3-16
F60 Feeder Protection System
GE Multilin
3.2 WIRING
3 HARDWARE
3
Refer to the
Digital elements
section of chapter 5 for an example of how form-A and solid-state relay contacts can be
applied for breaker trip circuit integrity monitoring.
Relay contacts must be considered unsafe to touch when the unit is energized! If the relay contacts need to
be used for low voltage accessible applications, it is the customer’s responsibility to ensure proper insula-
tion levels!
USE OF FORM-A AND SOLID-STATE RELAY OUTPUTS IN HIGH IMPEDANCE CIRCUITS
For form-A and solid-state relay output contacts internally equipped with a voltage measuring cIrcuit across the
contact, the circuit has an impedance that can cause a problem when used in conjunction with external high input
impedance monitoring equipment such as modern relay test set trigger circuits. These monitoring circuits may con-
tinue to read the form-A contact as being closed after it has closed and subsequently opened, when measured as
an impedance.
The solution to this problem is to use the voltage measuring trigger input of the relay test set, and connect the form-
A contact through a voltage-dropping resistor to a DC voltage source. If the 48 V DC output of the power supply is
used as a source, a 500
Ω
, 10 W resistor is appropriate. In this configuration, the voltage across either the form-A
contact or the resistor can be used to monitor the state of the output.
Wherever a tilde “~” symbol appears, substitute with the slot position of the module; wherever a number
sign "#" appears, substitute the contact number
When current monitoring is used to seal-in the form-A and solid-state relay contact outputs, the Flex-
Logic™ operand driving the contact output should be given a reset delay of 10 ms to prevent damage of
the output contact (in situations when the element initiating the contact output is bouncing, at values in the
region of the pickup value).
Table 3–2: DIGITAL INPUT/OUTPUT MODULE ASSIGNMENTS
~6A MODULE
~6B MODULE
~6C MODULE
~6D MODULE
TERMINAL
ASSIGNMENT
OUTPUT OR
INPUT
TERMINAL
ASSIGNMENT
OUTPUT OR
INPUT
TERMINAL
ASSIGNMENT
OUTPUT
TERMINAL
ASSIGNMENT
OUTPUT
~1
Form-A
~1
Form-A
~1
Form-C
~
1a,
~
1c
2 Inputs
~2
Form-A
~2
Form-A
~2
Form-C
~
2a,
~
2c
2 Inputs
~3
Form-C
~3
Form-C
~3
Form-C
~
3a,
~
3c
2 Inputs
~4
Form-C
~4
Form-C
~4
Form-C
~
4a,
~
4c
2 Inputs
~5a, ~5c
2 Inputs
~5
Form-C
~5
Form-C
~
5a,
~
5c
2 Inputs
~6a, ~6c
2 Inputs
~6
Form-C
~6
Form-C
~
6a,
~
6c
2 Inputs
~7a, ~7c
2 Inputs
~7a, ~7c
2 Inputs
~7
Form-C
~
7a,
~
7c
2 Inputs
~8a, ~8c
2 Inputs
~8a, ~8c
2 Inputs
~8
Form-C
~
8a,
~
8c
2 Inputs
~6E MODULE
~6F MODULE
~6G MODULE
~6H MODULE
TERMINAL
ASSIGNMENT
OUTPUT OR
INPUT
TERMINAL
ASSIGNMENT
OUTPUT
TERMINAL
ASSIGNMENT
OUTPUT OR
INPUT
TERMINAL
ASSIGNMENT
OUTPUT OR
INPUT
~
1
Form-C
~
1
Fast Form-C
~
1
Form-A
~1
Form-A
~
2
Form-C
~
2
Fast Form-C
~
2
Form-A
~2
Form-A
~
3
Form-C
~
3
Fast Form-C
~
3
Form-A
~3
Form-A
~
4
Form-C
~
4
Fast Form-C
~
4
Form-A
~4
Form-A
~
5a,
~
5c
2 Inputs
~
5
Fast Form-C
~
5a,
~
5c
2 Inputs
~5
Form-A
~
6a,
~
6c
2 Inputs
~
6
Fast Form-C
~
6a,
~
6c
2 Inputs
~6
Form-A
~
7a,
~
7c
2 Inputs
~
7
Fast Form-C
~
7a,
~
7c
2 Inputs
~
7a,
~
7c
2 Inputs
~
8a,
~
8c
2 Inputs
~
8
Fast Form-C
~
8a,
~
8c
2 Inputs
~
8a,
~
8c
2 Inputs
WARNING
NOTE
NOTE
NOTE
Содержание F60 UR Series
Страница 2: ......
Страница 4: ......
Страница 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 96: ...3 48 F60 Feeder Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3 ...
Страница 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Страница 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Страница 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Страница 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 558: ...x F60 Feeder Protection System GE Multilin INDEX ...