GE Multilin
F60 Feeder Protection System
5-173
5 SETTINGS
5.6 CONTROL ELEMENTS
5
5.6.8 AUTORECLOSE
PATH: SETTINGS
ÖØ
CONTROL ELEMENTS
ÖØ
AUTORECLOSE
Ö
AUTORECLOSE 1(2)
AUTORECLOSE 1
AR1 FUNCTION:
Disabled
Range: Disabled, Enabled
MESSAGE
AR1 INITIATE:
Off
Range: FlexLogic™ operand
MESSAGE
AR1 BLOCK:
Off
Range: FlexLogic™ operand
MESSAGE
AR1 MAX NUMBER OF
SHOTS: 1
Range: 1, 2, 3, 4
MESSAGE
AR1 REDUCE MAX TO 1:
Off
Range: FlexLogic™ operand
MESSAGE
AR1 REDUCE MAX TO 2:
Off
Range: FlexLogic™ operand
MESSAGE
AR1 REDUCE MAX TO 3:
Off
Range: FlexLogic™ operand
MESSAGE
AR1 MANUAL CLOSE:
Off
Range: FlexLogic™ operand
MESSAGE
AR1 MNL RST FRM LO:
Off
Range: FlexLogic™ operand
MESSAGE
AR1 RESET LOCKOUT IF
BREAKER CLOSED: Off
Range: Off, On
MESSAGE
AR1 RESET LOCKOUT ON
MANUAL CLOSE: Off
Range: Off, On
MESSAGE
AR1 BKR CLOSED:
Off
Range: FlexLogic™ operand
MESSAGE
AR1 BKR OPEN:
Off
Range: FlexLogic™ operand
MESSAGE
AR1 BLK TIME UPON
MNL CLS: 10.000 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR1 DEAD TIME 1:
1.000 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR1 DEAD TIME 2:
2.000 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR1 DEAD TIME 3:
3.000 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR1 DEAD TIME 4:
4.000 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR1 ADD DELAY 1:
Off
Range: FlexLogic™ operand
MESSAGE
AR1 DELAY 1:
0.000 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR1 ADD DELAY 2:
Off
Range: FlexLogic™ operand
Содержание F60 UR Series
Страница 2: ......
Страница 4: ......
Страница 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 96: ...3 48 F60 Feeder Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3 ...
Страница 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Страница 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Страница 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Страница 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 558: ...x F60 Feeder Protection System GE Multilin INDEX ...