EKS/HE High Efficiency
EKS/BS Business
–
EKS/HE High Efficiency
Mixture of ethylene glycol (Meg)
–
Correction factor
If a mixture of ethylene glycol is used instead of pure water, it causes a change in the performance of the unit. Remember that the choice of the
correct percentage of glycol to be used is determined taking into consideration not only the temperature of the chilled fluid, but also the
temperature of the outside air and/or the environment near the water circuit pipes.
For correct data, please use the correction factor indicated in the following table:
Meg
0 (pure water)
Meg 20% (*)
Meg 30% (*)
Meg 40% (*)
Freezing point
0°C
-8,9°C
-15,8°C
-24,8°C
CcCF
1
0,980
0,974
0,965
CcCF: Cooling capacity correction factor
(*): For mixtures of ethylene glycol (Meg) over 20% or for other types of anti-freeze solutions, please contact the manufacturer,
for further technical checks.
Operating area
Operating at partial load
SP
–
Special configuration (available on request)
T air: Outdoor air temperature [C°]
LWT: Evaporator outlet temperature [C°]
MEG: Mixture of ethylene glycol
Operating area with Desuperheater
T out: Desuperheater water outlet temperature [C°]
LWT: Evaporator outlet temperature [C°]
MEG: Mixture of ethylene glycol
Operating area with Heat Recovery
T out: Total recovery exchanger water outlet temperature [C°]
LWT: Evaporator outlet temperature [C°]
MEG: Mixture of ethylene glycol
Pure water
T air
[°C]
LWT [°C]
Evaporator
COOLING OPERATION LIMITS
Pure water
Pure water
LWT [°C]
Evaporator
LWT [°C]
Evaporator
T out
[°C]
T out
[°C]
DESUPERHEATER OPERATION LIMITS
HEAT RECOVERY OPERATION LIMITS