Technical Data
CAN-CBX-THERMO
Manual • Doc.-No.: C.3034.21 / Rev. 1.2
Page 13 of 123
3. Technical Data
3.1 General technical Data
Power supply voltage
nominal voltage:
24 V/DC
input voltage range:
24 V ±20%
current consumption (24 V, 20
l
C): typical: 90 mA
Connectors
24V
(4-pin line connector with spring-cage connection, X400 )
- 24V-power supply voltage
InRailBus (5-pin CAN-CBX-TBUS connector, Phoenix Contact, X101)
- CAN interface and power supply voltage via InRailBus
S1...S4
(12-pin line connector with screw connection, X500)
- 4 high resolution thermocouple interfaces
CAN
(5-pin line connector with spring-cage connection, X400)
- CAN interface
Only for test and programming purposes:
X200
(6-pin connector) - the connector is placed inside the case
Temperature range
-20
l
C ... +60
l
C ambient temperature
Humidity
max. 90%, non-condensing
Protection class
IP20
Pollution degree
maximum permissible according to DIN EN 61131-2:
Pollution Degree 2
Housing
Phoenix “MEMAX” plastic housing for carrier rail mounting NS35/7,5
DIN EN 60715
Dimensions
width: 22.5 mm, height: 99 mm, depth: 114,5 mm
(including mounting rail fitting and connector projection, without
mating plug)
Weight
145 g
Table 1: General technical data