear panel All LEDs will turn off ...

Страница 10: ...ery is going to enter cut off state The battery voltage level for each LED indication is as follows NS1500 NS2200 NS3000 100 52 8V 79 2V 105 6V 75 49 6V 52 8V 74 4V 79 2V 99 2V 105 6V 50 44 0 49 6V 66 0 74 4V 88 0 99 2V 25 42 0 44 0V 63 0 66 0V 84 0 88 0V 4 5 Control Panel Buttons ON OFF 1 When utility power is available the UPS can be turned on or shut off by pressing the ON OFF button 2 When the...

Страница 11: ...below LED Indicator Bit Name Bit Def BATTERY 100 Bit 7 Bit Status BATTERY 75 Bit 6 Not defined BATTERY 50 Bit 5 Not defined BATTERY 25 Bit 4 Not defined LOAD 100 Bit 3 Green Mode LOAD 75 Bit 2 Not defined LOAD 50 Bit 1 O P Voltage LOAD 25 Bit 0 O P Voltage Bit Status Bit 7 Definitions Bit Name Bit 7 LED off 0 LED on 1 Bit 3 0 Enable Green Mode 1 Disable Green Mode Bit 1 Bit 0 00 100VAC output 01 1...

Страница 12: ...e Alarms The audible alarms are designed into two segments Each segment can exist alone or at the same time as the other First segment Output Overload long beep for few seconds with related LED Battery Low during discharging short beep continuously System Abnormal long beep for few seconds with related LED Utility Abnormal two short beep continuously Charger Abnormal long beep continuously Second ...

Страница 13: ...eady 4 5 Signal Ground Signal Ground 5 A RS232 ISOP interface Card NOTE An SNMP card will not work with the standard RS232 card which comes with the NS series UPS If you want to use an SNMP card then the RS232 card must be replaced by a RS232 ISOP card Software UPSilon 2000 9 pin Cables SPECIAL Cables Non standard Supported MS Windows 95 98 NT 2000 Me XP Novell NetWare v3 x v4 x v5 x Linux FreeBSD...

Страница 14: ... B RS232 Interface Card Software UPSilon 2000 9 pin Cables SPECIAL Cables Non standard PC Cables standard Supported MS Windows 95 98 NT 2000 Me XP Novell NetWare v3 x v4 x v5 x Linux FreeBSD J3 J4 J5 RS232 Card J6 C Optional DB9 ISOP Interface Card ...

Страница 15: ...pin Cables SPECIAL Cables Non standard Supported Windows 3 1 95 98 NT 2000 Me XP Novell NetWare 3 1x 4 x 5 x MS DOS Linux J3 FAULT J6 J7 J5 J4 LOW BAT DB9 ISOP Card J2 REMOTE SHUTDOWN J9 Function J PIN of J Definition For LED Panel SELECT LED LCD PANEL J9 For LCD Panel PIN of DB9 FUNCTION 1 2 BATTERY LOW 3 4 5 POWER FAILURE 6 7 REMOTE SHUTDOWN UPS 8 9 FAULT PIN UPS PIN PC 5 1 4 7 3 2 8 ...

Страница 16: ...UTPUT 3 POWER FAILURE normally closed state will become open during active state OUTPUT 4 Reference GND for pin 2 3 and 5 OUTPUT 5 BATTERY LOW normally open state will become closed during active state OUTPUT 6 Remote shutdown UPS keep this pin at high voltage 5V 12V Needs 500 ms to shut down UPS Activates at battery mode INPUT 8 FAULT normally open state will become closed during UPS fault OUTPUT...

Страница 17: ...LECT LED LCD PANEL J12 For LED Panel 5 Storage 1 Before storing charge the batteries for at least 24 hours 2 Be sure that the UPS is switched off and that no cable is connected to the interface port 3 Store the UPS in a dry location with a storage temperature within 4 F to 113 F 20 C to 45 C 4 If the unit is to be stored for an extended period of time then the batteries must be recharged once ever...

Страница 18: ...wer 0301 UPS operates in DC mode although utility power exists AC detecting circuit failed Call for service 0302 UPS still in bypass mode after disabling green mode function UPS still in POWER OFF status Press power ON OFF button an audible beep will sound and the UPS reverts to normal 0401 UPS is proceeding controlling process Wait for a while to operate the UPS 0501 Buttons on front panel don t ...

Страница 19: ... abnormal Call for service center 1102 Internal overheating Check the ventilation 1201 Five short beep continuously Fan failure Call for service to replace the fan 1202 Four short beep continuously PFC over load protect in action due to low AC input check input AC power or release some load 1301 AC input is abnormal due to input voltage and UPS goes into DC mode Disconnect input AC power and check...

Страница 20: ...e Green Mode Load under 30W Load under 60W Load under 90W Audible Noise 45dBA BATTERY Voltage Cells 48V 4pcs 72V 6pcs 96V 8pcs Type Weight 12V7AH sealed lead acid 5 5 lbs 2 5kgs pc Backup Time 6min typical for full load 15min for half load Recharge Time 8 hours to 90 capacity CONTROL PANEL Buttons ON OFF FUNCTION and SET Indicators Fault Charger PFC OL Green Line Boost Inverter Bypass Load 25 50 7...

Отзывы: