Manufacturer Specific Profile Area
CAN-CBX-THERMO
Manual • Doc.-No.: C.3034.21 / Rev. 1.2
Page 113 of 123
8.11.10.2 Disable Cold Junction Compensation (2425
h
)
INFORMATION
Object 2425
h
is only intended for test and calibration purposes!
Index
Sub-
index
Description
Value range
Default
Data type
Access
2425
h
0
Ignore_ADT7320
0,1
0
unsigned 8
rw
Description of the parameter Ignore_ADT7320:
By means of this parameter the automatic cold junction compensation can be disabled. Only if this
parameter is disabled the estimated junction temperature can be set manually.
1. If the value is set to ‘1’, the variable “estimated_junction_temp_X” (index 2423
h
, sub-index 1...4)
is no longer supplied by the firmware. The previous value is kept.
2. Now the variables “estimated_junction_temp_X” (index 2423
h
, sub-index 1...4) can be set
manually. If they are set for example to the value ‘0’, than there will be no compensation.
Value range:
Ignore_ADT7320
Meaning
0
Automatic cold junction compensation is enabled
(object 6150
h
can not be written)
1
Automatic cold junction compensation is disabled
(object 6150
h
, sub-index 1..4 can be written)