Mixture of propylene glycol (Mpg)
–
Correction factor
If a mixture of propylene glycol is used instead of pure water, it causes a change in the performance of the unit. Remember that the choice of
the correct percentage of glycol to be used is determined taking into consideration not only the temperature of the chilled fluid, but also the
temperature of the outside air and/or the environment near the water circuit pipes.
For correct data, please use the correction factor indicated in the following table:
Mpg
0 (pure water)
Mpg 20% (*)
Mpg 30% (*)
Mpg 40% (*)
Freezing point
0°C
-7,4°C
-13,1°C
-21,5°C
CcCF
1
0,950
0,9375
0,925
CcCF: Cooling capacity correction factor
(*): For mixtures of propylene glycol (Mpg) over 20% or for other types of anti-freeze solutions, please contact the manufacturer,
for further technical checks.
For all of the models in the EKS Business and High Efficiency series, the following tables show the minimum and maximum evaporator water flow
values, to be taken into consideration and evaluated during the sizing of pumps, storage tanks and water circuit. These values must be considered
as operation limits. If the installation or type of use requires working outside these limits, the manufacturer must carry out a technical check to
ensure the correct and efficient working of the chiller.
Evaporator
water flow
[m
3
/h]
EKS BS - Business
090-3-1
100-3-1
110-3-1
120-3-1
120-4-2
140-4-2
160-4-2
180-6-2
200-6-2
220-6-2
240-6-2
Minimum
31,7
34,0
36,3
38,1
44,4
48,1
51,2
57,9
69,2
72,5
75,5
Maximum
47,5
51,1
54,5
57,2
66,6
72,2
76,9
86,8
103,9
108,8
113,3
Evaporator
water flow
[m
3
/h]
EKS HE
–
High Efficiency
055-2-1
060-2-1
070-2-1
080-4-2
090-4-2
100-4-2
110-4-2
120-4-2
140-4-2
160-4-2
180-6-2
Minimum
21,6
24,2
26,9
29,9
33,8
37,0
43,2
48,4
53,7
62,2
71,0
Maximum
32,4
36,3
40,3
44,9
50,7
55,6
64,9
72,6
80,6
93,3
106,5
2.3
TECHNICAL DATA
(1) Reference conditions: performance based on: Condenser air intake temperature 35°C
–
Evaporator water temperature IN/OUT = 12/7°C - Fluid: pure water
–
Condensing coil:
Microchannel
(2) Reference conditions: sound power level in compliance with ISO 3744
–
Sound pressure level (average) at 10-meter distance, unit in a free field on a reflective surface; non-binding
value obtained from the sound power level.
EKS BS - Business
090-3-1 100-3-1 110-3-1 120-3-1 120-4-2 140-4-2 160-4-2 180-6-2 200-6-2 220-6-2 240-6-2
Cooling capacity
(1)
[kW]
244
262
280
294
342
371
395
446
533
559
582
Compressor power input (tot.)
(1)
[kW]
81,6
90,6
99,8
108,0
104,4
122,8
139,6
174,0
177,4
195,2
213,6
Fan power input (tot.) ST version
[kW]
6,0
6,0
6,0
6,0
9,1
9,1
9,1
9,1
12,1
12,1
12,1
Fan power input (tot.) LN / SL version
[kW]
8,4
8,4
8,4
8,4
12,6
12,6
12,6
12,6
16,8
16,8
16,8
Supply
V/ph/Hz 400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
Total installed power (ST version)
[kW]
116
125
134
143
156
174
191
228
250
267
285
Maximum absorbed current
Full load (ST version)
[A]
212
229
246
263
285
319
354
416
458
492
527
Total sound power (ST version)
(2)
[db(A)]
91
92
94
94
92
94
96
93
95
97
98
Total sound pressure (ST version)
(2)
[db(A)]
58
60
61
62
60
62
63
61
63
64
65
Total sound power (LN version)
(2)
[db(A)]
87
88
90
90
88
90
92
89
91
93
94
Total sound pressure (LN version)
(2)
[db(A)]
54
56
57
58
56
58
59
57
59
60
61
Total sound power (SL version)
(2)
[db(A)]
85
86
88
88
86
88
90
87
89
91
92
Total sound pressure (SL version)
(2)
[db(A)]
52
54
55
56
54
56
57
55
57
58
59