Manufacturer Specific Profile Area
CAN-CBX-THERMO
Manual • Doc.-No.: C.3034.21 / Rev. 1.2
Page 115 of 123
8.11.11 Channel Temperature Offset (2507
h
)
Index
Sub-
index
Description
Value range
Default
Data type
Access
2507
h
0
Number_of_entries
4
4
unsigned 8
ro
1
channel_temp_offset_1
8000
h
...7FFF
h
0
integer 16
rw
2
channel_temp_offset_2
8000
h
...7FFF
h
0
integer 16
rw
3
channel_temp_offset_3
8000
h
...7FFF
h
0
integer 16
rw
4
channel_temp_offset_4
8000
h
...7FFF
h
0
integer 16
rw
Description of the variable channel_temp_offset_x (x = 1...4)
The variable channel_temp_offset_x contains the temperature offset of the cannel x in m
Ä
C.
It is used for the compensation of the temperature drop between local PCB-temperature (local_
temperature, 2420
h
) and real connector temperature.
The corrected local temperature value of channel x is calculated as:
local_temperature_corr_x = local_temperature - channel_temp_offset_x
(+)
Example:
channel_temp_offset_1 = 1234
d
=> 1234 m
Ä
C => 1.234
Ä
C