GE Multilin
F60 Feeder Protection System
B-45
APPENDIX B
B.4 MEMORY MAPPING
B
AA46
...Repeated for IEC 61850 GOOSE analog input 11
AA4D
...Repeated for IEC 61850 GOOSE analog input 12
AA54
...Repeated for IEC 61850 GOOSE analog input 13
AA5B
...Repeated for IEC 61850 GOOSE analog input 14
AA62
...Repeated for IEC 61850 GOOSE analog input 15
AA69
...Repeated for IEC 61850 GOOSE analog input 16
IEC 61850 GOOSE/GSSE Configuration (Read/Write Setting)
AA80
Default GOOSE/GSSE Update Time
1 to 60
s
1
F001
60
AA81
IEC 61850 GSSE Function (GsEna)
0 to 1
---
1
F102
1 (Enabled)
AA82
IEC 61850 GSSE ID
---
---
---
F209
“GSSEOut”
AAA3
IEC 61850 GOOSE Function (GoEna)
0 to 1
---
1
F102
0 (Disabled)
AAA4
IEC 61850 GSSE Destination MAC Address
---
---
---
F072
0
AAA7
IEC 61850 Standard GOOSE ID
---
---
---
F209
“GOOSEOut”
AAC8
IEC 61850 Standard GOOSE Destination MAC Address
---
---
---
F072
0
AACB
IEC 61850 GOOSE VLAN Transmit Priority
0 to 7
---
1
F001
4
AACC
IEC 61850 GOOSE VLAN ID
0 to 4095
---
1
F001
0
AACD
IEC 61850 GOOSE ETYPE APPID
0 to 16383
---
1
F001
0
AACE
Reserved (2 items)
0 to 1
---
1
F001
0
IEC 61850 Server Configuration (Read/Write Settings/Commands)
AAD0
TCP Port Number for the IEC 61850 / MMS Protocol
1 to 65535
---
1
F001
102
AAD1
IEC 61850 Logical Device Name
---
---
---
F213
“IECName”
AAE1
IEC 61850 Logical Device Instance
---
---
---
F213
“LDInst”
AAF1
IEC 61850 LPHD Location
---
---
---
F204
“Location”
AB19
Include non-IEC 61850 Data
0 to 1
---
1
F102
0 (Disabled)
AB1A
IEC 61850 Server Data Scanning Function
0 to 1
---
1
F102
0 (Disabled)
AB1B
Reserved (15 items)
IEC 61850 XCBR configuration (read/write settings)
AB24
Operand for IEC 61850 XCBR1.ST.Loc status
0 to 65535
---
1
F300
0
AB25
Command to clear XCBR1 OpCnt (operation counter)
0 to 1
---
1
F126
0 (No)
AB26
Operand for IEC 61850 XCBR2.ST.Loc status
0 to 65535
---
1
F300
0
AB27
Command to clear XCBR2 OpCnt (operation counter)
0 to 1
---
1
F126
0 (No)
AB28
Operand for IEC 61850 XCBR3.ST.Loc status
0 to 65535
---
1
F300
0
AB29
Command to clear XCBR3 OpCnt (operation counter)
0 to 1
---
1
F126
0 (No)
AB2A
Operand for IEC 61850 XCBR4.ST.Loc status
0 to 65535
---
1
F300
0
AB2B
Command to clear XCBR4 OpCnt (operation counter)
0 to 1
---
1
F126
0 (No)
AB2C
Operand for IEC 61850 XCBR5.ST.Loc status
0 to 65535
---
1
F300
0
AB2D
Command to clear XCBR5 OpCnt (operation counter)
0 to 1
---
1
F126
0 (No)
AB2E
Operand for IEC 61850 XCBR6.ST.Loc status
0 to 65535
---
1
F300
0
AB2F
Command to clear XCBR6 OpCnt (operation counter)
0 to 1
---
1
F126
0 (No)
IEC 61850 LN name prefixes (read/write settings)
AB30
IEC 61850 logical node LPHD1 name prefix
0 to 65534
---
1
F206
(none)
AB33
IEC 61850 logical node PIOCx name prefix (72 items)
0 to 65534
---
1
F206
(none)
AC0B
IEC 61850 logical node PTOCx name prefix (24 items)
0 to 65534
---
1
F206
(none)
AC53
IEC 61850 logical node PTUVx name prefix (13 items)
0 to 65534
---
1
F206
(none)
AC7A
IEC 61850 logical node PTOVx name prefix (10 items)
0 to 65534
---
1
F206
(none)
AC98
IEC 61850 logical node PDISx name prefix (10 items)
0 to 65534
---
1
F206
(none)
ACB6
IEC 61850 logical node RBRFx name prefix (24 items)
0 to 65534
---
1
F206
(none)
ACFE
IEC 61850 logical node RPSBx name prefix
0 to 65534
---
1
F206
(none)
AD01
IEC 61850 logical node RRECx name prefix (6 items)
0 to 65534
---
1
F206
(none)
AD13
IEC 61850 logical node MMXUx name prefix (6 items)
0 to 65534
---
1
F206
(none)
AD25
IEC 61850 logical node GGIOx name prefix (4 items)
0 to 65534
---
1
F206
(none)
AD31
IEC 61850 logical node RFLOx name prefix (5 items)
0 to 65534
---
1
F206
(none)
AD40
IEC 61850 logical node XCBRx name prefix (6 items)
0 to 65534
---
1
F206
(none)
AD52
IEC 61850 logical node PTRCx name prefix (6 items)
0 to 65534
---
1
F206
(none)
Table B–9: MODBUS MEMORY MAP (Sheet 37 of 53)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание F60 UR Series
Страница 2: ......
Страница 4: ......
Страница 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 96: ...3 48 F60 Feeder Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3 ...
Страница 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Страница 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Страница 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Страница 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 558: ...x F60 Feeder Protection System GE Multilin INDEX ...