5-182
F60 Feeder Protection System
GE Multilin
5.6 CONTROL ELEMENTS
5 SETTINGS
5
5.6.10 DIGITAL COUNTERS
PATH: SETTINGS
ÖØ
CONTROL ELEMENTS
ÖØ
DIGITAL COUNTERS
Ö
COUNTER 1(8)
There are 8 identical digital counters, numbered from 1 to 8. A digital counter counts the number of state transitions from
Logic 0 to Logic 1. The counter is used to count operations such as the pickups of an element, the changes of state of an
external contact (e.g. breaker auxiliary switch), or pulses from a watt-hour meter.
•
COUNTER 1 UNITS:
Assigns a label to identify the unit of measure pertaining to the digital transitions to be counted.
The units label will appear in the corresponding actual values status.
•
COUNTER 1 PRESET:
Sets the count to a required preset value before counting operations begin, as in the case
where a substitute relay is to be installed in place of an in-service relay, or while the counter is running.
•
COUNTER 1 COMPARE:
Sets the value to which the accumulated count value is compared. Three FlexLogic™ output
operands are provided to indicate if the present value is ‘more than (HI)’, ‘equal to (EQL)’, or ‘less than (LO)’ the set
value.
•
COUNTER 1 UP:
Selects the FlexLogic™ operand for incrementing the counter. If an enabled UP input is received
when the accumulated value is at the limit of +2,147,483,647 counts, the counter will rollover to –2,147,483,648.
•
COUNTER 1 DOWN:
Selects the FlexLogic™ operand for decrementing the counter. If an enabled DOWN input is
received when the accumulated value is at the limit of –2,147,483,648 counts, the counter will rollover to
+2,147,483,647.
•
COUNTER 1 BLOCK:
Selects the FlexLogic™ operand for blocking the counting operation. All counter operands are
blocked.
COUNTER 1
COUNTER 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
COUNTER 1 NAME:
Counter 1
Range: 12 alphanumeric
characters
MESSAGE
COUNTER 1 UNITS:
Range: 6 alphanumeric characters
MESSAGE
COUNTER 1 PRESET:
0
Range: –2,147,483,648 to +2,147,483,647
MESSAGE
COUNTER 1 COMPARE:
0
Range: –2,147,483,648 to +2,147,483,647
MESSAGE
COUNTER 1 UP:
Off
Range: FlexLogic™ operand
MESSAGE
COUNTER 1 DOWN:
Off
Range: FlexLogic™ operand
MESSAGE
COUNTER 1 BLOCK:
Off
Range: FlexLogic™ operand
MESSAGE
CNT1 SET TO PRESET:
Off
Range: FlexLogic™ operand
MESSAGE
COUNTER 1 RESET:
Off
Range: FlexLogic™ operand
MESSAGE
COUNT1 FREEZE/RESET:
Off
Range: FlexLogic™ operand
MESSAGE
COUNT1 FREEZE/COUNT:
Off
Range: FlexLogic™ operand
Содержание F60 UR Series
Страница 2: ......
Страница 4: ......
Страница 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 96: ...3 48 F60 Feeder Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3 ...
Страница 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Страница 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Страница 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Страница 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 558: ...x F60 Feeder Protection System GE Multilin INDEX ...