CANopen-Firmware
Manual • Doc.-No.: C.3034.21 / Rev. 1.2
CAN-CBX-THERMO
Page 52 of 123
8.7 Reading the Analog Values
8.7.1 Messages of the Analog Inputs
The transmission types for the analog inputs are described in the following:
s
acyclic, synchronous: The transmission is initiated if a SYNC-message has been received (PDO-
transmission type 0) and data has changed.
s
cyclic, synchronous: The transmission is initiated if a defined number of SYNC-messages have
been received (PDO-transmission type 1...240).
s
event controlled, asynchronous: The transmission is initiated if the state of selected inputs has
changed (PDO-transmission type 254, 255).
8.7.2 Supported Transmission Types Based on DS-301
Transmission
Type
PDO-Transmission
supported by
CAN-CBX-
THERMO
cyclic
acyclic
synchro-
nous
asynchro-
nous
RTR
0
X
X
x
1...240
X
X
x
241...253
reserved
-
254
X
x
255
X
x