9 Measurement
FLUXUS G801
9.2 Measurement settings
89
UMFLUXUS_G801V1-0EN, 2020-06-26
The following list items are available:
If a totalizer is activated during the measurement of the standard volumetric flow rate, the standard volumetric flow rate will
be totalized. The unit of measurement of the standard volumetric flow rate is displayed without any prefix.
9.2.2
Input of the damping factor
Each displayed measured value is a floating average of all measured values of the last x seconds, with x being the
damping factor. A damping factor of 1 s means that the measured values are not averaged because the measuring rate is
approx 1/s. The default value of 10 s is appropriate for normal flow conditions. Values which fluctuate strongly due to a
higher flow dynamic require a higher damping factor.
• Select the program branch
Output Options
.
• Press ENTER until the menu item
Damping
is displayed.
• Enter the damping factor.
• Press ENTER.
• Press BRK to return to the main menu.
9.2.3
Installation of an output
If the transmitter is equipped with outputs, they have to be
installed and activated before they can be used:
• assignment of a measuring channel (source channel) to
an output (if the transmitter has more than one measuring
channel)
• assignment of the physical quantity (source item) to be
transmitted to the output by the source channel, and of
the signal properties
• definition of the output behavior in case no valid
measured values are available
• activation of the installed output in the program branch
Output Options
In the following, the configuration of an analog output is described.
• Select the menu item
Proc. outputs
.
• Press ENTER.
list item
display of the operating volumetric flow rate
display of the standard volumetric flow rate
(none)
without prefix, e.g.,
m³/h
without prefix, e.g.,
m³/h
’ ’/’N’
without prefix, e.g.,
m³/h
with prefix N, e.g.,
Nm³/h
’ ’/’S’
without prefix, e.g.,
m³/h
with prefix S, e.g.,
Sm³/h
’A’/’S’
with prefix A, e.g.,
Am³/h
with prefix S, e.g.,
Sm³/h
Output Options\...\Damping
SYSTEM settings
Proc. outputs
Install Output
Enable
Source chan.
Source item
see annex A
Notice!
The settings will be stored at the end of the dialog. If the menu item is quit by pressing BRK, the changes will not be
stored.
Special Funct.\SYSTEM settings\Proc. outputs