When using a lifter, this installation procedure needs to be carried out by
maintenance personnel.
Figure 24: Installing the server into the rack rails
▶
Fully extend the rack rails until they lock in place (1).
The rack rails must click into place so that they can no longer be
moved.
▶
At a slight angle, lower the server onto the rear mounting point on the rack
rails (2).
▶
Fold down the server, while pressing the rail to the server side (3). Ensure
that all six rack mounting bolts are properly seated in the mounting points on
the rack rails and that the locking bars engage (4).
Basic hardware procedures
TX2550 M5
Upgrade and Maintenance Manual
73