5.3.2 Storage of the battery
In case of extended storage, when the delivery includes maintenance free batteries, keep in mind that
they are subject to auto-discharging process
.
To avoid permanent damages to the battery, you must observe the following instructions:
•
The storage time without charging the battery depends on the temperature of the storage ambient.
•
The optimal ambient temperature for the batteries is
20°C
(68°F).
For storage temperature higher than
20°C
(68°F), the storage time will decrease.
•
Each additional
10°C
(18°F) over the nominal temperature of
20°C
(68°F) will decrease the storage
time, without freshening charge, by half.
In case of a
maintenance free battery
, the storage time without charging the
battery
is
approximately:
6 months with storage temperature 20°C (68°F)
3 months with storage temperature 30°C (86°F)
2 months with storage temperature 35°C (95°F)
NOTE !
In case of
battery
storage pay
attention to:
FRAGILE
SENSITIVE
TO DAMPNESS
TO HEAT
SENSITIVE
TO FROST
SENSITIVE