Modifications reserved
Page 45/103
OPM_LPS_33E_60K_M12_2GB_V010.doc
Operating Manual
LP 33 Series 60-80-100-120 kVA / S2
5.8.7 RPA Parallel System - Control bus connection
WARNING !
This operation must be performed by trained personnel before the initial start-up
(ensure that the UPS installation is completely powered down).
LPS33_060-080_
S2_RPA connecti
on_01
B
A
OFF
ON
OFF
ON
C
D
Fig. 5.8.7-1 LP 33 Series 60 - 80 kVA - Access to the RPA board
Access to the RPA board
1 - Open the front door
“
A
”
of the
UPS cabinet.
2 - Remove the front panel
“
B
”
.
3 - Remove with appropriate tool
the metallic window
“
C
”
from
the metal screen
“
D
”
.
NOTE !
Put in place the
front panel
“B”
paying attention to
not damaging the
control bus cables.
C
D
LPS33_100-120_
S2_RPA connect
ion_01
B
A
Q2
O N
OFF
Q2
ON
OFF
Fig. 5.8.7-2 LP 33 Series 100 - 120 kVA - Access to the RPA board