Modifications reserved
Page 91/103
OPM_LPS_33E_60K_M12_2GB_V010.doc
Operating Manual
LP 33 Series 60-80-100-120 kVA / S2
8.2.8 Restore to normal operation after “EPO – Emergency Power Off”
NOTE !
Make sure the all units of the
Parallel System
to be status of the activation of “
EPO -
Emergency Power Off”
, i. e. Q1 closed, Q2 open and the
external battery fuses
connected.
View of the
synoptic diagram
, on all UPS units, after pressing
the push-button “
EPO - Emergency Power Off”
:
•
All
Contactors
are open.
•
Booster, Inverter
and
Static-Switch
shutdown.
1. Reset
the
push-button
“
EPO
”
.
Press
MUTE
key to reset
Alarm and Acoustical alarm
.
LED Alarm
remains lit.
2.
Reset the UPS by pressing “Inverter OFF” ( O ) key on all UPS units.
The load is supplied by the
mains
through the
automatic bypass
.
The
booster
starts automatically.
The
synoptic diagram
must display the status
“
LOAD SUPPLIED BY
AUTOMATIC BYPASS
”
.
3. Insert the inverter by pressing
“
Inverter ON
”
( I ) key on first UPS unit
.
In case of sufficient output power, the output will transfer to
Inverter
.
LED Alarm
turn Off and the
LED Operation
must be is lit.
The
Synoptic diagram
, on first UPS unit, must display the status
“
LOAD SUPPLIED BY INVERTER
”
.
4. Insert the inverter by pressing
“
Inverter ON
”
( I ) key on all other UPS units
.
Do not start the next
inverter
until the sequence of the previous one ends.
As soon as the output power of the
inverters
is sufficient to supply the
load
, the output of the units with
running
inverter
will transfer to
inverter
.
LED Alarm
turn Off and the
LED Operation
must be lit.
The
Synoptic diagram
, on all UPS units, must display the status
“
LOAD SUPPLIED BY INVERTER
”
.
END OF PROCEDURE