5.0 START-UP AND CONTROL PANEL
After identifying the cause of the alarm and making the consequent checks, modifications or resets, please follow the procedure to reset the
alarm:
-
The ALARM button is flashing. This means that at least one alarm is active
-
Press the ALARM button to access the alarm screen
-
Use the UP and DOWN keys to move to the screen showing the alarm to be reset
-
To reset the alarm displayed, press the ALARM button again
-
If the ALARM button is pressed for at least 3 seconds, all of the active alarms are reset
-
If the cause of the alarm hasn’t been
completely resolved, it will be signalled again after reset
-
To return to the main menu of the microprocessor, simply press ESC
5.4.2 ALARM TABLE
The following table shows a complete list of the alarms that can be found on the microprocessor with a code of reference, an explanation of the
fault and the reset system (before resetting the alarm, it is necessary to eliminate the cause):
In the event of a fault, the microprocessor
“Alarm”
button will flash. This means that there are faults compared to normal operation. To display
the alarm, refer to the procedure in the previous paragraph.
Code
Description
Reset
Action
Delay
AL001
Unit - Remote alarm
M
Switch the unit Off
No
AL002
Unit - Error in the number of retain memory writings
M
None
No
AL003
Unit - Error in retain memory writings
M
None
No
AL004
Unit - User inlet water temperature probe
A
Switch the unit Off
10s
AL005
Unit - User outlet water temperature probe
A
Switch the unit Off
10s
AL007
Unit - External temperature probe
A
Compensation Off
10s
AL008
Unit - User pump 1 overload
1)
M
None
No
AL009
Unit - User pump 2 overload
1)
M
None
No
AL012
Unit - Flow switch alarm with user pump 1 active
1)
M
Switch the unit Off
Parameter A034/A035
AL013
Unit - Flow switch alarm with user pump 2 active
1)
M
Switch the unit Off
Parameter A034/A035
AL016
Unit - User pump group alarm
M
Switch the unit Off
No
AL018
Unit - User 1 pump maintenance
A
None
Parameter A00
AL019
Unit - User 2 pump maintenance
A
None
Parameter A02
AL022
Unit - High chilled water temperature
A
None
Parameter A021/A022
AL100
Circuit 1 - Alarm discharge probe pressure
A
Stop circuit 1
10s
AL101
Circuit 1 - Alarm suction probe pressure
A
Stop circuit 1
10s
AL102
Circuit 1 - Alarm discharge probe temperature
A
Stop circuit 1
10s
2)
AL103
Circuit 1 - Alarm suction probe temperature
A
Stop circuit 1
10s
AL105
Circuit 1 Envelope - High compression ratio
A
Stop circuit 1
Parameter Cb17
AL106
Circuit 1 Envelope - High discharge pressure
M
Stop circuit 1
Parameter Cb17
AL108
Circuit 1 Envelope - High suction pressure
A
Stop circuit 1
Parameter Cb17
AL109
Circuit 1 Envelope - Low compression ratio
A
Stop circuit 1
Parameter Cb17
AL110
Circuit 1 Envelope - Low differential pressure
A
Stop circuit 1
Parameter Cb18
AL111
Circuit 1 Envelope - Low discharge pressure
A
Stop circuit 1
Parameter Cb17
AL112
Circuit 1 Envelope - Low suction pressure
A
Stop circuit 1
Parameter Cb17
AL113
Circuit 1 Envelope - High discharge temperature
A
Stop circuit 1
Parameter Cb17
AL114
Circuit 1 EVD - Low SH
M
Stop circuit 1
Parameter B024
AL115
Circuit 1 EVD - LOP
A
Stop circuit 1
Parameter B025
AL116
Circuit 1 EVD - MOP
A
Stop circuit 1
Parameter B026
AL117
Circuit 1 EVD - High condensing temperature
A
Stop circuit 1
Parameter B029
AL118
Circuit 1 EVD - Low suction temperature
A
Stop circuit 1
Parameter B031
AL119
Circuit 1 EVD - Motor error
M
Stop circuit 1
No
AL120
Circuit 1 EVD - Emergency closing
A
Stop circuit 1
No
AL121
Circuit 1 EVD - Setting out of bound
A
Stop circuit 1
No
AL122
Circuit 1 EVD - Settings range error
A
None
No
AL123
Circuit 1 EVD - Offline
A
Stop circuit 1
No
AL124
Circuit 1 EVD - Low battery
A
None
No
AL125
Circuit 1 EVD - EEPROM
A
None
No
AL126
Circuit 1 EVD - Incomplete valve closing
A
Stop circuit 1
No
AL127
Circuit 1 EVD - Firmware not compatible
A
Stop circuit 1
No
AL128
Circuit 1 EVD - Configuration error
A
Stop circuit 1
No
AL165
Circuit 1 - Alarm freeze evaporation temperature
M
Stop circuit 1
Parameter A041
AL166
Circuit 1 - Compressor 1 maintenance
A
None
Parameter Ca00
AL167
Circuit 1 - Compressor 2 maintenance
A
None
Parameter Ca02
AL168
Circuit 1 - Compressor 3 maintenance
A
None
Parameter Ca04
AL169
Circuit 1 - Alarm condensing temperature probe
A
Stop circuit 1
10s
AL170
Circuit 1 - Source fan 1 maintenance
A
None
Parameter E006