Device Profile Area
CAN-CBX-THERMO
Manual • Doc.-No.: C.3034.21 / Rev. 1.2
Page 93 of 123
8.10.9 AI Status (6150
h
)
Index
Sub-
index
Description
Value range
Default
Data type
Access
6150
h
0
Number_of_entries
4
4
unsigned 8
ro
1
AI_status_1
0...5
-
unsigned 8
ro
2
AI_status_2
0...5
-
unsigned 8
ro
3
AI_status_3
0...5
-
unsigned 8
ro
4
AI_status_4
0...5
-
unsigned 8
ro
Description of the variable AI_status_x (x = 1...4):
These variables return the state of the corresponding analog input channel.
Bit:
7
6
5
4
3
2
1
0
Meaning:
reserved
*
3)
not supported *
3)
reserved
*
3)
Negative
Overload
Positive
Overload
Not Valid
*
3)
These bits are always returned as ‘0’.
Value range:
Description
Negative overload limit
Positive overload limit
thermocouple type J
-210
¶
C
1212
¶
C
thermocouple type K
-200
¶
C
1400
¶
C
thermocouple type L
-200
¶
C
908
¶
C
thermocouple type N
-250
¶
C
1315
¶
C
thermocouple type R
-50
¶
C
1782
¶
C
thermocouple type S
-50
¶
C
1792
¶
C
thermocouple type T
-250
¶
C
405
¶
C
thermocouple type B
50
¶
C
1835
¶
C
thermocouple type U
-200
¶
C
605
¶
C
voltage measurement
at default setting
- 0.512 V
+ 0.512 V