Manufacturer Specific Profile Area
Manual • Doc.-No.: C.3034.21 / Rev. 1.2
CAN-CBX-THERMO
Page 108 of 123
8.11.8 Calibration Delta Temperature (2422
h
)
Index
Sub-
index
Description
Value range
Default
Data type
Access
2422
h
0
Number_of_entries
4
4
unsigned 8
ro
1
delta_calibration_temp_1
0...FFFF
h
0
unsigned 16
rw
2
delta_calibration_temp_2
0...FFFF
h
0
unsigned 16
rw
3
delta_calibration_temp_3
0...FFFF
h
0
unsigned 16
rw
4
delta_calibration_temp_4
0...FFFF
h
0
unsigned 16
rw
Description of the variable delta_calibration_temp_x:
The ADS1255 performs a self-calibration, if the temperature of the PCB (2420
h
) deviates more than the
value specified in delta_calibration_temp_x from the last_calib_temp_x .
Value
delta_calibration_temp_x
Function
0
no automatic self-calibration at deviation of the temperature
0001
h
...FFFF
h
automatic self-calibration at exceeding the allowed deviation of the
temperature
The value is coded as:
Temperature C
Int
Value
d
[
]
_
°
=
16
256
Example:
delta_calibration_temp_1 = 0180
h
=> Temperature deviation = 1.50
¼
C