GE Multilin
F60 Feeder Protection System
B-71
APPENDIX B
B.4 MEMORY MAPPING
B
F196
ENUMERATION: NEUTRAL DIRECTIONAL OVERCURRENT
OPERATING CURRENT
0 = Calculated 3I0, 1 = Measured IG
F199
ENUMERATION: DISABLED/ENABLED/CUSTOM
0 = Disabled, 1 = Enabled, 2 = Custom
F200
TEXT40: 40-CHARACTER ASCII TEXT
20 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB
F201
TEXT8: 8-CHARACTER ASCII PASSCODE
4 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB
F202
TEXT20: 20-CHARACTER ASCII TEXT
10 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB
F203
TEXT16: 16-CHARACTER ASCII TEXT
F204
TEXT80: 80-CHARACTER ASCII TEXT
F205
TEXT12: 12-CHARACTER ASCII TEXT
F206
TEXT6: 6-CHARACTER ASCII TEXT
F207
TEXT4: 4-CHARACTER ASCII TEXT
F208
TEXT2: 2-CHARACTER ASCII TEXT
F211
ENUMERATION: SOURCE SELECTION
0 = None, 1 = SRC 1, 2 = SRC 2, 3 = SRC 3, 4 = SRC 4,
5 = SRC 5, 6 = SRC 6
F220
ENUMERATION: PUSHBUTTON MESSAGE PRIORITY
F222
ENUMERATION: TEST ENUMERATION
0 = Test Enumeration 0, 1 = Test Enumeration 1
F224
ENUMERATION: RATE TREND FOR FREQ RATE OF CHANGE
0 = Increasing, 1 = Decreasing, 2 = Bidirectional
F226
ENUMERATION: REMOTE INPUT/OUTPUT TRANSFER
METHOD
0 = None, 1 = GSSE, 2 = GOOSE
F227
ENUMERATION: RELAY SERVICE STATUS
0 = Unknown, 1 = Relay In Service, 2 = Relay Out Of Service
F230
ENUMERATION: DIRECTIONAL POLARIZING
0 = Voltage, 1 = Current, 2 = Dual
F231
ENUMERATION: POLARIZING VOLTAGE
0 = Calculated V0, 1 = Measured VX
F232
ENUMERATION: CONFIGURABLE GOOSE DATASET ITEMS
FOR TRANSMISSION
value
priority
0
Disabled
1
Normal
2
High Priority
value
GOOSE dataset item
0
None
1
GGIO1.ST.Ind1.q
2
GGIO1.ST.Ind1.stVal
3
GGIO1.ST.Ind2.q
4
GGIO1.ST.Ind2.stVal
↓
↓
255
GGIO1.ST.Ind128.q
256
GGIO1.ST.Ind128.stVal
257
MMXU1.MX.TotW.mag.f
258
MMXU1.MX.TotVAr.mag.f
259
MMXU1.MX.TotVA.mag.f
260
MMXU1.MX.TotPF.mag.f
Содержание F60 UR Series
Страница 2: ......
Страница 4: ......
Страница 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 96: ...3 48 F60 Feeder Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3 ...
Страница 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Страница 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Страница 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Страница 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 558: ...x F60 Feeder Protection System GE Multilin INDEX ...