GE Multilin
F60 Feeder Protection System
5-131
5 SETTINGS
5.5 GROUPED ELEMENTS
5
b) GROUND INSTANTANEOUS OVERCURRENT
(ANSI 50G)
PATH: SETTINGS
ÖØ
GROUPED ELEMENTS
Ö
SETTING GROUP 1(6)
ÖØ
GROUND CURRENT
ÖØ
GROUND IOC1(2)
The ground instantaneous overcurrent element may be used as an instantaneous element with no intentional delay or as a
definite time element. The ground current input is the quantity measured by the ground input CT and is the fundamental
phasor magnitude.
These elements measure the current that is connected to the ground channel of a CT/VT module. The conversion
range of a standard channel is from 0.02 to 46 times the CT rating.
This channel may be equipped with a standard or sensitive input. The conversion range of a sensitive channel is
from 0.002 to 4.6 times the CT rating.
Figure 5–61: GROUND IOC1 SCHEME LOGIC
GROUND IOC1
GROUND IOC1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
GROUND IOC1 SIGNAL
SOURCE: SRC 1
Range: SRC 1, SRC 2
MESSAGE
GROUND IOC1
PICKUP: 1.000
pu
Range: 0.000 to 30.000 pu in steps of 0.001
MESSAGE
GROUND IOC1 PICKUP
DELAY: 0.00
s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
GROUND IOC1 RESET
DELAY: 0.00
s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
GROUND IOC1 BLOCK:
Off
Range: FlexLogic™ operand
MESSAGE
GROUND IOC1
TARGET: Self-reset
Range: Self-reset, Latched
,
Disabled
MESSAGE
GROUND IOC1
EVENTS: Disabled
Range: Disabled, Enabled
NOTE
NOTE
S
ETT
I
NG
GROUND IOC1
FUNCTION:
Disabled = 0
Enabled = 1
S
ETT
I
NG
GROUND IOC1
SOURCE:
IG
GROUND IOC1
BLOCK:
Off = 0
FLEXLOG
I
C OPE
R
AND
S
GROUND IOIC DPO
GROUND IOC1 OP
S
ETT
I
NG
S
ETT
I
NG
IG
≥
PICKUP
GROUND IOC1
PICKUP:
RUN
GROUND IOC1 PICKUP
DELAY:
S
ETT
I
NG
S
GROUND IOC1 RESET
DELAY:
t
PKP
t
RST
827037A4.VSD
AND
GROUND IOC1 PKP
Содержание F60 UR Series
Страница 2: ......
Страница 4: ......
Страница 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 96: ...3 48 F60 Feeder Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3 ...
Страница 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Страница 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Страница 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Страница 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 558: ...x F60 Feeder Protection System GE Multilin INDEX ...