Modifications reserved
Page 68/103
OPM_LPS_33E_60K_M12_2GB_V010.doc
Operating Manual
LP 33 Series 60-80-100-120 kVA / S2
Example 5
:
An equivalent set of parameters for
Example 4
is.
Weekday
d1
- Saturday
d2
- Sunday
d3
- Monday
d4
- Tuesday
d5
- Wednesday
d6
- Thursday
d7
- Friday
ECO Mode START
00:00 00:00 18:00 18:00 06:00 09:00 12:00
ECO Mode STOP
23:59 20:00 18:00 06:00 06:00 09:00 13:00
ECO Mode START
ECO Mode STOP
The
ECO Mode
is active from 18:00 of weekday
d3 - Monday
until 06:00 of weekday
d4 - Tuesday
(as
indicated by the
ECO Mode STOP
time of weekday
d4 - Tuesday
).
The
ECO Mode STOP
time of weekday
d3 - Monday
has no effect as it is followed by the
ECO Mode STOP
time of weekday
d4 - Tuesday
.
It can be, without change of meaning, any time between 18:00 and 23:59.
Similarly, the
ECO Mode
is active from 18:00 of weekday
d4 - Tuesday
until 06:00 of weekday
d5 -
Wednesday
.
The
ECO Mode START
time of weekday
d5 - Wednesday
has no effect as it is preceded by the
ECO Mode
START
time of weekday
d4 - Tuesday
.
It can be, without change of meaning, any time between 00:00 and 06:00.
NOTE !
To avoid undesired
ECO Mode
operation, verify:
•
Date and Time (first page of parameter).
•
ECO mode
screen how many hours of
ECO Mode
operation have been selected for
each day of the week.
NOTE !
The
ECO Mode
will become active only if the load is supplied from the inverter.